Hi !! How the current from the inverter is going to RTDS? This means what equipment in this setup is consuming power from the inverter?
@cengmusical2 жыл бұрын
Hi Maneesha - There is a four quadrant amplifier from the manufacturer Spitzenberger and Spies in the setup. The amplifier is capable of sinking power from the inverter. In terms of the current value, a sensor on the amplifier picks up the current and it can be input into the simulation using either the Aurora protocol or the analogue input card.
@maneeshaampolu54582 жыл бұрын
Hi Kiki Sparkles - Thank you so much for the reply :)
@ntubankhasi24602 жыл бұрын
hi there How do you set the plots in runtime to continuously show the graphs as it plots, not only when you update it? Thank you
@rtdstechnologiesinc.32492 жыл бұрын
Hi Ntuba - The plots don't display continuously for signals such as instantaneous voltage and current because of the huge amount of data. You can monitor slower-changing quantities (such as RMS values) by using a meter component, which can be displayed in graph format to give the effect of a continuous plot. There are some other options as well for data display of instantaneous values - please email support@rtds.com if you are a user working on a specific case.