Hey thanks for vids i use viega fittings and love them. Can you explain for me? The initial test with air .5 to 45 Or 15 to 85 water is to determine that all fittings have been pressed and nothing has been missed? Otherwise the larger pressures can alter the sealing element if they arent pressed. So its critical to ensure no fittings go unpressed before testing with higher pressure ?
@ViegaLLC9 ай бұрын
Hi there! Exactly, the step-test procedure is used to ensure all fittings have been pressed before increasing the pressure in the system. Learn more about Smart Connect and our sealing elements here! bit.ly/3s8y97A
@michaelisakov11082 ай бұрын
So air pressure testing is upto 200psi? What did u mean about max psi at 45 psi?