@charlesworrell5946
@charlesworrell5946 10 күн бұрын
Very easy to understand! Good information! I will watch again to reinforce learning. Thanks Chuck Worrell FireSafetyConcepts
@EnergyRiskEngineering
@EnergyRiskEngineering 2 күн бұрын
I glad you liked it. Thanks. 😊
@BigD-utah
@BigD-utah 7 ай бұрын
A great explanation. The only thing to add is that the fire pump alarm signals and controller functions must be tested as well per NFPA 25. Almost no one does that.
@EnergyRiskEngineering
@EnergyRiskEngineering 7 ай бұрын
Great points! Thanks.
@ahmedalbuaimi
@ahmedalbuaimi 4 ай бұрын
very useful explaination
@EnergyRiskEngineering
@EnergyRiskEngineering 4 ай бұрын
Thanks Kindly.
@parthchaudhary8993
@parthchaudhary8993 7 ай бұрын
Very informative 👍
@erdevendra
@erdevendra 7 ай бұрын
This was really amazing,
@user-qv7ov9gq5y
@user-qv7ov9gq5y 5 ай бұрын
A great Explanation thank you.
@hosemonster
@hosemonster 2 ай бұрын
Great video and explanation! Reach out to Hose Monster if anyone has questions on how to perform a test.
@EnergyRiskEngineering
@EnergyRiskEngineering 2 ай бұрын
Thanks for contributing!
@tduross
@tduross 4 ай бұрын
The only time I would apply affinity would be with a variable speed controller (VFD-PLD) because speed is what i is but also how well the mfgr matched the driver to the pump.
@lazarusakhagbosu371
@lazarusakhagbosu371 7 ай бұрын
Thank you sir.
@EnergyRiskEngineering
@EnergyRiskEngineering 7 ай бұрын
You are very welcome! Next video will be about lube oil system risks.
@dennisseretny6228
@dennisseretny6228 3 ай бұрын
I test a fire pump that consistently has a high churn pressure (140 PSI plus as compared to the factory churn of 116 PSI) The 100 % is always around 90% of the factory 104 PSI at 94 PSI and then the bottom falls out at the 150% point (Factory at 87PSI to the annual test pressure of 58PSI which is well below the 90% requirement). This is a vertical turbine pump with a raw water source. Normally I get a -3PSI for the supply pressure as the water level is usually around 6.5 ' from the surface of the water to the C/L of the discharge on the pump. The curve on the graph is always convex instead of concave. Would you be able to direct me to a corrective coarse of action that would help resolve this. The pump rating is 1,000 GPM @ 104 PSI with 1770 RPM. My RPM readings are around 1785 at churn, 1777 at 100% and 1774 at 150%. Yes, I do have my gauges calibrated annually.
@EnergyRiskEngineering
@EnergyRiskEngineering 3 ай бұрын
Dennis, thanks for the great questions. Can you get a borescope inspection of the bowls? The experience I have with VT fire pumps is that either a blockage of weeds and branches formed or one or more of the lifting bowls was damaged or missing. In those days we pulled the vertical impeller. Possibly a borescope would give you confidence to look elsewhere or actually find an issue.
@dennisseretny6228
@dennisseretny6228 3 ай бұрын
Thanks for the insight, once I get consent to proceed, I'll get back to you on the results.
@EnergyRiskEngineering
@EnergyRiskEngineering 7 ай бұрын
Thank you. Every plant should watch 😅
@MMAli-nj8xl
@MMAli-nj8xl 4 ай бұрын
What if corrected test result shows that test curve is above the pump OEM curve...what is the interpretation for such result? will 5% apply to going above the OEM curve as well?
@EnergyRiskEngineering
@EnergyRiskEngineering 4 ай бұрын
The NFPA 25 committee was not concerned with pumps performing above the curve. They weren’t even interested in meeting the largest system demand. The manufacturers reps on the committee were just looking for a way to monitor wear on the impellers. (Check that the driver is at an appropriate RPM.) The 5% was never about reducing risk. Risk was never discussed. Where did it come from? It was made up.
Diesel Fire Pump Test
20:19
howImetyourfather
Рет қаралды 26 М.
FIRE PUMP How to perform annual Fire pump test.
7:00
Fire Technician101
Рет қаралды 55 М.
Magic trick 🪄😁
00:13
Andrey Grechka
Рет қаралды 43 МЛН
Lehanga 🤣 #comedy #funny
00:31
Micky Makeover
Рет қаралды 29 МЛН
КАКУЮ ДВЕРЬ ВЫБРАТЬ? 😂 #Shorts
00:45
НУБАСТЕР
Рет қаралды 3 МЛН
Power Generator Risks - for Risk Engineers, Underwriters and Brokers
17:17
Energy Risk Engineering Lessons
Рет қаралды 397
Prejob - Hazards and Protective Measures
11:54
Utility Supply & Construction
Рет қаралды 8
Class 5 | NFPA 20 Fire Pump Performance Curves Decoded!
9:50
Irfan CFPS
Рет қаралды 2,3 М.
LNG and LPG Vapor Clouds for beginners
21:33
Energy Risk Engineering Lessons
Рет қаралды 249
Urban Pump Series (001) - Rated Capacity
3:20
Roll Steady
Рет қаралды 4,1 М.
How to Conduct a Fire Pump Flow Test | Hose Monster University
2:31
TheHoseMonsterCompany
Рет қаралды 19 М.
how to read centrifugal pump curves
7:24
AMJ Engineering
Рет қаралды 10 М.
Weekly diesel fire pump test.
15:20
Joy Cool
Рет қаралды 1,1 М.