Wow! Absolutely amazing, fabulous!!!. This is how you explain the concepts -- clear cut, right to the point, no beating around the bush, etc. I wish others watch this video and learn how to make educational videos..
@wangarooi3 жыл бұрын
I used to repair mitsi drives for a living...many moons ago when vf control was the defacto. This guy is exactly right in his explanation. If I could add a couple of points: 1. Smell the drive.....if it has a "burnt" smell then its usually the power section and chopper section blown. You can sometimes see the power device sidewall blown out, exposing some white smoky looking gel...maybe this has changed on the newer devices. 2. A faulty drive has a certain squeaky sound....unfortunately that a difficult one to explain I could diagnose a faulty drive just by the way it sounded..it was usually the capacitors on the chopper boards. Mitsubishi used to pull the gate signal slightly negative to switch the power devices off. I doubt I could hear a faulty drive now and the newer power devices are much better at switching on and off. Anyway, that was many moons ago my exposure to industrial drives is now a button/parameter checking thing and this in its own right can be the difficult thing you have to find the right parameter but the fundamental principles stay the same But to the good gentleman explaining this video you are spot on.
@technologytijuana2 жыл бұрын
Hello sir, what would be the problem for a vfd that is getting the dc bus voltage directly to the vfd output. Im getting 650vdc in u v w?
@wangarooi2 жыл бұрын
@@technologytijuana ...didi you chck for a short from the DC bus to UVW... Obviously let it discharge first
@mundrubjet8 жыл бұрын
Also, when you shut down a VFD, you should wait at least 10 minutes as most of them hold a charge that will dissipate through a resistor. If you go touching things right away because you have opened the disconnect, you could do the electron boogie for a few seconds. And that's worse than the chicken dance...
@MOHDFAISAL-qw8mz5 жыл бұрын
Right
@scottwillis54345 жыл бұрын
Allow for failed bleeder resistors. Use a voltmeter (rated for at least 500V) to check the capacitor voltage, which may exceed 320VDC when powered, before sticking your fingers in there. Stay clear of anything over 40V or so! AC 'tingles'; DC contracts your muscles and overrides any (millivolt) signals from your brain: your muscles won't let go! Bit awkward, that. A relative opened up a camera flash unit that had been off for a day (they don't have bleeder resistors to discharge them). He must have touched the charged capacitor; he doesn't *usually* scream loudly like that...
@MOHDFAISAL-qw8mz5 жыл бұрын
@@scottwillis5434 yes sir.... Right
@RyanJardina5 жыл бұрын
@@scottwillis5434 500v rated meter. The DC bus on a 480V AC input drive is about 680V DC 🤦♂️
@bch2780 Жыл бұрын
The way to solve problem is so simple, the complicated is the detail of parameters of each brand, How many brands in the market may be 100 brands
@kirkjackson3306 Жыл бұрын
Makes the job so much easier if, for example, the vfd reads a ground fault present. It allows you to make straight to that 3 phase motor and it's wiring,. Easy continuity testing. Such a help!
@Jimmyjackfruit2 жыл бұрын
Craig, I know the drive is not powered up, but watching you touch the U, V, W busses makes me jump. Haha! Great video.
@alejandromata825 Жыл бұрын
While the motor was disconnected and the drive was off you can also check the gates on the IGBTs with your meter on diode check, you can check the capacitors across the buses somewhat, you could also check the MOVs and the rectifier with a diode check as well.
@claudiuswilliams7829 Жыл бұрын
What if the VFD shows its running but there is no power coming out from the output phases. even though the VFD shows running . But when checked with a multimeter the VFD output to the motor itself has no power coming out of each phase..
@bobbyyoung28316 ай бұрын
Very much appreciated. Covered a bunch of info in a short time. Thanks
@pneumatic-generator20227 жыл бұрын
Thank you for your explain. i have a question . pls . a VFD can work with the dc source. if so can you give us clarificatons thank you .
@VFDscom7 жыл бұрын
Most VFDs out there are AC but some manufacturers make DC VFD. For example, Emerson has 2 lines of DC VFD.
@pneumatic-generator20227 жыл бұрын
thank you
@PBS-nm1uu4 жыл бұрын
this is a great presentation thanks, for all the info, made me a smarter person.
@allan_bomb7 жыл бұрын
Maybe you can describe how to check the rectifier bridge, if the SCRs are shorted and the capacitor in the next video. Also, before powering on the drive, you should always ohm the input terminals if they are shorted. Those are main causes of drive failure.
@SombraLocs6 жыл бұрын
Allan Valdez That's the video I'm looking for
@ackmino6 жыл бұрын
Allan - worked on many of these as a locomotive tech. Yes, the SCR/diodes fail more than anything. Basically you can find your problem using your meters diode check. They almost always fail shorted rather than open. The freq drives usually show the diode configuration on the panel cover.
@scottwillis54345 жыл бұрын
Just learn basic high-voltage precautions before starting work!
@richardcollins59314 жыл бұрын
VFD Repair - Industrial Solutions Authority, Hamilton Ohio, USA - Best turnaround time in the industry. Be sure to tell them Rich sent ya.
@jani1407 жыл бұрын
How can a normal vfd be able to put power back into the grid? It can't because normally on the utillity side of the DC bus is no inverter to do so. But if the motor feeds into the drive You could have a break resisor or DC break. Otherwise the drive will trip and let the motor free run
@jaythompson5102 Жыл бұрын
Can you explain why the power supply may be overvolting at night? I missed this concept somehow
@rocklymr157 жыл бұрын
Hey great video! Knew a lot of this before hand, but it was a great wrap up of a lot of basic issues. Any chance you have a video on VFD motor protection programming?
@maximochimfwembe5886 Жыл бұрын
I HAVE REPLACED AN FR-A700 WITH AN FR-A800 AND ENTERED THE SAME PARAMETERS THAT WAS IN A FAULT A700 INVERTER BUT THE DRIVE IS NOT WORKING.WHY?
@edgarbanuelos26605 жыл бұрын
Hi good morning I'm starting with vfd what book you recommend me
@talalalrahbi94305 жыл бұрын
THANK YOU SIR,,i have a problem with VFD is not working and the MCCB is burned ,,so what could be the causes of this issue?
@kevywevvy88337 жыл бұрын
On a mitsubishi inverter, 9999 in a parameter means it's set to dataplate ratings by default. Setting a 'real' value in there is usually a precursor to sensorless flux vector mode. Setting these away from 9999 must be followed by a flux vector autotune
@ramsahadeo94874 жыл бұрын
Now you made me smarter ...thank you
@zahirulislam79613 жыл бұрын
Running motor suddenly stop Vfd Display show, Err F 1301, what's the problem? Please tell me.
@1989Chrisc7 жыл бұрын
I was kinda scared when you started touching the power cables. I could hear a buzzing so was thinking it was powered up
@richardcollins59314 жыл бұрын
The stir fan alone on that drive would have been 120db, if it were on it would have been obvious.
@1989Chrisc4 жыл бұрын
@@richardcollins5931 I should have said live instead of powered up
@1989Chrisc4 жыл бұрын
@@richardcollins5931 or hot as you yanks say
@maximochimfwembe5886 Жыл бұрын
AN FR-A700 INVERTER HAS DEVELOPED A PROBLEM OF ONLY RUNNING IN ONE DIRECTION(FORWARD) BUT PREVIOUSLY IT WAS RUNNING IN BOTH DIRECTIONS AND I HAVE CHECKED THAT THERE IS NO SIGNAL FROM THE INVERTER(AT RUN TERMINAL) GOING TO THE PLC .WHAT CAN BE THE PROBLEM.QUICK RESPONSE WILL BE HIGHLY APPRECIATED
@en2oh4 ай бұрын
Do these drives have fuses? I have a drive that doesn’t even power on
@jonathanscott82262 жыл бұрын
Nice little video with great tips, thank you!
@zahirulislam79614 жыл бұрын
3 phase motor don’t run, VFD display show `fault` and E l l, what's the problem?
@abdullahghurbal374 жыл бұрын
Great effort and professional explanation Thank you sir
@brianstredder95256 жыл бұрын
Have an old Toshiba g2+. OC3 fault. No motor attached, still can't clear the fault?
@TangenyShikolalye6 жыл бұрын
pleae help meguys > i have mishubish A700 vfd but when i start it it only runs for 10 minutes then it trips, the it dispalys the OP3 ALARM , what could be the problem and what could be the cause
@spartaeus4 жыл бұрын
My Mitsubishi vfd goes back to default setting if I turn the power off to the vfd. Is that normal???
@josemiramontes42804 жыл бұрын
The mergency stop signal🤔???
@deepak96407 жыл бұрын
helo sir , i had a question 90 kw motor is controlled by danfoss vtl 6000 drive . when ever i check load of motor it is not constant some times it show 10amps and some time 50 amps. it showing variable load what should i do please help..
@VFDscom7 жыл бұрын
What is your application?
@deepak96407 жыл бұрын
It is used as exhaust fan
@corbeNification7 жыл бұрын
Test on another smaller motor. If it still shows the motor current incorrectly replace the current transducers. If problem persists replace the control card, Danfoss no longer support the VLT 5000 and 6000 I believe so you will have to source a second hand card..
@corbeNification7 жыл бұрын
I would also check the ribbon cables between the PCB's for continuity and the headers on the PCB's for corrosion.
@ishukaushikvideo61207 жыл бұрын
Dear sir May be some reasons for this type of problems. (1) check the motor winding resistance should be equal and in Ohms. (2) motor terminal connection should be not loose connection (u, v, W) . (3) may be possible Vfd CT have problems, need too replace or repair. (4) earthing should be proper between drive &exaust fan. (5) exaust fan should be not jam. Mob :8447550303
@madsteyn7393 жыл бұрын
how can i reset a allen bradley 1336 plus to factory settings?
@industrialautomationexpert7996 жыл бұрын
before vfd run Earth nutral viltage 1V, after vfd run Earth to nutral voltage 14/15 Volt-i need to solution please explain.we give Earth connection properly VFD to Motor. we use SUBMERSIBLE MOTOR.
@bigt95nt0110373 жыл бұрын
What is the best oscilloscope for troubleshooting a vfd?
@jb-ik8sj2 жыл бұрын
Do these work well with a 480 3phase generator?
@oregonsignalfan2 жыл бұрын
where can I find water-cooled VFDs?
@belkizaguinaga5032 Жыл бұрын
My VCU john zink turn off and gives me a code vfd 101 communication failure
@varune906 жыл бұрын
Dear sir vfd frequency going to low in auto mode what case this?
@AriVovp5 жыл бұрын
Why is this controller solarge for a 350hp motor, in the mean time , the controller for the Tesla Model s motor is tiny and light weight compare to this?
@jeremyhall93464 жыл бұрын
Dc..... tesla Ac...... this motor. Big difference.
@jprivacy50515 жыл бұрын
Great educational video man.
@JackDavidson-ov2tf6 жыл бұрын
Great video sir. Can you do a video on Siemens VFD drives? I have been running into issues on theses. Thank you
@anonymousperson25787 жыл бұрын
Excellent video!
@maryphiri45616 жыл бұрын
Hie can i run a say 1.5 kw 3phase motor with a petrol gen single phase using vfd? Anybody plz
@dosolmire94765 жыл бұрын
Please give me a Solution, Do you know how to fix ac drive problem, UVW unbalance output Voltage? U-V Voltage 7% less, compared to U-W & V-W Voltage
@alingeorge81607 жыл бұрын
Sir , for a 60Hz rated motor ,how much we can increase the frequncy ...? Plz help
@hast665 жыл бұрын
Depends on whole setup. When frequency increases, torque decreases until to point that the motor stalls. You're "lucky" if it still runs at 90Hz. But then, motorload should be probably zero.
@kjacoby4 жыл бұрын
Stefan Haesen yeah I didn’t think it would run that high?
@1krazmf8517 жыл бұрын
I put a dimmer switch on my ceiling fan. Po mans vfd
@scottwillis54345 жыл бұрын
That will result in extra heating, and the fan is running slowly so reduced cooling. At least keep an eye on it...
@mutunzanachisha22432 жыл бұрын
How to trouble shoot cfw-11 vsd
@franciscrasto4 жыл бұрын
Sir your explanation is simply great. .God bless you.
@drilonmuslii77257 жыл бұрын
VFD is not giving any output voltage. It seems that everything is OK with the wiring and the program but still I cannot get any output voltage. What can be the reason for this?
@VFDscom7 жыл бұрын
If the RUN light blinks then there is no Speed Reference.
@drilonmuslii77257 жыл бұрын
Thank you for your response. I've adjusted speed and other parameters but still I cannot get any output voltage.
@VFDscom7 жыл бұрын
Did you set your maximum speed to 60 or 50Hz? Did you set your run speed? Have you metered the input terminals to see if there are voltage on the inputs?
@drilonmuslii77257 жыл бұрын
there's voltage in input terminals. Also the the parameters are adjusted as they should be but still no output voltage.
@VFDscom7 жыл бұрын
What lights are on when it is running? Any error codes?
@LearningEngineering8 жыл бұрын
great thanks sir.
@jimbass9243 жыл бұрын
Great Profesional explanation!!
@ogbagiorgisabrha63553 жыл бұрын
It very good explanation I enjoy it very much.
@naivashatraveller5 жыл бұрын
5:09
@mithileshramteke38823 жыл бұрын
Good explanation thank you
@jakeblanton6688 Жыл бұрын
R= L1 S= L2 T= L3 N= Negative for DC Bus P= Positive for DC Bus P= ? U= T1 V= T2 W= T3 Would someone please explain to me what the second P stands for because Craig didn’t go over it. I would greatly appreciate it.
@Magneticitist11 ай бұрын
Well this is 5 months late and you know the answer by now.. but for the record this is typically the 'P+' connection where a DC Link Choke would go. So the choke itself is what would bridge the P and P+ terminals in order to close the loop to the DC bus. If the choke is not present, a jumper needs to be there in order for the DC bus to charge.
@sohailjanjua1233 жыл бұрын
Hi, I like your lecture. Thanks
@henzelmen3 жыл бұрын
Thank you sir, good and to the point information
@battsengelnansal47567 жыл бұрын
How to loading cell?
@alxk37137 жыл бұрын
Very Educational
@TheUkjedi3 жыл бұрын
Great video
@madchillen42057 жыл бұрын
What is a fault overload?
@jasmany197 жыл бұрын
When the motor is drawing more current than what the motor name plate is rated for.
@feedyourfaith73926 жыл бұрын
What is a current overload?
@eloymarquez47834 жыл бұрын
Great info! Thank you
@ltgaming85102 жыл бұрын
HOW TO TROUBLESHOOT COUNT OLAF
5 жыл бұрын
Good explanation
@kevinmithnick99935 ай бұрын
nice info sr
@arifmalik6607 Жыл бұрын
Sounds great
@creativeweirdo61934 жыл бұрын
Bruh I came here from a series of unfortunate events 😂
@josegeorgekadakampallil805511 ай бұрын
Thank you Sir
@primary12715 жыл бұрын
hey man you are the best
@antonioborges25764 жыл бұрын
Great info
@battsengelnansal47567 жыл бұрын
Not load power pault
@MOHDFAISAL-qw8mz5 жыл бұрын
Thanks guys
@dukewp54814 жыл бұрын
Hello Red River Electricians
@austinspivey74272 жыл бұрын
Who knew Donald trump was this good at troubleshooting VFDs
@abar71786 жыл бұрын
thank you
@rl76232 жыл бұрын
F70800???
@ВалентинПодольхов4 жыл бұрын
Great Thanks!
@coolworkshvac60433 жыл бұрын
awesome sir thank yoi
@nazgullinux66012 жыл бұрын
I know Donald Trump's uncle was a physicist and all that but I didn't expect to see the Don giving a VFD troubleshooting overview for a random vid like this lol.
@selvarasumanikandan76464 жыл бұрын
Thanks sir
@electroproject36555 жыл бұрын
thanx ..sir ...............
@xLSClanx4 жыл бұрын
😐
@creativeweirdo61934 жыл бұрын
Lol wut
@mikeadler434 Жыл бұрын
👍👍
@krankransegpatel9915 жыл бұрын
Hello
@isaacyaw79312 жыл бұрын
Great video. Thanks a lot. This man looks a little like Ex. Prez Trump haha