Structural Analysis and Design - Approximate building analyses / Truss-beam analogy for design

  Рет қаралды 35,668

FireSUN

FireSUN

Күн бұрын

It is useful for approximate analyses, and understanding load paths, to see the behaviour of beams being analogous to that of columns. This short video gives an overview of the concept and basic calculations.
Copyright Stellenbosch University.

Пікірлер: 25
@qzwxecqz
@qzwxecqz 3 жыл бұрын
Excellent presentation. It saves me a ton of time and money. Thank you very much
@RC-jx9nw
@RC-jx9nw 2 жыл бұрын
Thank you so much, this is exactly what I was looking for.
@mairajhabib9754
@mairajhabib9754 3 жыл бұрын
Prof Richard, Thanks for making the informative video. Approximate assessment was clearly defined, one point needs to understand, "Truss- beam interconvertibility is acceptable till the Shear is not high." Needs to understand the reason behind it, moreover what will be the behaviour under high shear values. Pl clarify through some lecture.
@firesun
@firesun 2 жыл бұрын
Calculations done here assume all deflections are due to bending. As the shear gets high and/or the truss gets deep the shear deformations start to become important and results become less accurate. You can test this by setting up simple truss and beam models and comparing results as you vary parameters.
@user-sr1bd3qo6t
@user-sr1bd3qo6t 2 ай бұрын
Thank you for the video
@wizamusinga716
@wizamusinga716 2 жыл бұрын
thanks so much prof
@chamithdilshan3547
@chamithdilshan3547 4 жыл бұрын
Thanks a lot!
@goldonon
@goldonon 2 жыл бұрын
Thanks for the detailed explanation How to estimate the deflection on typical roof truss (pin pin) with slopes (Not fixed height) ?
@firesun
@firesun 2 жыл бұрын
It depends on what you are doing and how accurate you need the answer to be. You could approximate the behaviour as a beam with multiple sections to account for the slope (e.g. use principle of virtual work). However, as the geometry gets more complicated and you need reasonable answers it is best to just go to a simple truss model.
@goldonon
@goldonon 2 жыл бұрын
"You could approximate the behaviour as a beam with multiple sections to account for the slope" Thank you for the answer It will be very helpful if you can give an example of this, I did not find such an example on KZbin Thanks
@firesun
@firesun 2 жыл бұрын
@@goldonon Use the principle of virtual work and integrate over multiple sections with each having a different stiffness. However, you are at the stage you shoudl probably just do a frame analysis,
@engr810
@engr810 Жыл бұрын
thanks a alot sir
@structuralchannel2507
@structuralchannel2507 2 жыл бұрын
Sr In the warehouse truss explaination , if the column is let say stiff of order of that required for miniumum slenderness criteria (not bulcky) and the truss is rigidly connected to column by welding then will column experience moment ?? If yes ,very small ? Or high? (i dont think) If no , bcoz column not rigid enough? Please answer sir
@firesun
@firesun 2 жыл бұрын
It will depend on the ratio of stiffness between the column and truss. If you have a braced frame you could even make a slotted connection on the bottom chord of the truss such that there would no moment. However, in most cases you will exert a moment, and likely of reasonable magnitude
@iniekpenyong2842
@iniekpenyong2842 Жыл бұрын
THANKS SO MUCH, PLEASE IS THERE ANY DESIGN CODE THAT SUPPORTS THISE METHOD?
@firesun
@firesun Жыл бұрын
Nope. Based on fundamental mechanics and structural analysis, rather than a code. However, most code guidelines follow such an analysis. Go find a structural engineer with grey hair and they will show you more useful techniques like this.
@mahendrasookoo3040
@mahendrasookoo3040 2 жыл бұрын
How many panels are allowed taking into account the depth ratio L/15
@firesun
@firesun 2 жыл бұрын
There are not specific rules as this is a an approximate analysis. As the truss gets deeper and the verticals + horizontals have a bigger influence on deflections the results become less accurate.
@rodrigoarancibia1975
@rodrigoarancibia1975 3 жыл бұрын
Hi, why the distance from the neutral axis is 1000?
@firesun
@firesun 3 жыл бұрын
The depth of the truss/beam is 1m. When working about Ix the distance from the neutral axis is 1000/2 = 500. When taking sum of moments it is easier to take it about the top or bottom chord such that those forces cancel (zero lever arm), and then a lever arm of 1m is used.
@collinladao7828
@collinladao7828 3 ай бұрын
WHERE DOES 10 AND 5 POINT LOAD COME FROM?
@firesun
@firesun 3 ай бұрын
UDL x span between nodes = 10kN/m x 1m = 10 kN (or half of this for the end bays)
@shelbyphillipson4336
@shelbyphillipson4336 10 ай бұрын
Where does sqrt 2 come from?
@richard_walls
@richard_walls 10 ай бұрын
1 / sin(45 degrees). It is to convert the diagonal force to a vertical force for sum of forces at a node.
Understanding and Analysing Trusses
17:41
The Efficient Engineer
Рет қаралды 3 МЛН
If Barbie came to life! 💝
00:37
Meow-some! Reacts
Рет қаралды 79 МЛН
Dad Makes Daughter Clean Up Spilled Chips #shorts
00:16
Fabiosa Stories
Рет қаралды 3,4 МЛН
小丑把天使丢游泳池里#short #angel #clown
00:15
Super Beauty team
Рет қаралды 48 МЛН
Please Help Barry Choose His Real Son
00:23
Garri Creative
Рет қаралды 23 МЛН
Truss Calculation
25:43
John Fuller
Рет қаралды 216 М.
SA36: Analysis of a Roof Truss: Method of Joints
12:27
Dr. Structure
Рет қаралды 186 М.
Design of Steel Deck Diaphragms
5:55
SKGAssociates
Рет қаралды 3,9 М.
The Secret to the Truss Strength!
9:40
The Engineering Hub
Рет қаралды 346 М.
8 Habits That Quickly Made Me a Better Civil Structural Engineer
10:03
5 Top equations | Steel Truss Design every Structural Engineer should know
3:09
Structural Engineer Calcs
Рет қаралды 118 М.
How to do a steel beam calculation - Part 1 - Loadings
11:39
Robin de Jongh
Рет қаралды 161 М.
If Barbie came to life! 💝
00:37
Meow-some! Reacts
Рет қаралды 79 МЛН