Zone Control Valve Assembly | ZCV Practical | Firefighting | in Urdu/Hindi

  Рет қаралды 39,798

Tanweer Ahmed

Tanweer Ahmed

Күн бұрын

Пікірлер: 175
@vivekkalidas
@vivekkalidas 4 жыл бұрын
hi sir, thanks for your videos. i have seen lots of youtube video but nothing is clear as like yours. Even in firefighting course the teach like this.
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
Thank you
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
Watch my this video, then ZCV concept will be more clear: kzbin.info/www/bejne/h4bNgXuwlLdpg9k
@ziyamasad2709
@ziyamasad2709 4 жыл бұрын
@@TanweerAhmed Thanks alot too you .. brother...
@edwinuy9443
@edwinuy9443 2 жыл бұрын
Mashallah very Nice video & knowledge shearing. 🌟🌟🌟🌟🌟
@TanweerAhmed
@TanweerAhmed 2 жыл бұрын
Thanks
@vashishthparikh
@vashishthparikh Жыл бұрын
Your all videos are in so much details and depth. Even non technical person also understand. Thank you very much sir for all the knowledge you share. Really Appreciate
@TanweerAhmed
@TanweerAhmed Жыл бұрын
Thank you for your kind words
@kartikkapat293
@kartikkapat293 4 жыл бұрын
Best Chanel for fire fighting... Thank you sir.
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
Welcome
@farazkhan2279
@farazkhan2279 4 жыл бұрын
Knowledge ke alawa you have very good explanatory skills.. Great job
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
Thank you
@nisarsethar3949
@nisarsethar3949 4 жыл бұрын
Behtareen video hy.
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
Thanks
@mohammedmubeen4727
@mohammedmubeen4727 4 жыл бұрын
I saw this videos I got good knowledge thank you sir
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
Welcome 😊
@VArjun26
@VArjun26 4 жыл бұрын
Hi sir, please sharing videos related to fire fighting system. Very helpful information.
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
I will continue upload videos about firefighting in future. Thanks for your interest
@abhinavkumarsingh6792
@abhinavkumarsingh6792 3 жыл бұрын
thank you so much for such unique live information
@TanweerAhmed
@TanweerAhmed 3 жыл бұрын
Welcome
@junedalam7381
@junedalam7381 3 жыл бұрын
Nice video sir video banane ke liye thanks
@TanweerAhmed
@TanweerAhmed 3 жыл бұрын
Welcome
@niazhussain2993
@niazhussain2993 3 жыл бұрын
Sir thank you very much for site recording. Thanks thanks thanks
@TanweerAhmed
@TanweerAhmed 3 жыл бұрын
Welcome
@shahzadnadir8805
@shahzadnadir8805 4 жыл бұрын
Behtreen video
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
Thank you
@MirBaqirAliSethar
@MirBaqirAliSethar 2 жыл бұрын
Good knowledge
@TanweerAhmed
@TanweerAhmed 2 жыл бұрын
Thanks
@farhanhaider3734
@farhanhaider3734 4 жыл бұрын
I'm from unilever pakistan.....thanks for video
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
Welcome
@rehanzahid9600
@rehanzahid9600 4 жыл бұрын
Very nice bro...
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
Thanks
@Irfanali-gp7ev
@Irfanali-gp7ev 4 жыл бұрын
Zabardast video
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
مھرباني ...
@mzs9262
@mzs9262 4 жыл бұрын
Kammmmmmmallll love
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
Thanks
@habeebrk
@habeebrk 4 жыл бұрын
Good work bro
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
Thank you
@AjitKumar-ol8ue
@AjitKumar-ol8ue 4 жыл бұрын
Excellent
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
Thank you
@mohammadkhan3796
@mohammadkhan3796 Жыл бұрын
Thanks Mr tanweer
@TanweerAhmed
@TanweerAhmed Жыл бұрын
Most welcome
@faizankhan-bo7sl
@faizankhan-bo7sl 4 жыл бұрын
Important video
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
Thank you
@atif-aftab1atif330
@atif-aftab1atif330 3 жыл бұрын
GREAT
@TanweerAhmed
@TanweerAhmed 3 жыл бұрын
Thanks
@AsgharAli-mo7gx
@AsgharAli-mo7gx 4 жыл бұрын
السلام علیکم سر،زبردست ڈیٹیل دے دیا آپ نے شکریہ۔ لیکن سر یہ اسمبلی وال میں جو کیبل ہیں وہ mov کیلئے ہیں یااور کوئی کنٹرول ؟ اسکا تھوڑا سا اکسپلین کرلیں ۔ شکریہ
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
I will make video about control wiring of ZCV
@AsgharAli-mo7gx
@AsgharAli-mo7gx 4 жыл бұрын
@@TanweerAhmed thanks sir, we will wait Insha Allah
@muhammadejaz8021
@muhammadejaz8021 3 жыл бұрын
Excellent sir g
@TanweerAhmed
@TanweerAhmed 3 жыл бұрын
Thanks
@muhammadejaz8021
@muhammadejaz8021 3 жыл бұрын
@@TanweerAhmed Which video is suitable to learn basic about ducting?
@TanweerAhmed
@TanweerAhmed 3 жыл бұрын
Visit my HVAC playlist, almost all videos are about basics including ducting
@muhammadejaz8021
@muhammadejaz8021 3 жыл бұрын
@@TanweerAhmed thk ha thanks sir
@TanweerAhmed
@TanweerAhmed 3 жыл бұрын
Welcome
@mskvideo8950
@mskvideo8950 2 жыл бұрын
Sir aap Pakistan se ho 👍I'm from India thanks to information
@TanweerAhmed
@TanweerAhmed 2 жыл бұрын
Yes, from Sindh, Pakistan
@sherin7222
@sherin7222 4 жыл бұрын
Why check valve is providing in combined sprinkler riser ZCV Assembly . Please explain.
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
The requirement for a check valve to be included as part of the connection to the sprinkler system is to permit the standpipe riser to be drained and refilled in a limited amount of time should repair be necessary to any portion of the standpipe riser, fire department hose valves, pipe, and fittings, etc.
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
The check valve arrangements in ZCV assembly permit the standpipe system to be drained while allowing the sprinkler pipe to remain water filled. In general, the check valve between the two systems maintains the water volume supplied within the sprinkler piping, thereby limiting the drain and refill time of the overall combination standpipe/sprinkler system. In addition, when combination risers are cross connected (loop or dual feed), the check valves will limit the flow to the appropriate floor where sprinklers have activated and limit circulation of water throughout multiple levels of the building.
@sherin7222
@sherin7222 4 жыл бұрын
Thank you👍🏻👍🏻
@amitsinghal5955
@amitsinghal5955 4 жыл бұрын
Sir I have a godown of Confectionery of 300 square yard. What fire fighting system we should install. Please guide
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
Wet fire sprinkler system
@tanvirmunna5862
@tanvirmunna5862 Жыл бұрын
Assalamualykum sir. If i set the riser of sprinkler far from the stair. And set the zone controll at the middle side of the building. Is that issue ase per nfpa?
@TanweerAhmed
@TanweerAhmed Жыл бұрын
Standpipe system's hose connections, hose cabinets or hose compartments are required in landings of staircase and exit or entry doors therefore mostly riser pipes are installed on the staircase side. You can install a riser pipe in the middle of the building but pipes connection may be difficult/
@amulyapankaj3961
@amulyapankaj3961 4 жыл бұрын
Please make a vedio over water storage tank designing and pipe sizing methods at branch
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
I will.... insha'Allah
@MohammadAli-qp7gx
@MohammadAli-qp7gx 4 жыл бұрын
Thanks for your nice videos. Could you make a video for sprinkler hydraulic calculation method!
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
insha'Allah in future
@ashutoshpandey8680
@ashutoshpandey8680 4 жыл бұрын
High rise building me water pressure top par kitna hoga and overhead tank aur booster pump ke case me pressure distribution kaise kaam karte he please explain.
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
Kindly watch my firefighting videos and check in my playlist. I hope you will understand
@habeebrk
@habeebrk 4 жыл бұрын
Bro, I have a single zone wet sprinkler system, Does it required both alarm check valve and zone control valve or alarm Check valve only ?
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
Single zone means one zone therefore no need ZCV assembly and only required Alarm check valve assembly which will fulfill the NFPA requirements
@habeebrk
@habeebrk 4 жыл бұрын
@@TanweerAhmed Good, Expected answer, In a combined system (sprinkler &FHC) from where we start fire hose connection, normally FHC line will start just before zcv na? If no zcv, from where we start fhc line ?
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
@@habeebrk ZCV is not used in fire hose connection because we use manually fire hose and ZCV is required in auto sprinkler system
@habeebrk
@habeebrk 4 жыл бұрын
@@TanweerAhmed I mean for combined system
@nayeemsaleem7466
@nayeemsaleem7466 4 жыл бұрын
@@habeebrk as per your case as it is combine system you can take fhc individual connection from main sprinkler line but with isolation valve after each connection to control fhc.
@MuhammadAli-cc7cm
@MuhammadAli-cc7cm 4 жыл бұрын
السلام علیکم Dear Sir, Kindly make a video for supervisory switch and fire alarm. Thanks
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
Ok noted 😊
@motivationalquotes2.5m84
@motivationalquotes2.5m84 Жыл бұрын
Sir os& y valve and supervisory valve me kya difference hai
@TanweerAhmed
@TanweerAhmed Жыл бұрын
OS&Y valve with tempering switch will be supervisory valve. Also Supervisory Butterfly valve available. Here both function will be same but physical structure change.
@mohammadshahzeb2459
@mohammadshahzeb2459 2 жыл бұрын
Sir why we use test drain valve?
@TanweerAhmed
@TanweerAhmed 2 жыл бұрын
Because if sprinkler glass break then when have to replace sprinkler after drain pipelines. Moreover, if you drain valve without sprinkler glass break then ACV activate in pump room and FACP panel inform about zone activation
@habeebrk
@habeebrk 4 жыл бұрын
Bro, I have a light hazard building with 12000m2 area, Can I Provide Fire water supply with Single riser with single Alarm Check valve and multiple Zone control valves? Or 3 riser with 3 Alarm check valve is must? (Bcs asper nfpa single riser can serve 4000m2 area only)
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
your second option
@syedasadshah3931
@syedasadshah3931 11 ай бұрын
Boss Zone Control valve say flow switch ka distance kitna hona chiyay?
@TanweerAhmed
@TanweerAhmed 11 ай бұрын
2D
@ziyamasad2709
@ziyamasad2709 4 жыл бұрын
Assalamualaikum wr.please let me know for how much area one zcv will be considered.
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
As per std 8.2.1 on NFPA 13 it indicates an area of 3720m^2 per control valve, this works out to be 400 sprinklers per control valve
@ziyamasad2709
@ziyamasad2709 4 жыл бұрын
@@TanweerAhmed jazakaallah bhai...
@ziyamasad2709
@ziyamasad2709 4 жыл бұрын
@@TanweerAhmed what will be the main line pipe size if 3720m^2 and 400 sprinkles can be served ,is there any limitations of pipe size .
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
Kindly watch my video of pipe schedule method regarding pipe size & number of sprinklers. Also another video pipe schedule method for Standpipe
@riyasatali6368
@riyasatali6368 10 ай бұрын
@TanweerAhmed
@TanweerAhmed 10 ай бұрын
Thanks
@ajishashok6550
@ajishashok6550 4 жыл бұрын
Hi sir, Can you please do a video on Vertical turbine fire pump?
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
Ok noted and thanks
@siddheswarray9041
@siddheswarray9041 4 жыл бұрын
Sir fire fighting system installation drawing Ka upor video Di ja
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
There is available video in my playlist of firefighting. If you have any questions then you can ask
@abduljabbaransari8462
@abduljabbaransari8462 4 жыл бұрын
Good
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
Thanks dear
@abidameen7933
@abidameen7933 4 жыл бұрын
Aoa bro why there isn't nrv in zcva? And if I use gate valve instead of supervisory valve ?
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
W.salam, No need NRV in ZCVA because NRV is installed in Pump room. In firefighting standard used supervisory valve because this valve give ON/OFF status on FACP & also physically status, while gate valve does not provide this information.
@waqarahmed4593
@waqarahmed4593 4 жыл бұрын
I worked at Doha metro and we used NRV in zcva
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
If you are away from pump Room or no access in pump Room then you can use NRV. But NFPA-13 allow NRV with ZCV
@amr5125
@amr5125 3 жыл бұрын
ممتاز
@TanweerAhmed
@TanweerAhmed 3 жыл бұрын
?
@amr5125
@amr5125 3 жыл бұрын
@@TanweerAhmed great
@waseemnaveed1138
@waseemnaveed1138 4 жыл бұрын
AoA sir kya sprinkler 175 psi k pressure pr design nhi hte?
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
Max design pressure of sprinkler is 150 to 175 psi
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
But working recommend pressure is 50 to 75 psi
@waseemnaveed1138
@waseemnaveed1138 4 жыл бұрын
@@TanweerAhmed sir aik jagah zcv me contractor prv nahi laga raha hai kyu pump 8bar ka pressure deraha hai kehta hai zarurat nahi hai prv ki zcv me
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
If 8 bar = 116 psi pressure of pump then water move up side to floor then gradually pressure decrease in height therefore I also suggest to no need PRV with ZCV (standard recommend working pressure 50 to 75psi but should be under pressure of sprinklers design) if our sprinklers design pressure is 150 to 175psi then no need to install PRV with ZCV
@nayeemsaleem7466
@nayeemsaleem7466 4 жыл бұрын
It's a Pressure reducing valve. It is required to maintain pressure not more than 175 psi.
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
Ok
@mohammadshahzeb2459
@mohammadshahzeb2459 2 жыл бұрын
It's a function of prv rather than pdv
@matiurrahmankhan1889
@matiurrahmankhan1889 3 жыл бұрын
Tanweer Bhai agar kaam shikhna hoto kya Karin
@TanweerAhmed
@TanweerAhmed 3 жыл бұрын
Kaam sikhnay k leay kaam Karna paray ga. Start practical work like job
@PradeepKumar-uu9im
@PradeepKumar-uu9im 2 жыл бұрын
Whater curon nozal agar chalu ho jay to floor suich signal dega ae hame pata nahi janna hai
@TanweerAhmed
@TanweerAhmed 2 жыл бұрын
Yes, it will provide signal at fire alarm panel and you have reach at the zone where is happened
@engrikram876
@engrikram876 4 жыл бұрын
From where we take connection for outer fire hydrant in combined sprinkler and fire hydrant system
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
From discharge header of fire pumps
@engrikram876
@engrikram876 4 жыл бұрын
@@TanweerAhmed thanks to reply Please confirm me from header or from riser secondly what will be dia of 4 or 6 inch if our header is 4 inch
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
Riser means standpipe: this pipe is installed vertically for water flow upward to building, while hydrant are installed outside of building at ground floor (Note: no hydrants are installed inside of building, these are called landing valve or standpipe hose connection with or without cabinet and hose reel)
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
If header is 4" means your system is not combine system. In hydrant system, minimum main pipe should be 6" diameter as per standard requirements.
@engrikram876
@engrikram876 4 жыл бұрын
@@TanweerAhmed thanks to reply our header is 6 inch and hydrant are out side building My question is that we will take two connection from header one for riser and one for out side hydrant or only one connection for riser and than from riser we will take a connection for hydrants. Thanks for your valuable input
@jawheroueslati5681
@jawheroueslati5681 4 жыл бұрын
thanks for videos sir but i need documentation english because my langue arabic english please
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
I will try subtitles
@jawheroueslati5681
@jawheroueslati5681 4 жыл бұрын
@@TanweerAhmed thanks sir
@Rakib.Mahmud
@Rakib.Mahmud 4 жыл бұрын
Vaiya please Help me. NFPA As a rule how to calculated fire centrifugal pump water pressure bar and bar to galleon to pound. How to calculation. Please Help me vaiya.
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
Watch my video i.e. " NFPA-14 Pressure Requirements" which to be helpful for you
@Rakib.Mahmud
@Rakib.Mahmud 4 жыл бұрын
Thank you vaiya
@sahidahmed8092
@sahidahmed8092 3 жыл бұрын
Assalamualaikum Sir Aap Ka Company Ka hai
@TanweerAhmed
@TanweerAhmed 3 жыл бұрын
W.Salam, Karachi, Sindh, Pakistan
@dileshwarsahu6928
@dileshwarsahu6928 Жыл бұрын
Sir 1 ICV m kitne sprinkler install Kiya ja sakta h
@TanweerAhmed
@TanweerAhmed Жыл бұрын
What is ICV?
@dileshwarsahu6928
@dileshwarsahu6928 Жыл бұрын
@@TanweerAhmed installation control valve
@TanweerAhmed
@TanweerAhmed Жыл бұрын
As per NFPA 13:2019, 4.5.1 The maximum floor area on any one floor to be protected by sprinklers supplied by anyone sprinkler system riser or combined system riser shall be as follows: (1) Light hazard - 52,000 ft2 (4830 m2) (2) Ordinary hazard - 52,000 ft2 (4830 m2). Therefore on any one floor, you can install one Zone Control Valve Assembly and sprinklers quantity to be calculated according to hazard recommended area.
@hadinadeem3525
@hadinadeem3525 4 жыл бұрын
Kamal ka describe kya
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
Thanks
@kaworld6626
@kaworld6626 2 жыл бұрын
Bhai ZCV ka zikar hi nhi hai kahi 🙄
@TanweerAhmed
@TanweerAhmed 2 жыл бұрын
These all things are part of Zone Control Valve Assembly
@muthumuruganm9795
@muthumuruganm9795 5 ай бұрын
Please add English suptitle brother
@TanweerAhmed
@TanweerAhmed 4 ай бұрын
Ok noted
@zinanvlog3020
@zinanvlog3020 3 жыл бұрын
Assalamu alaikkum Sir aappka wattsapp nambar thega
@TanweerAhmed
@TanweerAhmed 3 жыл бұрын
Already shared
@MohammedVIPsmile
@MohammedVIPsmile 4 жыл бұрын
No English
@TanweerAhmed
@TanweerAhmed 4 жыл бұрын
I will make subtitles but it take time
@MohammedVIPsmile
@MohammedVIPsmile 4 жыл бұрын
@@TanweerAhmed thank you 😊
@sunilraj4423
@sunilraj4423 Жыл бұрын
Good
@TanweerAhmed
@TanweerAhmed Жыл бұрын
Thanks
Inspectors Test & Drain Valve for ZCV Assembly in Urdu
17:47
Tanweer Ahmed
Рет қаралды 11 М.
Alarm Check Valve Assembly - ACV Complete Detail in Urdu/Hindi
19:27
Don't underestimate anyone
00:47
奇軒Tricking
Рет қаралды 27 МЛН
SIZE DOESN’T MATTER @benjaminjiujitsu
00:46
Natan por Aí
Рет қаралды 7 МЛН
А я думаю что за звук такой знакомый? 😂😂😂
00:15
Денис Кукояка
Рет қаралды 5 МЛН
Fire Fighting Pump Room | Firefighting Fire Pumps in Urdu/Hindi
16:11
Tanweer Ahmed
Рет қаралды 352 М.
Fire Fighting Pump Room Installation Mistakes NFPA 20 in Urdu
20:07
Tanweer Ahmed
Рет қаралды 22 М.
The Future of Fire Safety: Alarm Check Valves and Zone Control Valves Leading the Way
31:26
SM Techno MEP Training Services
Рет қаралды 8 М.
Firefighting zone control valve ( ZCV ) practical installation in the site
4:12
The Engineering Galaxy - Engalaxy
Рет қаралды 41 М.
Main Components of Fire Fighting Pump Room Part 1 in Urdu
13:48
Tanweer Ahmed
Рет қаралды 166 М.
Don't underestimate anyone
00:47
奇軒Tricking
Рет қаралды 27 МЛН