Пікірлер
@muhammadrafique3603
@muhammadrafique3603 2 күн бұрын
We need MICOM E1 Battery Box
@user-cc8ps8tf1d
@user-cc8ps8tf1d 3 күн бұрын
Please can you make a vedio about distance relay test by doble software?please
@user-cc8ps8tf1d
@user-cc8ps8tf1d 3 күн бұрын
please I need to explain for doble tester software specially distance relay test by doble tester software
@user-qt3eb7tf4o
@user-qt3eb7tf4o 4 күн бұрын
Sir G what is the reason why this show phase to phase current ?I in normal condition current is zero
@zakirullah1826
@zakirullah1826 9 күн бұрын
Once again think you Sir ❤
@sijopaulthomas4182
@sijopaulthomas4182 Ай бұрын
Hi Pratik…How much time will it take to complete the test including the preparation for the tests on a single core CT for all theee phases
@avinashpatil4388
@avinashpatil4388 22 күн бұрын
45 seconds
@BhupendraPatel-qf4ux
@BhupendraPatel-qf4ux 2 ай бұрын
For one c. T. only S1 and S2, how to connect?
@BhupendraPatel-qf4ux
@BhupendraPatel-qf4ux 2 ай бұрын
Good information for study, thanks
@boatymcboatface45yearsago59
@boatymcboatface45yearsago59 2 ай бұрын
No idea what you said but the wiring connection helped me verify that what I was doing was correct. Thank you, please always show how you wire connections to the test set🙏🏼
@jims9916
@jims9916 4 ай бұрын
what is the function of poledead in undervoltage on P142
@pratikbhatt95
@pratikbhatt95 4 ай бұрын
If Voltage-current goes below set threshold value or CB open status through logic then it will be pole dead condition.
@Ya_Allah_madad-786
@Ya_Allah_madad-786 4 ай бұрын
Sir, is input DC IN 1 and 2 is 24 volt? Best regards
@pratikbhatt95
@pratikbhatt95 4 ай бұрын
No, this model is for 60-250V DC & 115-230V AC. For 24V you will have to choose different MFLB number
@Ya_Allah_madad-786
@Ya_Allah_madad-786 4 ай бұрын
@@pratikbhatt95 Thanks a lot
@mahmoodhameed3072
@mahmoodhameed3072 4 ай бұрын
Please to explain in English.
@kirankumar-zf9mx
@kirankumar-zf9mx 4 ай бұрын
Please send the link to download drivers
@kirankumar-zf9mx
@kirankumar-zf9mx 4 ай бұрын
How can I transfer old ALSTOM make micom 143 settings file to new Schneider make 143 relay
@kirankumar-zf9mx
@kirankumar-zf9mx 4 ай бұрын
Please provide the link for downloading this easergy studio software
@pratikbhatt95
@pratikbhatt95 4 ай бұрын
www.se.com/in/en/download/document/Easergy_Studio_Installer/
@kirankumar-zf9mx
@kirankumar-zf9mx 4 ай бұрын
Thank you
@KingBD328
@KingBD328 5 ай бұрын
Great job
@RahulKumar-sw2hk
@RahulKumar-sw2hk 6 ай бұрын
Thank
@chandraanand4102
@chandraanand4102 6 ай бұрын
7sk8012 model
@eeeknowledgesharingblog8994
@eeeknowledgesharingblog8994 6 ай бұрын
Sir, I've DIGSI software to Access siprotec series such relay. Would you please tell me - what interface port is used to establish connection with laptop for build up access, please.
@pratikbhatt95
@pratikbhatt95 6 ай бұрын
To connect 7sj600 series you will have to connect RS485 converter +ve to relay terminal 29 and -ve to terminal 28. Then using Siprotec 3 option in digsi, u'll able to connect. Make sure interface selection should be digsi v3 in relay. For Siprotec 4 communication related information please go through my 7sj8081 relay video 👇 kzbin.info/www/bejne/rmrXeWmjqdx1eKcsi=bZywDpoa7X_lg4ZZ
@GaurangMaruti
@GaurangMaruti 6 ай бұрын
Sir, PSL kaise banate hai ? Video banake share kiji ye
@pratikbhatt95
@pratikbhatt95 6 ай бұрын
Sir, It'll be available soon.👍
@SamiUllah-ks7oe
@SamiUllah-ks7oe 6 ай бұрын
Very well thanks brother 😊
@dnyanotech1404
@dnyanotech1404 7 ай бұрын
Very nice information
@aexm6527
@aexm6527 7 ай бұрын
I have to set the first earth chain threshold to 2A with TO 100/1 but the minimum value is 0.05 of the nominal value. come what should I do?
@user-gm4ph9fj7c
@user-gm4ph9fj7c 7 ай бұрын
Sir, how to copy relay settings to spare relay through Digsi software
@pratikbhatt95
@pratikbhatt95 7 ай бұрын
I got your mail, i replied over there...👍
@alokshahi1251
@alokshahi1251 8 ай бұрын
Nice explanation sir
@曾晁軒
@曾晁軒 8 ай бұрын
Sir,I have a problem. how can i leave monitor mode? Which is ''SIEMENS intern'' password?
@pratikbhatt95
@pratikbhatt95 8 ай бұрын
First try to initialise proper programme, or default programme with basic settings. If not working then contact me on [email protected]
@ankitbakshi9286
@ankitbakshi9286 8 ай бұрын
Sir, is there ny Institute where i get training of such equipment like ct analyzer kit, testrano 600,cpc 100? Plz help
@pratikbhatt95
@pratikbhatt95 8 ай бұрын
Actually fact is different, once you understand testing concepts these kits are so easy to use, sometimes there will be some queries which can be easily get clear from manual. Ofcourse there are some courses available in market but looking at cost & outcome, i suggesting u to do not waste money in it. Do understand concepts, read manual & learn yourself. Still you need to learn fast by someone, i am providing personal coaching with nominal cost at online & offline both platforms.
@tjjanarthananx
@tjjanarthananx 9 ай бұрын
Hi how to check relay has 1 A or 5A CT input? Waiting for reply.. Thanks in advance
@sehliboubekeur2542
@sehliboubekeur2542 9 ай бұрын
Salam Can I ask you for information? I have a problem with micom p142 when I inject the current I > the circuit breaker reacts and opens but when I inject the fault current the circuit breaker is in the open position it closes greetings
@pratikbhatt95
@pratikbhatt95 9 ай бұрын
Check PSL if there any closing logic mistake, if necessary check real time monitoring, so u can check live status changes. If nothing there from relay side then you need to check external wiring.
@sehliboubekeur2542
@sehliboubekeur2542 9 ай бұрын
Think you very much
@sehliboubekeur2542
@sehliboubekeur2542 9 ай бұрын
can I send you PSL to check
@AmanKumar-gy1he
@AmanKumar-gy1he 9 ай бұрын
Why it is required to short 2s1- 2s2.? If three core is there, then while testing 1s1-1s2 , is it required to short 2s1-2s2 and 3s1-3s2
@pratikbhatt95
@pratikbhatt95 9 ай бұрын
Omicron CT Analyser works on voltage injection method, so it can be done without shorting as well, i've also tried same, and it works fine. However it is standard practice for primary injection that CT secondary cannot kept open as it will create burden on CT, also mentioned in omicron CT Analyser manual to short other cores.
@AmanKumar-gy1he
@AmanKumar-gy1he 9 ай бұрын
@@pratikbhatt95 ok Thank u
@ruinica2118
@ruinica2118 10 ай бұрын
What digsi version are you using? Everytime i tried to connect it to digsi v4.92 it says cannot connecy
@pratikbhatt95
@pratikbhatt95 10 ай бұрын
You should have device drivers for same model & same or higher P-set version, which you can free download from siemens website.
@singhbains6903
@singhbains6903 11 ай бұрын
Sir how to communicate this relay via ethernet port
@pratikbhatt95
@pratikbhatt95 11 ай бұрын
There is no ethernet port available in these type of compact series, you can communicate with printer cable only...
@ahmadzubik7412
@ahmadzubik7412 Жыл бұрын
how i can download new virgin 4.79 to digsi 4 because the devise dont conaction ??
@pratikbhatt95
@pratikbhatt95 11 ай бұрын
If you are having no driver installed then you have to download from siemens website. It's available free. It will just ask you to register then you will able to download.👍
@ranjansahu2362
@ranjansahu2362 Жыл бұрын
Very nice sir... Psl kete banate hey... Ek panels drawing dekh k ..plz make a video on that
@pratikbhatt95
@pratikbhatt95 Жыл бұрын
Soon, It will be available...
@ranjansahu2362
@ranjansahu2362 Жыл бұрын
Great... Plz make a video on relay configuration
@meganathanbalasubramanian3395
@meganathanbalasubramanian3395 Жыл бұрын
How Can we read kw and kwh ,?
@pratikbhatt95
@pratikbhatt95 Жыл бұрын
In this version only current percentage value & amps value can be seen.
@meganathanbalasubramanian3395
@meganathanbalasubramanian3395 Жыл бұрын
Hi
@rezaulkarim1369
@rezaulkarim1369 Жыл бұрын
Sir, can you provide software to me.
@pratikbhatt95
@pratikbhatt95 Жыл бұрын
Software is available free on internet but you will have to get the key from somewhere...
@sktabrez786
@sktabrez786 Жыл бұрын
kindly 🙏 make vdo of siemens differential relay , oc relay communication and logic file
@pratikbhatt95
@pratikbhatt95 Жыл бұрын
It will be available soon...👍
@shravanthipk1442
@shravanthipk1442 Жыл бұрын
Haw to adjust relay display cotrast please explain.
@pratikbhatt95
@pratikbhatt95 Жыл бұрын
7sj6001 relay not having any screen light. So, no any contrast adjustment option.
@subhrajitdas1990
@subhrajitdas1990 Жыл бұрын
Thanks sir for relay training video..we expect more relay videos from u..plz
@oshovision-lx1jw
@oshovision-lx1jw Жыл бұрын
Make video on seimens and micom relay
@pratikbhatt95
@pratikbhatt95 Жыл бұрын
You already have commented on micom relay video. For siemens relay visit kzbin.info/www/bejne/rmrXeWmjqdx1eKc
@nabeelahamad5026
@nabeelahamad5026 Жыл бұрын
Mashaallah please very good and informative
@vasimkhanapathan7888
@vasimkhanapathan7888 Жыл бұрын
How to test thermal overload protection in this relay
@pratikbhatt95
@pratikbhatt95 Жыл бұрын
Give 2 times or multiple times current of thermal set value, if u need to match timing, set time constant (tau) value to 1min & inject current 2 times of set value, your tripping time will be around 17.26 sec.👍
@PrasathE-c5u
@PrasathE-c5u Жыл бұрын
is it possible to change the IDMT curve in Device configuration without DIGSI??
@pratikbhatt95
@pratikbhatt95 Жыл бұрын
You can't change in device config. without digsi. But if you already enabled IDMT in device config. then you can manually change curve in settings.
@PrasathE-c5u
@PrasathE-c5u Жыл бұрын
@@pratikbhatt95 shall we do in trial version of DIGSI
@nabeelahamad5026
@nabeelahamad5026 Жыл бұрын
Mashaallah very good sir
@viewpointelectrical3800
@viewpointelectrical3800 Жыл бұрын
Keep it up
@viewpointelectrical3800
@viewpointelectrical3800 Жыл бұрын
Good 👍
@sanjeevrai913
@sanjeevrai913 Жыл бұрын
One more question sir, In my plant one of the micom relay keypad is not working only book and C is working when we press. I want to know what is fault and what is reason behind...... Is only keypad change is option or anything else. However relay is not so old and key pad looking in good condition. Please provide some idea in this regard. Your videoes is very much understandable and nice.... Keep it up.
@pratikbhatt95
@pratikbhatt95 Жыл бұрын
In Siemens you can change front facia if there any problem. But in Schneider you don't have that option, if it is under warranty contact to Schneider or you have to replace the relay. Also Sometimes if you toggle DC, keypad get working again(10% chance only).
@sanjeevrai913
@sanjeevrai913 Жыл бұрын
Sir, Micom relay ka PSL kaise banate hai...... Brief me video banaye please
@pratikbhatt95
@pratikbhatt95 Жыл бұрын
Sure👍