No Heat Service Call Zone Valve End Switch

  Рет қаралды 60,582

The HVAC Hacker

The HVAC Hacker

5 жыл бұрын

I am on a no heat service call. I find the zone valve end switch even though pressed in by zone valve motor isn't closing the circuit to bring on the boiler.

Пікірлер: 152
@styldsteel1
@styldsteel1 2 жыл бұрын
Thank you for providing the clearest most concise step by step instructional video. One gets tired of HVAC specialists trying to clean my clock.
@swiftjeff
@swiftjeff 5 жыл бұрын
You dropped the screwdriver and I said "ha! I'm not the only one!". Repairing janitorial equipment I drop stuff every day. My hands don't always work right when the mind is everywhere else at once.
@alabama7636
@alabama7636 5 жыл бұрын
Nice to see a professional who knows that appearance is part of a quality repair.
@jasonbrus1273
@jasonbrus1273 5 жыл бұрын
I was on a roof working on a 40 ton intellapack unit today my helper dropped some screws I told him he needed to go back to school... He didn't get it I thought it was funny. Great vids keep it up.
@keno8503
@keno8503 5 жыл бұрын
Another great job, learning a lot, keep the videos coming!
@zhang32796
@zhang32796 5 жыл бұрын
Keep up with the good work! Thanks for sharing
@andreagate542
@andreagate542 3 жыл бұрын
Hi im new the boiler hydronics game and have a question regarding the end switch.....does the 24v that passes through this end switch first originate from the boiler,,then once the end switch closes does that same 24v travel back down to the boiler to through the safeties and on to the gas valve(regarding this boiler you are working on) ??? Thanks for sharing!!!!
@aircooledtx
@aircooledtx 5 жыл бұрын
Good repair,on Zone .
@markneuman2686
@markneuman2686 4 жыл бұрын
Hi, my zone valve stopped working a few days ago. The motor makes a buzzing sound all the time, so I tested the voltage and it shows constant 6V whether there is or not a call for heat. I checked the transformer it seemed to be fine but just in case I replaced it but the issue did not go away. I also switched my Ecobee thermostats around, same issue. I replaced the wire going to the thermostat, same issue. I have a 2 zone heating and cooling system with a boiler. Ecobees are connected with Rc, Y, G and C wire from a handler and Rh from transformer going to both Ecobees and coming back as Ws with each connected to the respective zone valve motor. The the other zone valves motor wires are connected together to the negative wire from the transformer. Just in case I checked the relay on the zone valve and it is fine. At this point I have 0 ideas what could be wrong and a bit short on money to call a professional. Could you please let me know what could be wrong?
@adrianthoroughgood1191
@adrianthoroughgood1191 2 жыл бұрын
I have a zone valve passing water when it should be closed. I bought a new valve set and first tried changing just the actuator. I tried that for a couple of weeks but it was still passing water. So I replaced the valve fully, so new valve and the new actuator. It is still passing water. When the zone call for heat is on the motor starts and opens the valve and the boiler activates as it should. When I turn it off the spring closes the valve and the boiler shuts off. I can see that the actuator mechanism has moved back to about where it should be for closed. But if I turn on another zone then water still passes through the faulty one. Even with a brand new valve. I have double checked that the flow direction as labelled on the valve is correct with regards to the flow outlet from the boiler, plus it's the same as all the others anyway. I don't understand what's wrong. Is my new valve faulty too? Do I need to return it and buy a different one? The only difference with the other zone valves that work fine is that they are mounted vertically and the faulty one is horizontal. That shouldn't be a problem should it?
@hsdoor414
@hsdoor414 4 жыл бұрын
Very nice work. But the camera cannot really shot the working detail. Your words can help me to follow! Really helpful! Keep things up! Thank you once again to resolve my wife ‘s complaint.
@sldulin
@sldulin 5 жыл бұрын
I'm not in the field but enjoy your vid's because you are obviously knowledgeable, methodical, purposeful. Would appreciate just a little more intro to your diagnostics when you walk into a situation like this. I'm distracted by "wow, nice pool!" while you have already started thinking critically about the problem, how to narrow it down.
@jxtdenco6984
@jxtdenco6984 3 жыл бұрын
My Honeywell zone won't shut off unless I tap the motor. As soon as I do that (with the thermostat turned down all the way), it'll shut off. Do I need to replace the motor? And I am a little confused as to how which voltage motor I would need. How do I tell by looking at the valve? All of the motors may have been replace at one time or another and I don't know what voltage the motors should have.
@eugeneshealthproject
@eugeneshealthproject 5 жыл бұрын
Why do the Honeywell end switch valves stick open? Only two years old.
@mik693
@mik693 Жыл бұрын
Links or information on the screwdriver and led light used in the video ?, please
@italyworrier
@italyworrier 5 жыл бұрын
Hello from Bergen County !! great vid man !! keep em up . fuck any one who dont like them !!
@roykressin8229
@roykressin8229 4 жыл бұрын
what caused the click around
@4825sardis
@4825sardis 2 жыл бұрын
I have 6 zone valves, 3 won't open via thermostat. But if I manually lock them open the heat goes through because other 3 zone valves work fine with their thermostats and the boiler and pump work. I took the thermostat off the wall and couldn't get a spark from touching the 2 wires together. Where could the problem be? Sounds to me like there's no signal getting through in the wiring.
@throttlebottle5906
@throttlebottle5906 5 жыл бұрын
I don't recall if that model is spring loaded for the actual valve position or not. if it's not a tight failing valve will eat the gearing in no time and you'll be back....
@BillyN31
@BillyN31 Жыл бұрын
Just had the same call last week. Zone was for the indirect tank so I just swapped it for the 2nd floor till we got the head delivered
Crucial Knowledge To Heat Pump Troubleshooting
14:15
Jersey Mike HVAC
Рет қаралды 23 М.
NO HEAT. SERVICE CALL # 5  3 WIRE TACO VALVE FAILED. TROUBLESHOOTING
7:55
Alex The Handyman
Рет қаралды 10 М.
Why Is He Unhappy…?
00:26
Alan Chikin Chow
Рет қаралды 17 МЛН
Double Stacked Pizza @Lionfield @ChefRush
00:33
albert_cancook
Рет қаралды 91 МЛН
Motorised Valve Fault Finding
9:08
Skill Builder
Рет қаралды 24 М.
Inside a clever Honeywell boiler wiring centre and a 3-way valve.
23:02
Hot Water Baseboard Cold Zone Valve Clicking Repair
17:27
The HVAC Hacker
Рет қаралды 3,9 М.
5 most common Boiler Problems 🔥🛠️
9:44
The HVAC Dope Show
Рет қаралды 8 М.
Honeywell zone valve motor head & end switch replacement
15:44
Homeowner DIY
Рет қаралды 347
Installing Zone Valves Soldering And Wiring
25:34
The HVAC Hacker
Рет қаралды 17 М.
How a Zone Valve Works - Hot Water Heating
11:03
Andrew W
Рет қаралды 348 М.