The cause of the AC electrocuting or short body

  Рет қаралды 36,170

Johan teknik

Johan teknik

Күн бұрын

back again with johan technique
This time, Johan Teknik wants to review a little about the problems that cause the AC to shock or short body, whatever the causes are:
1. Grounding or Grounding is not installed
because the function of grounding is as a neutralizer of leakage current which will later flow to the ground or earth.
2. This leaky capacitor can also cause a short body or electrocution, which can be marked by the physical characteristics of the capacitor
a. the capacitor bloats and cracks and releases liquid
b. the capacitor melts.
3. It could also be caused by a compressor coil that is not good enough because the spool layer is peeling off
4. The problem with the cable is peeling and the skun is rusty
there's a way to fix it:
Note measuring how much the short body voltage or stun it, if it's still below 100 V, we can still trick it
1.Give additional ground to the outdoor unit
2. Change the position of the neutral and phase wires on the outdoor unit
3. on the indoor unit switch the position of the neutral and phase wires
4. remove the grounding cable attached to the indoor
good luck
greetings johan technique
description
description

Пікірлер
@nazacom2152
@nazacom2152 3 жыл бұрын
Ya betul bang... sy pernah ketemu kontak body di outdoor ac 2x. Satu karna terbalik pasang antara kabel fasa dan netral pada colokan indoor ke sumber. Kedua terjadi gesekan kabel pendek di overload dgn baut karna getaran kompresor lama2 kabel terkelupas.. Trimakasih.. 👍🙏
@mabruriruri5854
@mabruriruri5854 2 жыл бұрын
Yg paling sering terjadi colokan di in door unit kebalik posisinya bos, coba urut kabel netral itu langsung dan yg line itu lewat relay dulu baru konek dan kalau dibalik kabel out door sama saja jebakan
@noeakbar
@noeakbar Жыл бұрын
Jebakan gimana bang, apa bakal konsleting listrik. ?
@TrickEelektrik3533
@TrickEelektrik3533 26 күн бұрын
mkasih banyak bang ... smoga banyak rejeki
@teddy210
@teddy210 Жыл бұрын
Makasih ya bro atas infonya... Semoga kakak sehat selalu...
@SugengacSugengac
@SugengacSugengac 5 ай бұрын
Kalo kabel grounding di evapnya di lepas dan di isolasi,apakah ngga pengaruh sama kelistrikan dan kinerja kompresor nya bang??,mohon bantu jawab, terima kasih 🙏🙏🙏
@JohanChannel
@JohanChannel 5 ай бұрын
Kenapa harus dilepas mas?sebetul nya tidak ada pengaruh dengan kerja kompresor akan tetapi fungsinya untuk mencegah arus bocor .
@rizkyalfarizih3869
@rizkyalfarizih3869 4 ай бұрын
Apa efek kompresor short body? Bagi aliran freon? Atau dingin maksimal pada AC
@danangdanang4675
@danangdanang4675 2 жыл бұрын
ISTIMEWA
@noeakbar
@noeakbar Жыл бұрын
Ketika kabel di balik, iya setrumnya ilang pas posisi ac mati. Tapi 2 bulan kemudian, outdor nyetrum lagi pas posisi ac nyala. Tapi pas ac mati ga nyetrum. Kenapa ya bang.
@ferdinandanoi9629
@ferdinandanoi9629 7 ай бұрын
Kalau short body hanya saat kondisi mati itu karena apa pak? Pada saat nyala justru normal.
@SugengacSugengac
@SugengacSugengac 5 ай бұрын
Assalamualaikum bang,klo kabel nya di balik bagian outdoor,jadi yg di indoor jg bali kah??
@JohanChannel
@JohanChannel 5 ай бұрын
Disesuaikan mas terutama yg di indoor jangan ter balik
@idhamandre8996
@idhamandre8996 Жыл бұрын
Bang numpang tanya serius klo kita beli kompresor bekas bagaimana cara menentukan brapa kapsitas kompresor ac tsb moho dijawab ya bang
@JohanChannel
@JohanChannel Жыл бұрын
Cek divideo saya sebelum nya Mas .amper normal kompresor ac tanpa freon
@marchaliihsan2787
@marchaliihsan2787 Жыл бұрын
Terimakasih ilmunya bro sangat nanfaat
@wildayananci7834
@wildayananci7834 7 ай бұрын
Bang , gmna klo nyetrum pas di slimut, jendela, nyentuh kaki ke lantai😢 Brp tahun udah ga nemu solusinya? Apa yg harus diperbaiki?
@SusantoDumai
@SusantoDumai 6 ай бұрын
apa sudah tau penyebab kak?
@wildayananci7834
@wildayananci7834 6 ай бұрын
@@SusantoDumaiblm nih😢
@SugengacSugengac
@SugengacSugengac 5 ай бұрын
@@wildayananci7834 ganti aja unit baru mbak 🤭😀😀🙏
@yusufaja1993
@yusufaja1993 Жыл бұрын
Mau nanya om,Kalo di biarkan saja,bisa bikin ac rusak gak om...
@JohanChannel
@JohanChannel Жыл бұрын
Tidak juga cuma kwatir tersengat saja
@mustagfirinyahya2224
@mustagfirinyahya2224 Жыл бұрын
Pengaruh ke pengunaan listrik jadi boros apa tidak
@sbhartanto66
@sbhartanto66 Жыл бұрын
Klo pas ac on, unit outdoor nyetrum, itu kenapa? Apa yg harus di check?
@JohanChannel
@JohanChannel Жыл бұрын
Coba balik antara kabel fhasa dan netral pada kabel input yang dri pln ke indoor
@sbhartanto66
@sbhartanto66 Жыл бұрын
@@JohanChannel setelah dibalik malah kondisi off dan on jadi nyetrum, sebelum dibalik hanya kondisi on ac unit outdoor yanh nyetrum
@JohanChannel
@JohanChannel Жыл бұрын
Kabel2 unit outdoor sudah di cek ? Kemungkinan besar kompresor mengalami arus bocor mas coba buat grounding Mas di init outdoor nya.
@sbhartanto66
@sbhartanto66 Жыл бұрын
@@JohanChannel saya cek di evaporator indoor kondisinya sama ketika on cek testpen nyala
@JohanChannel
@JohanChannel Жыл бұрын
Udah dicoba coba dicopot kabel yg ke outdoor apakah evap tetep nyetrum apa enggak
@insan788
@insan788 2 жыл бұрын
bang , ac dikamar saya klo suhunya uda dingin bisa memyebabkan kontak gitu saat bergesekan dgn selimut/kasur , dan jerjak besi jendela ketika dipegang, begitu juga pas turun tempat tidur kaki menyentuh lantai terjadi kontak sedikit sampai menghasilkan suara percikan gitu, itu apanya yg bermasalah?
@menimbailmu5314
@menimbailmu5314 2 жыл бұрын
Benar saya juga mengalami kejadian ini sampai sekarang, kaki menginjak lantai juga agak nyetrum sedikit, pegang selimut juga, pegang tralis juga, bahkan kadang bersentuhan dengan istri saja nyetrum, keluar percikan nyetrum.. Kenapa ya?
@felixgamingambon2180
@felixgamingambon2180 2 жыл бұрын
Aku sama istri dalam beberapa bulan ini gitu sama bang percikan klu kulit sentuhan
@ErwinjayaChanel
@ErwinjayaChanel Жыл бұрын
@@felixgamingambon2180 abis nyetrum muncrat 🤭
@Viadesvia
@Viadesvia Жыл бұрын
Hallo kak Insan saya skrng juga lagi ngalamin hal yg serupa dengan kk , itu penyebabnya karna apa yaa , boleh sharing pengalamannya kak dan solusinya🙏
@Viadesvia
@Viadesvia Жыл бұрын
@@menimbailmu5314 kak itu penyebabnya ac kenapa apa yaa saya sekarang lagi ngalamin juga ?
@bimayulianto3548
@bimayulianto3548 Жыл бұрын
Efek k dpnny ap ya klo d biarin
@JohanChannel
@JohanChannel Жыл бұрын
1.sangt membahayan bagi yng akan service 2.listrik Boros
@ropikahdiar6744
@ropikahdiar6744 2 жыл бұрын
Kita pasang ac lg baru kok bisa setrum
@JohanChannel
@JohanChannel 2 жыл бұрын
Coba di balik antara kabel netral dan kabel fasa nya dan kabel gronding pasang
@ropikahdiar6744
@ropikahdiar6744 2 жыл бұрын
@@JohanChannel apa gak ada masalah lain..soalnya ac baru..apa jg bisa gitu
@JohanChannel
@JohanChannel 2 жыл бұрын
Bisa saja kalo ac nyetrum yerjadi karna ada arus bocor memang ada beberapa poin penuyebab 1.masalah grounding 2.bisa dri kabel terkelupas 3.bisa dari gulungan kompresor lecet
@balimoreelectro437
@balimoreelectro437 2 жыл бұрын
Inverter acny gkv
GAMPANG ,,,,,,AC NYETRUM,,,,,,
24:40
andre tatum
Рет қаралды 25 М.
OUTDOOR AC INVERTER NYETRUM, AMANKAH?
7:29
AirCond Solution
Рет қаралды 5 М.
黑天使只对C罗有感觉#short #angel #clown
00:39
Super Beauty team
Рет қаралды 36 МЛН
Что-что Мурсдей говорит? 💭 #симбочка #симба #мурсдей
00:19
Don’t Choose The Wrong Box 😱
00:41
Topper Guild
Рет қаралды 62 МЛН
She made herself an ear of corn from his marmalade candies🌽🌽🌽
00:38
Valja & Maxim Family
Рет қаралды 18 МЛН
ciri-ciri overload AC rusak dan sudah lemah.
8:22
Johan Teknik
Рет қаралды 96 М.
penyebab dan solusi kabel Fasa dan Netral ada arus listrik nya
7:12
MENGATASI AC SERING MATI SENDIRI
18:38
HIDAYAH TEKNIK
Рет қаралды 25 М.
Jika kipas outdoor & kompresor ga mau hidup
13:44
AirCond Solution
Рет қаралды 150 М.
Cara bongkar dan memperbaiki kompresor AC
21:06
Karir Kedua
Рет қаралды 40 М.
AC Nyetrum ‼️Cara mudah mengatasi
6:52
Ubaid Teknik
Рет қаралды 2,9 М.
Efek salah pasang kabel kapasitor ac
8:51
Johan Teknik
Рет қаралды 86 М.
Ac lg kurang dingin solusinya flushing pakai tiner
14:19
Zadi Channel
Рет қаралды 383 М.
ciri dari AC mampet dan tidak lancar
13:25
Johan Teknik
Рет қаралды 85 М.
黑天使只对C罗有感觉#short #angel #clown
00:39
Super Beauty team
Рет қаралды 36 МЛН