SELECTIVITY, DISCRIMINATION and CO-ORDINATION of electrical devices for protection

  Рет қаралды 20,104

LEARN ELECTRICS

LEARN ELECTRICS

Күн бұрын

Пікірлер: 57
@learnelectrics4402
@learnelectrics4402 3 жыл бұрын
SEE ALL OUR VIDEOS To view a list of all our LearnElectrics videos, click on the link below. There are many videos on many electrical topics including Installation, Part P, 18th Edition, Testing, Certification, Lighting, Sockets, Ring Circuits, Calculations and much more. kzbin.info/door/YaJQnpO4XAp0yCgqzMkmfA
@barashah1171
@barashah1171 2 жыл бұрын
thank you sir....for extremly useful content.
@johanburger4454
@johanburger4454 9 ай бұрын
Great video mate. I have a question regarding fault currents, particularly PSCC. How would you coordinate these in a case when the current is so high that both devices operate within 0.1 secs. I have a 160A Bs882 fuse supplying a 125A type B circuit breaker. These are in coordination regarding overload protection however not with short circuit. Do i have to select an upstream device that simply doesn't "see" the fault current and thereby forcing the downstream device to operate first?I would like to avoid this as by having an extremely high rated protective device upstream, it would then force me to upgrade the cable size.
@chelsea08FC
@chelsea08FC Жыл бұрын
This guy is the master of educating. He already helped me pass my 18th edition 👊🏾
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Well done my friend. You passed because YOU wanted to pass. If the videos helped in a small way that is good too. Keep learning, its a good trade. Dave.
@TheZohri
@TheZohri 5 ай бұрын
I wish I had you as my tutor for the whole course. The way you explain stuff makes it so easy to understand. As such, I thank you a million times over.
@learnelectrics4402
@learnelectrics4402 4 ай бұрын
That's really nice to know. I do actually miss face to face teaching now. If you can get interested students, it is actually a pleasure to pass on knowledge. I want you to be better than me, to take the industry into the future, Dave.
@michaelviney3737
@michaelviney3737 3 жыл бұрын
I find your videos very very good. Thank you. Your answer to another subscriber on discrimination between house and garage using RCBOs was just what I was after. I was thinking of treating my outbuilding as a separate supply via an Henry( Isco ) block and 60 amp switch fuse. The outbuilding having it’s own distribution box with RCD and mcbs. This provided discrimination with the 100amp supply fuse, but left the swa cable to the outhouse without RCD protection. So adding an extra RCD would have solved that one. However….happy days change the 25 year old cu for a new Hager rcbo scheme complete with surge protection. BTW. …..I’m not changing my terminology!!. I spent a couple of years designing protection systems on the electricity board’s 132 kv to 66kv to 33kv networks……it’s DISCRIMINATION. Who dreams up these changes? We’ll be calling the earth wire cpc next!
@learnelectrics4402
@learnelectrics4402 3 жыл бұрын
Ha ha. CPC? As if. I blame it on the white coats, the boffins that are all listed at the front of the Regs book. I tell my guys that if they say the earth in the switch or call the phase the live, we on the tools will still understand. It will take generations to work its way out of our genes. Thanks for watching. Dave.
@no_short_circuit
@no_short_circuit 3 жыл бұрын
Thanks again for explaining a potentially tricky topic in simple language. The way you use graphics and examples in your videos is invaluable to me.
@learnelectrics4402
@learnelectrics4402 3 жыл бұрын
Thank you so much. This is exactly the same way I teach in the classroom. Keep it simple and keep the students interested. Everybody wants to learn. Thanks for watching.
@venkybvcits6715
@venkybvcits6715 2 жыл бұрын
It's very easy to understand while giving your explanation. Thank you
@learnelectrics4402
@learnelectrics4402 2 жыл бұрын
Much appreciated, thank you. Dave.
@Britishbaptist
@Britishbaptist Жыл бұрын
Thank you for this very clear explanation
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Very welcome, thanks. Dave.
@jimhughsTV
@jimhughsTV 3 жыл бұрын
Really nice explanation, addressing some issues that I seem to go around in circles with. And here's an example..... looking at an existing install, the main CU has a distribution circuit to a garage CU. The main CU is a very conventional 2 RCD split board, with the MCB to the sub-board of RCD bank No.2, so a 30mA type AC RCD. Sub board in the garage has another 30mA RCD isolator and 2 circuits. So no selectivity between the RCDs. The cable between the main and sub starts life as twin and earth and connects to SWA at an external junction box before disappearing underground for a short run to the garage. Providing selectivity in compliance with 536.4.1.4 note ii Selectivity in case of residual currents, might sound straightforward, as in, just pop a 100mA RCD at the source of the distribution circuit, but part of this cable run is twin and earth within the fabric of the building. Regulation 415.1 and 522.6.202 to 204 present a strong case for keeping 30mA RCD at the main board, protecting the twin and earth cable run as it makes its way out of the building (exact route unknown, so assuming the worst ). I'm more than likely changing the mainboard to all RCBO, so a garage fault tripping 6 RCD protected circuits, common to it, in the house can't happen. And therefore the nuisance of an upstream RCD trip is less significant. I'd be interested to know what you would do assuming a mainboard RCBO set up? Install without selectivity, respecting 415.1 and listing lack of selectivity RCD/RCBO house to garage as a departure from BS:7671?
@learnelectrics4402
@learnelectrics4402 3 жыл бұрын
Yes Jim, agree with that. If the garage is on its own 30mA RCBO at the house then no need for another RCD and selectivity is also ensured. I've seen lots of installers fitting all RCBO boards now. Certainly worth it when you do a board change, another £200 or so at this point is certainly worth it long term for the customer. Dave.
@zu1875lu
@zu1875lu 3 жыл бұрын
What would you do if the client doesn't want a board change?
@learnelectrics4402
@learnelectrics4402 3 жыл бұрын
That's between you and the customer. The client does not have to have a board change and you are not obliged to do the job if you feel that what the customer is asking for is not as safe as a new board. You can walk away from a job if you haven't started work on it and you think the customer is being blinkered to the dangers.
@ubsurdnerd
@ubsurdnerd 2 жыл бұрын
@@learnelectrics4402 Is there an alternative solution taking into account your example of the cellar, and not wanting to lose lighting in the garage? Is there a way of having discrimination with RCBOs on each of the garage circuits to avoid losing the garage lighting upon an earth fault?
@ubsurdnerd
@ubsurdnerd 2 жыл бұрын
Does the SWA from the main DB to the garage DB not need overcurrent protection? Or is that fine as each circuit fed from it has overcurrent protection?
@robertwilson1496
@robertwilson1496 3 жыл бұрын
Excellent. Really clear and easy to understand. The graphics really helped thank you
@learnelectrics4402
@learnelectrics4402 3 жыл бұрын
Thanks Robert, these comments really are encouraging. Thanks for watching. Dave.
@Trade920
@Trade920 3 жыл бұрын
Fantastic video, very well explained thank you
@learnelectrics4402
@learnelectrics4402 3 жыл бұрын
thanks for the positive feedback, really appreciated. Dave.
@StereoFozzie
@StereoFozzie Жыл бұрын
Wondered if I could trouble you for an answer to a question? I visited a house today where the main CU fed a sub CU from a 30mA RCD B circuit. The sub CU has no RCD and supplies a garage CU from a 32A MCB. Owner wants to run an EV charger from the garage board. But the only way I can see to do this, is if the cable from the main CU to the Sub CU is upgraded to SWA, and same for the run from the Sub to the garage. And protect the circuit from the main board with the type B RCD. But I read a lot of conflicting information that suggests this still might fall short of BS 7671. Could I have some advice?
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Appendix F of the on-site guide has information about cable sizes and breaker sizes. There is a lot to consider with EV charging points. Take a look at the video on the link at the bottom. The fifth edition of the IET code of practice has just been published. Electric Vehicle Charging Equipment Installation. This will answer many of your questions, its a little pricey, but it is tax deductable. Perhaps I should do a video or two on EV charging. Thanks for watching. Dave. kzbin.info/www/bejne/nJy2hqWwZa2Uhqc
@reanult457
@reanult457 2 жыл бұрын
It is easy to understand the concept!! thx you
@learnelectrics4402
@learnelectrics4402 2 жыл бұрын
Thanks Anthony. Appreciated.
@michaelcostello6991
@michaelcostello6991 2 жыл бұрын
Where do you get the fault current values ?
@learnelectrics4402
@learnelectrics4402 2 жыл бұрын
In some of the examples I have just used typical values as examples.
@joto4587
@joto4587 4 ай бұрын
If I come across tripping of the wrong RCD while providing Inspection and Testing, is it a C3 ?
@learnelectrics4402
@learnelectrics4402 4 ай бұрын
I would put it as a C2. Its dangerous when something goes wrong and it needs to work - but doesn't.
@Dibbo1979
@Dibbo1979 3 жыл бұрын
Another great video.
@learnelectrics4402
@learnelectrics4402 3 жыл бұрын
Thank you, your support is very much appreciated. Dave.
@angelofranklin1
@angelofranklin1 3 жыл бұрын
Hi Dave, Good Morning, Great Video. all this is really helping me with my studies and I’m very grateful thank you. Question: Should you also consider upgrading the supply to the garage in line with Iz => In if you are upgrading the protection to stop nuisance tripping.
@learnelectrics4402
@learnelectrics4402 3 жыл бұрын
The supply cable should already be the correct size for the everyday loads expected. The 30mA RCD in the garage should operate first so no need to upgrade if the cables are already correct. Even a 100mA RCD will only draw 0.1 amps down the earth. Good question. Dave.
@angelofranklin1
@angelofranklin1 3 жыл бұрын
Thanks Dave.
@kirandewoo5390
@kirandewoo5390 2 жыл бұрын
Thank you Sir.
@learnelectrics4402
@learnelectrics4402 2 жыл бұрын
You are most welcome Kiran. Thanks for watching. Dave.
@dave11282
@dave11282 2 жыл бұрын
great, please can you do a video on fault currents, how to calculate etc
@learnelectrics4402
@learnelectrics4402 2 жыл бұрын
Excellent idea Dave, it's now on the list tobe done. Keep watching.
@db-bv5rs
@db-bv5rs 2 жыл бұрын
i understand however the diagram at 7:15 shows you connecting a S rcd off of busbar, perhaps henley block, but if you are not going to do it inside the board why add a S RCD upstream and RCD downstream, why not just an RCD downstream?
@learnelectrics4402
@learnelectrics4402 2 жыл бұрын
Thanks for watching. We are showing you some of the different methods that are used and in accordance with recommendations in the Regs.
@db-bv5rs
@db-bv5rs 2 жыл бұрын
@@learnelectrics4402 so say you have a spare slot in the non rcd side, could you just put an mcb and rcd then downstream?
@britoalphonso172
@britoalphonso172 3 жыл бұрын
A 16 A breaker with a slight overload of 70 amps, how it is assume 70 amps when there is 16 amps and 6 amps breaker. I am confused how 70 amps is assume can you please explain me?
@learnelectrics4402
@learnelectrics4402 3 жыл бұрын
Have another look at the video. It says that a 16amp breaker with 70 amps of fault current will take 15 or 16 seconds to trip. If the fault current was 80 amps it would trip in 0.4 seconds or less. Follow the video and use the Regs book at the same time, it is all explained. Thanks for watching. Dave.
@britoalphonso172
@britoalphonso172 3 жыл бұрын
@@learnelectrics4402 thanks dave
@thisname1is1sukzable
@thisname1is1sukzable 2 жыл бұрын
@@learnelectrics4402 so the 70 amp is just a rudimentary value ? if you choose a value of say 50 amps you still get the same answer you set out in your video. but if you have an over current of 20 amps you could do with a 20 amp fuse. what do you base your over current condition on? Is that why you say in you video we need to use the curved bits in the graphs? so you have a rough idea where certain conditions are going to be problematic? Love the video btw. very clear with a good practical example!
@garyplant487
@garyplant487 3 жыл бұрын
Another M* performance again Dave. 👍 Would the person who gave it a thumbs down, like to explain why please, as I'm curious to know?
@learnelectrics4402
@learnelectrics4402 3 жыл бұрын
Thank you Gary. Much appreciated feedback. Dave.
@ilhanyakay7411
@ilhanyakay7411 Жыл бұрын
According to Schneider/Siemens, Ground Fault Protection (GFP) selectivity is wrong. RCC has Definite Time curves. Lower RCD 30mA 40mS time delayi upstream RCCD 300mA 100mS RCD. Upstream RCD must have longer tripping time. RCD selectivity mus be time selectivity, not current selectivity.
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Yes, use an S type. Great input, thanks for watching. Dave.
@steveokinevo
@steveokinevo 3 жыл бұрын
Hit subscribe and don't forget the bell icon too Dave, another fine work of art sir, thanking you.
@learnelectrics4402
@learnelectrics4402 3 жыл бұрын
Great response Stevo. Thanks for your support. Dave.
Electrical Disconnection Times Why they matter
15:33
LEARN ELECTRICS
Рет қаралды 17 М.
Confronting Ronaldo
00:21
MrBeast
Рет қаралды 21 МЛН
How to Fight a Gross Man 😡
00:19
Alan Chikin Chow
Рет қаралды 19 МЛН
Thank you Santa
00:13
Nadir Show
Рет қаралды 45 МЛН
Молодой боец приземлил легенду!
01:02
МИНУС БАЛЛ
Рет қаралды 2,3 МЛН
EARTH LEAKAGE MEASUREMENTS
15:38
LEARN ELECTRICS
Рет қаралды 81 М.
Protection Coordination of Circuit Breakers - Example Calculation
9:57
WHAT IS R1+R2. How to change the values, what do they mean.
17:23
LEARN ELECTRICS
Рет қаралды 52 М.
Types of MCB / Circuit Breaker, BCDKZ
24:33
John Ward (jwflame)
Рет қаралды 110 М.
CABLE TESTING. HOW TO TEST CONTINUITY AND INSULATION RESISTANCE
19:21
LEARN ELECTRICS
Рет қаралды 132 М.
Motors: Conductor sizing and overcurrent protection
58:34
Ryan Jackson
Рет қаралды 9 М.
Confronting Ronaldo
00:21
MrBeast
Рет қаралды 21 МЛН