In this video we take a quick look at how to calculate the short circuit current on an electrical system using transformer information in a Radial distribution system.
When dealing with determining in a network system there are many more factors to take into consideration.
Edit; in the first example the 75000/120V should result in a secondary current of 625A not 312.5A. This would also, when used in the short circuit current formula, yield a short circuit current of 25000A. My bad.
Feel like buying Chris a coffee? Think of it as SchulerRuler fueler!
www.buymeacoff...

Пікірлер: 66
@animal579
@animal579 2 жыл бұрын
i just spent 2 hours on an eaton video and learned alot at a system level, but still didn't learn how to do a SCCR basic calc. Now I got at least this part, thank you.
@shrimp1948
@shrimp1948 Жыл бұрын
😂 I watched it to
@brenden9755
@brenden9755 3 жыл бұрын
Super helpful gearing up for another take on my IP and no teacher could explain in the detail and tenacity that you have!
@schulerruler
@schulerruler 3 жыл бұрын
Thanks for the encouragement my friend. I'm glad it's helped!
@victorcolindres9273
@victorcolindres9273 3 жыл бұрын
this is a great learning Mr Schuller ruler, I thank you for it, but data of single phase transformer calculation is wrong, the I sec is 625A not 312.5A , but again thanks.
@jerrycamboim9216
@jerrycamboim9216 3 жыл бұрын
He divided by 240v instead of 120v. That's probably what happened
@suvius4
@suvius4 Жыл бұрын
Thanks a lot dude! really helping me out for my IP prep!
@ericstandefer9138
@ericstandefer9138 3 жыл бұрын
Very cool, I have been wondering how this was calculated for a long time, thanks. (Subscribed).
@schulerruler
@schulerruler 3 жыл бұрын
Thank you for the support!
@yellow8954
@yellow8954 3 жыл бұрын
Again thank for this awesome content.
@schulerruler
@schulerruler 3 жыл бұрын
Thank you for watching and supporting!
@gunsparky
@gunsparky 2 жыл бұрын
Nice work. It's so hard to find watchable content on this topic.
@masershasibhat
@masershasibhat 2 жыл бұрын
Super talented. God bless you.
@genespliced
@genespliced 3 жыл бұрын
On your 75000va / 120v the result is actually 625A. Why do you get half (312.5A)? If you are using secondary L1 to L2 V as 240v, why not put 240v in the calculation for secondary current? Or use (x 2) in the denominator to indicate single line current for the 2 secondary Lines?
@schulerruler
@schulerruler 3 жыл бұрын
Good catch. I honestly have no idea why I got 312.5. It absolutely should be 625A on this one. This would also make the short circuit current 25000A as well.
@victorcolindres9273
@victorcolindres9273 3 жыл бұрын
Thank youh so much Schuller , I am pretty sure we really appreciate these very important and refreshing knowledge in electrical. Thank you Vic
@ajdsparky
@ajdsparky 2 жыл бұрын
Thanks for clearing this up. However wouldn’t the short circuit be 2,500,000? 25,000 is 625/2.5%.? Thanks again. Just making sure I understand.
@skinnymouse1410
@skinnymouse1410 Жыл бұрын
@@ajdsparky Ishort CCT = Isec x 100 / %Iz = 625A x 100 / 2.5 = 62500A / 2.5 = 25000Amps
@jacobburesh8522
@jacobburesh8522 3 жыл бұрын
great video! good to go back and watch these vids to reinforce what im learning in mach & xfmrs
@schulerruler
@schulerruler 3 жыл бұрын
Happy they are helping!
@ErkadalaMP
@ErkadalaMP Жыл бұрын
It's easy to understand. Thanks a lot!
@schulerruler
@schulerruler Жыл бұрын
Thanks for watching!
@rajindermultani9972
@rajindermultani9972 2 жыл бұрын
Hi I am confused about 75000va Devided by 120 volt .I get 625amp.how you get 312.5 amp.
@dhrupadsaha4171
@dhrupadsaha4171 3 жыл бұрын
Great teaching sir 🙏❤❤🇮🇳
@schulerruler
@schulerruler 3 жыл бұрын
Thanks for the support!
@manafkhalifeh6068
@manafkhalifeh6068 2 жыл бұрын
great Explanations thank you !
@johnhenry4113
@johnhenry4113 3 жыл бұрын
Hello, thank you for the video. Can you please do a s.c calculation for a final sub circuit further downstream in the electrical network. Say a lighting circuit 35 meters away from the transformer? Thanks again.
@malcolmsg7442
@malcolmsg7442 Жыл бұрын
Thank you
@gabopani
@gabopani 2 жыл бұрын
can you explain this exercise ? A 100 kVA, 2400/240 V, single-phase step-down transformer has a 5% impedance rating. What is the minimum interrupting capacity rating for an overcurrent device that is protecting the secondary conductors of the transformer?
@schulerruler
@schulerruler 2 жыл бұрын
100000va ÷ 240V will give you your secondary rated current (root 3 not needed as it's single phase). This can be used to determine the short circuit current using the same method in the video. Secondary current x 100 ÷ 5 will be the short CCT current. This is used to select the IR rating which must not be less than the short CCT current. Hope this helps!
@sohailjanjua123
@sohailjanjua123 3 жыл бұрын
Hi, I like your lecture. Thanks
@JoseTorres-tw6xi
@JoseTorres-tw6xi 3 жыл бұрын
what whiteboard program did you use in your presentation ? it looks similar to the Windows whiteboard , however the one one you used looks to have more features.
@skinnymouse1410
@skinnymouse1410 Жыл бұрын
Which secondary voltage do you use to perform the short circuit calculation on a 3PH xfmr w/ 460/277 primary 208/120 secondary?
@schulerruler
@schulerruler Жыл бұрын
208v but remember the root 3 as well.
@jasonh8542
@jasonh8542 Жыл бұрын
This is a question I should already know but I am done trying to remember why. So why does the O/C protection rating for a short circuit current need to have a higher amperage that the Short circuit fault? Is it because it needs to handle such a huge in-rush of current but the magnetic trip is strong enough?
@schulerruler
@schulerruler Жыл бұрын
It will withstand the internal force generated by the release of short circuit energy, as long as the rated interrupting rating is higher than the calculated minimum value. Underating could result in critical failure or rupturing of oc devices meaning injury, etc.
@CarlosTorres-vx5zu
@CarlosTorres-vx5zu 2 жыл бұрын
A PV module has a surface area of 0.75 square meters and the radiation striking the module is 1000 watts per square meter. What is the short circuit current at 0.75 square meters, if at 1 square meter, the short circuit current is 8.5 A? what the formula for this
@expnnt_designteam9609
@expnnt_designteam9609 2 жыл бұрын
How do you compute for the overall %IZ of the banked 3 single phase transformers for 3 phase use ?
@driftx2
@driftx2 2 жыл бұрын
I got info from the utility company and they gave me a max and min %X for the transformer. Which do I use? I assume the smaller one gives you a more conservative number?
@schulerruler
@schulerruler 2 жыл бұрын
I would always go for the sheer option with the smaller number as yes, as you mentioned it would be more conservative.
@pramodgavit7666
@pramodgavit7666 3 жыл бұрын
Sir can you post vdo on short circuit calculation for hone of 4kw load with suply 229v
@krishnasamykesavan4816
@krishnasamykesavan4816 11 ай бұрын
Great video. Need to know Copper bus bar short circuit current rating formula..or my bus bar size is 15 X 5 mm. Total 75 sqmm copper busbar in DB. Voltage rating 3 phase 415 VAC. give me the answer. Thanks once again. If any one please answer it.
@gusakpan9730
@gusakpan9730 Жыл бұрын
How do you find the impedance percentage?
@schulerruler
@schulerruler Жыл бұрын
Here is a link to my video detailing the test performed to obtain the percent impedance! kzbin.info/www/bejne/bZLOgWZ7jraVb9U
@maurogonzalez5792
@maurogonzalez5792 2 жыл бұрын
🔥
@inder8750
@inder8750 3 жыл бұрын
hey i have a question thats asking for fault current is that the same formula and also it gives me two coltages for the primary and 2 for the secondary
@schulerruler
@schulerruler 3 жыл бұрын
What are the secondary voltages given?
@possibility28able
@possibility28able 3 жыл бұрын
What happens in the event that the breaker is underrated for the short circuit? I. E you have a 10kva rating or AIR and the available short circuit current is 15kva?
@schulerruler
@schulerruler 3 жыл бұрын
There's a good chance that the amount of energy will destroy the overcurrent device violently causing potential injuries
@possibility28able
@possibility28able 3 жыл бұрын
@@schulerruler Interesting. Thanks for the response!
@jasonh8542
@jasonh8542 Жыл бұрын
@@schulerruler so that’s why the OC protection rating must be the Short Circuit rating or higher. But I assume just because the OC Protection is rated higher doesn’t mean it won’t trip because the SSC fault value is less. This has kind of messed with me.
@schulerruler
@schulerruler Жыл бұрын
Always size the interrupting rating of the overcurrent to the short circuit current, or higher preferably. If not marked, assume 5kA for Breakers 100 A or less, and 250 V or less, and 10kA for Breakers larger than 100 A or greater than 250 V. All fuses if not marked, assume 10kA. (Check appendix B 14-012 for this info)
@jasonh8542
@jasonh8542 Жыл бұрын
@@schulerruler seriously you are the man for taking the time to write to your subscribers. It’s very much appreciated.
@gabopani
@gabopani 2 жыл бұрын
I see now thx
@danielcarpenter9299
@danielcarpenter9299 3 жыл бұрын
What exactly is E Line? Is that a shortcut on the calculator?
@schulerruler
@schulerruler 3 жыл бұрын
E line would be source voltage AKA line voltage. The E is the symbol that represents Electromotive force.
@sanjeevbhogal6818
@sanjeevbhogal6818 2 жыл бұрын
WHAT ABOUT SCARY AUTOTRANSFORMER?
@maddog4437
@maddog4437 Ай бұрын
6:25 what was EL?
@schulerruler
@schulerruler Ай бұрын
That would be the rated E line voltage, which in this example was 600Vac.
@allpurposeconstructionwiz
@allpurposeconstructionwiz 7 ай бұрын
What does "I z" mean ?
@schulerruler
@schulerruler 7 ай бұрын
When used as %IZ it is the amount of voltage applied to the primary, compared to rated primary voltage, that will cause RATED current to flow on the secondary of a transformer, when the secondary is short circuited. This is obtained by performing a short circuit test on a transformer (which I do have a video on) but is usually a number listed on the nameplate as well. I hope this helps.
@Buck1954
@Buck1954 Жыл бұрын
SOOOO, What is "EL"?
@schulerruler
@schulerruler Жыл бұрын
If you're referring to the abbreviation used in the formula, that's the line voltage, which is measured line to line.
Electrical Bonding Fail Example
7:02
schulerruler
Рет қаралды 8 М.
What Does Available Fault Current Mean?
7:53
Electrician U
Рет қаралды 42 М.
Wait… Maxim, did you just eat 8 BURGERS?!🍔😳| Free Fire Official
00:13
Garena Free Fire Global
Рет қаралды 9 МЛН
How Much Tape To Stop A Lamborghini?
00:15
MrBeast
Рет қаралды 89 МЛН
Who's spending her birthday with Harley Quinn on halloween?#Harley Quinn #joker
01:00
Harley Quinn with the Joker
Рет қаралды 22 МЛН
Calculating Fault Current using transformer impedance
17:22
INW Industrial Training
Рет қаралды 10 М.
Grounding and Bonding
8:01
schulerruler
Рет қаралды 675 М.
Individual Motor Calculations
9:25
schulerruler
Рет қаралды 31 М.
Overcurrent, Overload, Short Circuit, and Ground Fault
6:54
Dave Gordon
Рет қаралды 912 М.
Everything you need to know to solve Voltage Drop Calculations!!
14:57
Craig Michaud- Electrical Instructor
Рет қаралды 233 М.
How to calculate fault current using percent impedance
4:53
The Electric Academy
Рет қаралды 49 М.
Short-Circuit Current Calculations and Equipment Evaluation
2:07:03
Thomas Domitrovich
Рет қаралды 30 М.
3 PHASE PFC - How to calculate 3 phase Prospective Fault Current
13:09
LEARN ELECTRICS
Рет қаралды 19 М.
Percent Impedance of a Transformer
6:44
Zack Hartle
Рет қаралды 34 М.
Wait… Maxim, did you just eat 8 BURGERS?!🍔😳| Free Fire Official
00:13
Garena Free Fire Global
Рет қаралды 9 МЛН