Just last week had a similar problem on the same kind of tandem compressors ......had to change both of them due to over amping Thanks for the video
@UlisesPalacios7 жыл бұрын
JUAN JASSO for sure. I'm going to have to change a set soon. They are heavy. 300 lbs for the set.
@polishtheturdmickelson54737 жыл бұрын
Nice video Ulises. You stole my thunder at the 14:57 mark about installing a oil separator with the new compressor. Tandems units are not cool. I know Trane likes them in their commercial equipment. I am not familiar with that brand. Addison, looks like a unique system. Definitely the oil was not dumped out of the accululator and it was not replaced. Maybe there is a issue with the accumulator? Caused flooding back and washed the oil out of the failed compressor somehow? I have also heard scrolls sound like that. The one I remember ran in a vacuum for a period of time. It was on a walkin freezer. It would not pump down. I found a failed low pressure control.
@philltafolla7 жыл бұрын
That compressor sounds like is going to pop open ..sounds and looks like a restriction could be the issue you can hear the compressor struggling, and over amping... .. came across a few 5 ton Lennox RTUs with a similar issue last summer what do you think ?great video ...Ulises.
@UlisesPalacios7 жыл бұрын
Felipe Tafolla I wish it was just a restriction. Actually with a restriction in most cases you would have lower than normal amp draw. Pressure and temps where fine. Something caused the low oil level in the compressor.
@UlisesPalacios7 жыл бұрын
Thanks man
@philltafolla7 жыл бұрын
Ohh I see .. bad ass video bro.. how you liking the new tool? The power lift?
@UlisesPalacios7 жыл бұрын
Felipe Tafolla i love it. I just need to find a different way to mount it for my ladder.
@philltafolla7 жыл бұрын
Niiiceeee. Looking forward to see more videos
@principeazteca20006 жыл бұрын
very good video Ulises.....thanks for sharing...
@mekyleavacadogaming73544 жыл бұрын
great video. I like the flir device.
@NorCal-refrigeration7 жыл бұрын
Compressor is done. Great video.
@UlisesPalacios7 жыл бұрын
Nor-Cal Refrigeration & H.V.A.C yup. Thanks man.
@carlosbanegas75773 жыл бұрын
very good video thank you
@josbrun7 жыл бұрын
Very nice video, thank you for sharing!
@UlisesPalacios7 жыл бұрын
Josef Brunclik thanks man
@suljohumcevic77796 жыл бұрын
Ulises Palacio s
@joeshearer12477 жыл бұрын
In a residential system with no sight glass and multiple compressor replacements it's hard to tell how much oil is left in the system waiting to cause issues. I try and drain the old compressor and see how much oil I get out to guage what's in there but still leaves uncertainty
@UlisesPalacios7 жыл бұрын
Joe Shearer yeah. I actually took a compressor out of a working unit. Only 4 ounces low which is pretty good. I wish more units had oil separators. Better yet oil less magnetic bearing compressors for residential and light commercial one day. I bet they are working on something.
@anthonysuau54377 жыл бұрын
what are you using to protect the iconnect pressure probes is that a bottle insulator?
@UlisesPalacios7 жыл бұрын
Anthony Suau lol yes. They are.
@jasonaguilar49295 жыл бұрын
What do think about the new update on the iconnect
@UlisesPalacios5 жыл бұрын
Jason Aguilar I think it’s horrible. You? Maybe I’m just used to the old version.
@jasonaguilar49295 жыл бұрын
Ulises Palacios i agree 100% I went back to my testo smart probes thanks
@jemhvacvaii81367 жыл бұрын
yooooo! another bit the dust! I had that issue but with an R22 to R421A conversion
@UlisesPalacios7 жыл бұрын
JEM HVAC VA II yeah buddy. really. How old was it.
@jemhvacvaii81367 жыл бұрын
6months old. a new born lol!
@UlisesPalacios7 жыл бұрын
JEM HVAC VA II damn. That sucks.
@ganchimegochir11475 жыл бұрын
i had this kind situation too, directly get a new compresser, there is nothing else you can do to a hermetic.
@jimbola777 жыл бұрын
thank you for sharing palacios!!!!
@UlisesPalacios7 жыл бұрын
jimbola77 thanks
@theairconditioningguy7 жыл бұрын
If you ever decide to move to LA let me know. You have a job with me. What was the name of that app?
@UlisesPalacios7 жыл бұрын
The Air Conditioning Guy heck yeah. It's called Copeland mobile. You have to register to use it but it's easy to register and get a user name set up.
@ThomasBahamas7 жыл бұрын
Are you using one of those Seek thermal imaging cameras?
@UlisesPalacios7 жыл бұрын
NSNOfm78 it's actually a Flir one. Similar to the seek but I think the flir is a littler better for the price.
@anthonysuau54377 жыл бұрын
what model flir is it?
@UlisesPalacios7 жыл бұрын
Anthony Suau it's the flir One. They actually have a new model coming out.
@nicholasgoodridge82977 жыл бұрын
Those condenser coils really bad. Chocked to the max. That could be part of the of the cause of the problems
@UlisesPalacios7 жыл бұрын
Nicholas Goodridge yeah they probably have never been cleaned in 5 years.
@kinggenius66607 жыл бұрын
good job good video good work! the print at the bottom of the screen a little hard to read on the cell phone thank you for making videos!
@justin09577 жыл бұрын
That's a loud vibrator
@mailtoray4 жыл бұрын
Someone did electrical work in the main electrical entry point and cause wrong phase