Using Telegram30 with G120 & S7 cpu (TIA PORTAL V15)/START DRIVE
Пікірлер: 6
@giovanigaspar5 жыл бұрын
thanks guys, helped me a lot!
@Coyote9734 жыл бұрын
Very useful video, It's a shame that official Siemens videos are just useless as their manuals. The "Nuts&Bolts" as you call it from 29:00 were the cause for 3 days of mad guessing. It was only solved upon watching this video. Still, I am struggling with acceptance test, I can't figure out how it can be skipped, or why you say "not needed in V15". The inverters keep outputing the error: acceptance test needed.
@bobbycole56864 жыл бұрын
Thank you. If you have teamviewer I am happy to help! Shoot email to colecontrol@gmail.com
@mustafayurtseveri843 жыл бұрын
@@bobbycole5686 Thanks for video. can you explain how to do acceptance test. I cant ack the faoult and do the test
@bobbycole56863 жыл бұрын
@@mustafayurtseveri84 a power cycle is most important after finishing safety commissioning.
@vorapobautomation97605 жыл бұрын
How can I using Telegram 1 to control G120 with S7-317F-2PN/DP ?