Hi Bob, Thanks for the many videos you posted and it really helped me. Just a question if you can assist, Can I create two separate Alarm controls to work independently in winCC explorer V8 if I have two separate systems running in single project? Looking forward to hearing from you Regards.
@WinCCGURU3 ай бұрын
Yes you can! You are not limited on the number of alarm controls you can add to the project. They can all be filtered many different ways so for the other system, as long as you have the tags in there and put them in their own group then just filter that alarm control to show messages from the other system.
@MePregunto Жыл бұрын
Hello WinCCGURU. I'm currently struggling with WinCC v7.5 SP2, because I'm not able to set, for the message source (text) of an alarm, an internal tag (Text tag 8-bit character set. How can this be achieved? Is this applicable to external tags also? However, I managed to display this internal tag content a process value. Thank you
@WinCCGURU Жыл бұрын
You can use the insert process variables method. I’ll post a link to the video to show you how.
@WinCCGURU Жыл бұрын
Watch this video to show you how to insert the value of a tag into the message text. You will need to choose string as the format char %s. WinCC V8 Tip 7: Insert Process values Into Alarm Messages! ⏰ Learn SCADA Programming #WinCCGURU kzbin.info/www/bejne/qKDRin9vjcSVmtE
@Invitekz Жыл бұрын
HI, there is such a problem I created a warning message and added a sound (horn). the message works, but the sound does not work , then I did so first I added a sound (horn) to the class, then I added a message. Then the sound worked, but the message warning does not display
@WinCCGURU Жыл бұрын
Looking in to this
@stradadeb6 ай бұрын
Hi, I'm trying to set a Alarm group for OPC UA Tags, but in Tag Selection Dialog I can't see my tags list, i already logging this tags for Trends but i don't know if is not possible for Alarm logging of OPC tags.... Thanks!!
@WinCCGURU6 ай бұрын
Alarm logging only allows discrete tags such as unsigned 8,16 or 32 bit or binary. If your tags are signed or float they won’t show. You can however use them with analog alarms and set limits.
@farhanali934010 ай бұрын
hello sir, i could'nt find my wincc tag simulation window in wincc.. how to open that after starting runtime.
@WinCCGURU10 ай бұрын
Which version are you on? In WinCC v7.5 and higher it’s in WinCC control center. In WinCC 7.4 and lower it’s a windows app called tag simulator.
@farhanali934010 ай бұрын
I am using WinCC v7.5. But where to or below which...?? this option could be find out
@WinCCGURU10 ай бұрын
Look in WinCC control center. There is tag simulation editor.
@farhanali934010 ай бұрын
@@WinCCGURU sir i still haven't found this options in wincc 7.5
@farhanali934010 ай бұрын
I found tag simulation option below down the wincc explorer, but that didn't work like you have worked in uploaded videos tutorial.. What's the difference or changing i have to made Could you guide in that