Vijeo XD - Communicating to M221 using Modbus TCP

  Рет қаралды 16,448

Paul Derbyshire

Paul Derbyshire

Күн бұрын

How to Setup up a simple M221 project. How to set up EcoStruxure Operator Terminal Expert (Vijeo XD) to Communicate to the M221 using Modbus TCP.
EcoStruxure Operator Terminal Expert (Vijeo XD v3.0) project file - app.box.com/s/...
SoMachine Basic Project (v1.6) - app.box.com/s/...
Have you decided to try Vijeo XD? If so, you might be wondering about how to establish some basic communication to some Schneider Electric PLCs. In this article we can talk about getting communication going between Vijeo XD (EcoStruxure Operator Terminal Expert) and a small M221 SoMachine Basic PLC.
At present, March 2018, the best way to communicate to the M221 using Vijeo XD is with Modbus TCP (alternatively serial/USB). The steps are simple and straightforward.
After configuring the ethernet port for the M221 and adding 1 rung of instructions the PLC is ready for communication via Modbus TCP.
In Vijeo XD we add the Schneider Electric Modbus TCP driver. In the properties of the Mobus TCP driver we set the IP address of the PLC (hopefully on the same network as your PC/Runtime) and the addressing to IEC mode. That's it for the driver!
You can now add variables pointing at the appropriate driver name and IEC addresses you have used in the M221. Graphic objects are bound to the variable name as required.
To test the communication you can use the Vijeo XD simulation which can communicate directly with the PLC (even with the trial version). If all goes well you should be seeing and changing data in the M221 immediately.
For those interested in importing Symbols into Vijeo XD instead of addressing, this feature is coming very soon. Stayed tuned for my article on Vijeo XD Symbol Link as it becomes available.
Happy HMI development!

Пікірлер: 17
@YoungOby
@YoungOby 5 жыл бұрын
Hello thank you for that awesome video. I try to follow the step but the communication between my HMI on Vijeo and the M221 is not working. Is it because i am using the trial version? Is it possible to have the link to download the lastest Vijeo XD version too? Thank you :)
@PaulDerbyshire
@PaulDerbyshire 5 жыл бұрын
The latest version is available from here: download.schneider-electric.com/files?p_enDocType=Software+-+Updates&p_File_Name=EcoStruxure+Operator+Terminal+Expert.pdf&p_Doc_Ref=Software_Download_Instructions
@sarwerwasi2922
@sarwerwasi2922 4 жыл бұрын
@@PaulDerbyshire this link is not available, please share the updated link
@PaulDerbyshire
@PaulDerbyshire 4 жыл бұрын
@@sarwerwasi2922 The latest version of 3.1 SP1 is available here: download.schneider-electric.com/files?p_Archive_Name=Installation_File_v3.1_SP1.zip&p_enDocType=Software%20-%20Released&p_Doc_Ref=Installation_File_v3.1_SP1
@minhlenhat3088
@minhlenhat3088 5 жыл бұрын
I can't do it. I can't read or write values in simulated HMI. can you help me solve this
@PaulDerbyshire
@PaulDerbyshire 4 жыл бұрын
Sorry for the late reply. Please ensure you are using "Simulate", not "Device Simulation". You choose between them using the drop arrow for the play button. See at 5:00 onwards. kzbin.info/www/bejne/o4eum2prmN6eh7c
@anhtuan4304
@anhtuan4304 2 жыл бұрын
@@PaulDerbyshire Thank you
@allanjacob8047
@allanjacob8047 4 жыл бұрын
Is it possible to mirror a st6 series hmi on local network on to my pc?
@PaulDerbyshire
@PaulDerbyshire 4 жыл бұрын
We hope to release a verison of EcoStruxure Operator Terminal Expert next year in 2021 that includes remote viewing of the ST6 using an HTML5 compatible web browser (PC, tablet, phone).
@sgonzalez0502
@sgonzalez0502 5 жыл бұрын
Is it possible to communicate Vijeo XD with a modbus simulator in the same computer ?
@PaulDerbyshire
@PaulDerbyshire 4 жыл бұрын
Sorry for the late reply. Yes it possible. You can uses the PC IP address or 127.0.0.1 depending on the simulator
@DioinerFernandez
@DioinerFernandez 4 жыл бұрын
quiero comunicar el PLC221C24R con el MODEM SR2MOD03 alguien que tenga una idea?
@PaulDerbyshire
@PaulDerbyshire 4 жыл бұрын
You can use Modbus RTU or SoMachine protocol. Here is a reference to start. download.schneider-electric.com/files?p_enDocType=Catalog&p_File_Name=DIA3ED2160107EN.pdf&p_Doc_Ref=DIA3ED2160107EN
@LorentzIbanez
@LorentzIbanez 5 жыл бұрын
I can do the simulation if it is in trial mode Vijeo xd?
@PaulDerbyshire
@PaulDerbyshire 4 жыл бұрын
Yes. :)
@francisward7466
@francisward7466 5 жыл бұрын
Hi Paul, This is an excellent vid. Do you have any guidance on how I establish comms between a M221 and HMI that does not support modbus TCP? I am using a M221C16R and HMISTO715
@PaulDerbyshire
@PaulDerbyshire 4 жыл бұрын
M221C16R should support Modbus TCP Slave, so it is similar but you choose a different model.
Тестирую Modbus шлюз TCP→RTU.
12:00
Юрий Р
Рет қаралды 2,8 М.
Schneider m221 plc & C# ModbusTCP communication
22:14
Abdullah KARAKAYA
Рет қаралды 15 М.
Они так быстро убрались!
01:00
Аришнев
Рет қаралды 3,3 МЛН
Doing This Instead Of Studying.. 😳
00:12
Jojo Sim
Рет қаралды 37 МЛН
schneider m221 plc & delta hmi communication
11:26
Abdullah KARAKAYA
Рет қаралды 11 М.
Training - M221 - M10.1 Modbus TCP Communication Blocks
16:34
LeTomas AHUMADA
Рет қаралды 17 М.
Schneider 3 pcs M221 Plc ModbusTCP Communication
10:03
Abdullah KARAKAYA
Рет қаралды 12 М.
Comunicación de HMI Kinco con Schneider M221 (Modbus TCP)
23:23
IES Cavanilles ARI
Рет қаралды 14 М.
Discover Vijeo XD v3 0  (EcoStruxure Operator Terminal Expert)
9:40
Paul Derbyshire
Рет қаралды 17 М.
Они так быстро убрались!
01:00
Аришнев
Рет қаралды 3,3 МЛН