would you please explain how you add object on the screen? i can not make this object that you have been made. please explain it . thanks
@sadiqshakir68892 жыл бұрын
How can I get the PDF files?
@davidstuart2434 Жыл бұрын
HI there, I'm using a S 7 1200 PLC and has various sensors connected to it. The PLC has numerous 485 Sensors connected to it and all the sensors are working and sending the correct data values to the PLC. LODTemp1 DB5.DBD32 - Floating-point Number LODPerc1 DB5.DBD44 - Floating-point Number LODmg DB5.DBD52 - Floating-point Number AmbientHumid1 DB5.DBD82 - Floating-point Number AmbientTemp1 DB5.DBD90 - Floating-point Number AmbientLUX1 DB5.DBW72 - DEC +/- PhSen1 DB7.DBD0 - Floating-point Number OrpSen1 DB7.DBD4 - Floating-point Number WaterTemp1 DB7.DBD8 - Floating-point Number When setting these tags to real on Indusoft the Lux reading is correct (set to integer) but all the real tags are reading the incorrect AmbientTemp1 1106300109 - should be 30.1 AmbientLUX1 2348 - Correct LODmg 1084511463 - incorrect LODPerc1 1116454652 - incorrect LODTemp1 1107018776 - incorrect Any help will be greatly appreciated
@firdausimax2537 Жыл бұрын
For floating point you should write the address like this DB5.DBF32