sir all para meter vfd mai kitne dale jate hai vfd ran karane क liye
@satendraelectrical51506 ай бұрын
For this drive... 15-20 parameter Dale jate h jo basic program group me aate h... 1. Motor NP volts 2. Motor NP Hz 3. Motor OL current 4. Minimum Frequency 5. Maximum frequency 6. Start source (Auto/manual) 7.Stop mode 8. Speed reference 9. Accel time 10. Decel time 11. Reset to default 12. Auto mode. 13. Motor OL retention. Etc. Apart from this.. Advance program group parameter bhi use hote h.. as per requirement.
@imranamin2114 Жыл бұрын
Sr. Grond fult o13 ay raha he ap bta sakty he kis pramitr ka fult he
@satendraelectrical5150 Жыл бұрын
Phase U to GND. Check the wiring between the drive and motor. Check motor for grounded phase. Replace F39 Phase V to GND drive if fault cannot be cleared. A PowerFlex AC drive detects a ground fault when the output currents between two phases differ by more than 25% of the drive's rated current.
@marcustyrell43156 ай бұрын
How do I speed up the rotation on a wipeout wheel?
@satendraelectrical51506 ай бұрын
Use P38 (Speed source)
@amarchandchoudhary88706 ай бұрын
Vfd 40 hp power flex 400 me auto rest ho rahi h to usko sahi kesi khiya ja sakthi h
@satendraelectrical51504 ай бұрын
Change the mode from Auto-reset/run to Non -resettable/ Manual reset.
@avijit2586 Жыл бұрын
What is purge frequency in this Drive function
@avijit2586 Жыл бұрын
Have any time delay setting in motor Overload setting ?
@satendraelectrical5150 Жыл бұрын
Purge command is like a command to takes precedence over a stop command from the common port. The terminal block 5 port is for Digital input ( purge). A purge input starts the drive at a programmable purge speed regardless of the selected start source. In another way we can say that purge can occur and is operational at any time whatever the drive is running or stoped.
@satendraelectrical5150 Жыл бұрын
@@avijit2586 yes we can change... Delay time
@avijit2586 Жыл бұрын
@@satendraelectrical5150 From which parameter code?
@abdulkadirshaikh33103 жыл бұрын
Undervoltege ka folt 4 ka kya solution he
@satendraelectrical51502 жыл бұрын
For this... Monitor the incoming AC line for low voltage or line power interruption.
@anilbhogil49833 жыл бұрын
How to change motor direction by using keypad..?
@satendraelectrical51506 ай бұрын
To enable reverse operation, use A166 in program
@RanjeetKumar-oh4on2 жыл бұрын
Keypad se chalane ke liye aur pot se connection kar chalane ke liye parameter dalne ke liye
@satendraelectrical51502 жыл бұрын
You can use 0-11 and use code (2) for manual mode.
@satendraelectrical51502 жыл бұрын
And also use terminal at 50 and 55 where we use pot at terminal 50 (+10) and 55 ( common).
@rajeshdeep26263 жыл бұрын
Bro... Fault no 6 motor stalled proplem how solved
@satendraelectrical51502 жыл бұрын
If fault no 6 showing then can do set by perameter A 089 current limit. Increase [Accel Time x] or reduce load so drive output current does not exceeded.
@shashikapoor65562 жыл бұрын
VFD out put voltage nhi aa rahi hai kya Karn ho sakta hai
@satendraelectrical5150 Жыл бұрын
Check input connection and Parameters of vtd as per motor.
@electricallearning88632 жыл бұрын
Sir how can we see energy meter reading in this
@satendraelectrical51502 жыл бұрын
Go parameter b015 for drive kWh reading.
@subhankarroy91473 жыл бұрын
UV phase shot fault 41 is showing what to do
@satendraelectrical51502 жыл бұрын
If this showing you can check the motor and drive output terminal wiring for a shorted condition.
@KundanSingh-ds4dy8 ай бұрын
Isko auto manual kese chlaye
@satendraelectrical51506 ай бұрын
Use parameter P042 ( Auto mode) P036 ( start source) and hand mode command comes from the internal keypad.
@CarlosDejesus-c6f4 ай бұрын
Cómo ponerlo que el amperaje se me vea en la pantalla principal
@subhashsaini34552 жыл бұрын
Motar rpm kasa dala
@satendraelectrical5150 Жыл бұрын
Go in program group P032 for motor frequency Hertz, not RPM.
@shohelloveisendless84172 жыл бұрын
Boss tell me how to make PTC connection
@amarchandchoudhary88706 ай бұрын
Meri ko vfd auto rest honi ki vaja jan na h
@satendraelectrical51504 ай бұрын
If there are AR-Types faults occur, VFD can auto restart itself.
@trilokiflstudiomobile7012 Жыл бұрын
Sar ji fold cold ka bare mein bataiye fault Mein kya-kya code Aata Hai Kiska hai
@satendraelectrical51506 ай бұрын
There are many faults code with their meaning like.. 1. F2- Auxiliary input 2. F3- power loss 3. F4- Under voltage 4. F5- over voltage 5. F6- motor stalled 6. F7- motor overload 7. F8- heatsink over temp . . . F13 - ground fault F33 to F40 - phase to ground fault F41 to F 43- phase to phase fault F64- drive overload F94- function loss And for more complete fault, check manual..
@jagadeesh90033 жыл бұрын
Useful information
@satendraelectrical51503 жыл бұрын
Thanks 😊
@Jskdjdmdmz3 жыл бұрын
PowerFlex 400- How can we Program Unlock A198 , if it is locked on Option 3 , Pls guide
@satendraelectrical51506 ай бұрын
Use 0 for unlocked in A198.
@samirmammadov40733 жыл бұрын
Dear Friend watched you video how you set up Allen Bradley FLEX 400 You can help me set it up on the compressor Bottarini I was Thankful to you
@yaakash1504 жыл бұрын
Very good
@satendraelectrical5150 Жыл бұрын
Thanks
@Mrownerrdxj28372 жыл бұрын
Sir powerflex f500 ki user manual koren mein pdf hai to English mein pdf ka link send kar dein
Drive 100 set dekar start karne se start ho raha hai aur band ho ja raha hai kya problem ho sakta hai
@abhaykarmakar81482 жыл бұрын
Fault code d004and d003 batya
@satendraelectrical51502 жыл бұрын
Fault code D003 is power loss and D004 is under voltage so for Both Fault code D003 and D004 you can Monitor the incoming AC line for low voltage or line power interruption. If there is incoming power interruption check what problem? May be drive not get proper power supply.