Wilkins 975XL question: How do I removed the water from this unit? Especially in the regulator section. Unfortunately mine froze with an early winter in Virginia. I found water dripping from the vent and at the plate attachment joint. Do you think it is salvageable? I did finally get the system blown out but too late. Could I replace the diaphragm and O ring? Already turned the check valve rubber. Visual inspection of the seats look OK. Thanks for your help. Found a new unit damaged box 975XL on EBay for $300.
@backflowsupplyslcut93945 күн бұрын
For the 975XL 2" or smaller line size to drain the water out you just need to turn your supply off and open the test cocks and that will drain the water out of most of the assembly. But because of the design you need to take the cover off of the #2 check valve that sits behind the relief valve and the cover points down to the ground at an angle. After you get the water out then put the cover back on for the winter. The relief valve will not be an issue. But if you want to make sure you can remove the relief valve cover and let the water out, which may require pulling the diaphragm away from the housing. Sometimes they get stuck there from being bolted tight. Then make sure the handles on both ball valves are turned to a 45 degree angle to leave the valve part way open to lessen the chance of the ball valves from freeze damage. As far as if yours is still good or not I couldn't say without examining it. Even then sometimes you can get some warping that is difficult to see. If it was full of water you could have damaged the housing. Look inside the housing of both checks. You want to look closely at the seam where the two body halves are joined together. That is where you will typically find cracks and separations. These do not always go completely through the body to cause it to leak on the outside but it does make it so components can't seal.
@NapoleonLadell12 күн бұрын
My unit is leaking from the top of the what you suggested I do, should I replace it. Thank u
@backflowsupplyslcut939411 күн бұрын
I need more information. Do you have the model 720A? What size is it? Did you have freezing temperatures assuming it is outside? Have you taken it apart to inspect the parts? If you want you are welcome to call me at 801-355-6736 or email me at [email protected]
@IgorShapovalov-e1dАй бұрын
Thank you. very good education video!
@apriliaguy4life198Ай бұрын
Just saw this was my system was just installed this year. My installer blew it out last week and left the handles at a 45 as you suggest. He left the petcocks in the open position. Is that correct? Thanks
@backflowsupplyslcut9394Ай бұрын
Yes. I don't think it matters much with the test cocks. It is possible for them to get freeze cracks but if you want to try and move the slot to 45 degrees you can. Remember every quarter turn is open and close so you want to be in between the open close points.
@jaideepbhatiani97992 ай бұрын
Great video. Is it correct to say that the backflow device gets water from the in pipe and when you need to winterize the sprinkler system, you have to close the 1st valve for the in pipe or is that not the case? I'm trying to winterize my sprinkler system and I'm trying to identify, if any valve from your setup in the video needs to be closed 1st before putting an air compressor to the water pipe, coming in from the city? Basically, I'm tying to identify the backflow valve, so I can close it, in order to winterize my sprinkler system. My pipe is similar to your video setup. I hope, what I said, makes sense?
@backflowsupplyslcut93942 ай бұрын
If I understand you correctly you want to shut your water off to your sprinkler system and winterize the backflow assembly and sprinkler system. You should have a shut off valve in your basement or deep in the ground that shuts the water off to the system. You don't want to use the one on the inlet side of the backflow assembly because that will leave the pipe leading to the backflow assembly full of water and you can freeze and break that. And the ball valve. Find that ball valve and shut it off. Then open the test cocks on the backflow assembly. Test cocks four small valves that have a screw slot on it. A quarter turn opens it and that will drain most of the water out of the assembly. Depending on your model of assembly you my need to take a cover or two off to finish draining it. There is no need to blow through it and most manufacturers recommend you don't. People do it because that is where the easy connection is. You should have a blow out valve after the backflow assembly but most people don't. If you do hook up to the backflow I would hook up to the last one in the direction of flow. When you are done turn the handles on the ball valves to a 45 degree angle so the ball valves are not all the way on or off. That is the best way to keep those from freezing. If you have more questions you can call me at 801-355-6736
@JD0222 ай бұрын
Which direction should the test cock inside my home be going? Should it be parallel or perpendicular to the water line? Currently it’s parallel
@backflowsupplyslcut93942 ай бұрын
if the screw slot is turned in line with the flow out the testcock that is open. If the slot is turned across the test cock it is off. Every quarter turn is open close. It doesn't tighten, it is just a ball valve you are turning on and off. If water is coming out of it turn it a quarter turn either way. If it turns the water off leave it there . If you need to call me you can. 801-355-6736
@vlogsurfer2 ай бұрын
Wow! What a great video! You made it very easy to understand and touched on all my questions. Thank you very much
@davidschalk29302 ай бұрын
I need a number to call to order parts
@backflowsupplyslcut93942 ай бұрын
sorry for the delay. 801-355-6736
@SayteaMorrilex-n8b2 ай бұрын
Smith Brenda Garcia Nancy Clark Daniel
@desideriojuarez9433 ай бұрын
you did good , can you please show how to repair the other parts of the RPZ
@backflowsupplyslcut93943 ай бұрын
I didn't realize I never have done an entire repair video on this. I will have to do that. But until then here is a video from Zurn Wilkins channel, kzbin.info/www/bejne/maW8oKGEfNSaf6csi=r8dVZ-TlZI9H73RE
@charro2me4 ай бұрын
There is a plastic part underneath that is leaking. Don't know how to add picure.
@backflowsupplyslcut93944 ай бұрын
Sorry for the delay in responding. You can email the picture to me at [email protected] and confirm the model and size and the issue and I will get back to you.
@eddiehernandez48864 ай бұрын
Where would I find my cleanout pipe?
@backflowsupplyslcut93944 ай бұрын
Eddie, this would be something you would want to contact your sewer department. Depending on the age of your system it may be geo tagged. Some people see them sticking up above the ground a little bit. Sometimes even asking neighbors where theirs are can give you an indication where to look. To my knowledge they are all going to be accessible from outdoors.
@alexramirez55624 ай бұрын
Do you have a link on the video you did to take the seats out
@backflowsupplyslcut93944 ай бұрын
I don't think I ever did that video. I would have to search the videos.
@CaraLake-d4v4 ай бұрын
Thank you! This was super helpful
@clinteastwood69864 ай бұрын
Awesome tutorial. Thank you.
@dskrpncs4 ай бұрын
Homeowner here. Curious what you think might be wrong here. When I turn on the water too the system the Wilkins 720 PVB seals and the mainline fills. When I activate zone 1 the PVB leaks and nothing comes out of any of the heads. What might you recommend? Thank you!
@backflowsupplyslcut93944 ай бұрын
I am guessing when you activate zone 1 and the PVB leaks, it means it is dumping all the water that would be going to the zone. Is that correct? Does this do it on any other zone? It sounds like you are losing too much pressure after the PVB. Either there are too many heads on the zone or there is a break between the valve and the heads. For some reason too much water going out and not enough pressure to sustain the float of the PVB to keep it sealed. Call me if you need to and we can talk. Sean, 801-355-6736
@stevecarvalho69375 ай бұрын
What an educational video. Thorough and succinct explanation. Thank you
@squebler5 ай бұрын
Thank you. Now I know how to open and close my test cock valves.
@rhinotown766 ай бұрын
You should do all youtube videos. Great explanation.
@joelsander82896 ай бұрын
Excellent information! This is the fourth video on this regulator that I watched and is the only one to explain what I was doing wrong. Problem solved.
@robertkoellisch4706 ай бұрын
Just noticed a small drip coming out of the horizontal test cock. Is there a remedy for this or is this normal? Thank you!
@backflowsupplyslcut93946 ай бұрын
No. It is not normal. Make sure the screw slot is turned straight across the valve. Every quarter turn is open /close. If it is then it might be time to change the test cock or you can go buy a 1/4" brass plug, teflon it and put in if it is a female ended test cock. If it has a male end then buy a cap. Or you can replace the test cock. I am guessing your assembly is a 1" or smaller line size so that means you need a 1/8" male fitting (that goes into the body of the assembly) by a 1/4" female, or by a new one. Here is the link to the test cocks on our site. backflow-supply.com/search?q=test+cocks&options%5Bprefix%5D=last
@robertkoellisch4706 ай бұрын
@@backflowsupplyslcut9394 I thought I had it stopped but now it's not just dripping but more like spraying out where the plastic plug fits. I tried to teflon tape the plug until I can order something but that didn't work either. How do I know which size plug to order and does it need to be lead free? Thank you!
@backflowsupplyslcut93946 ай бұрын
@@robertkoellisch470 Is the screw slot going in the direction of the flow or across the test cock. It should be going across the test cock. If you need a plug in it for now and it is a female test cock you need a 1/4" male plug. If it is a male flare fitting you need a 1/4" flare fitting (cap)with an o-ring on it to stop it.
@CassandraZachary6 ай бұрын
I have the one on the left but when I remove the bonnet it’s a black piece with only 1 long piece it’s so hard to even remove I can’t get it to budge. Any advice ?
@backflowsupplyslcut93946 ай бұрын
I wonder if you have a different model. Both of these are the Wilkins 720A. I wonder if you have the Wattts 800M4 PVB? kzbin.info/www/bejne/qaK8pKuAf9Bro5Y Watch this and see if it helps. You are welcome to send me pictures to [email protected] or call at 801-355-6736
@petersonfamily62236 ай бұрын
Thanks, I had reduced pressure on all zones and my 800M4 was squealing when running. I took everything apart and cleaned it and ensured there were no cracks and or any damage. The difference is my float has a center tube with an internal spring the fits up into the bonnet center spring area. The pressure has returned minus the squeal but I now have a small leak and was going to replace everything inside our 20-year-old Watt 800M4 R regulator but I am not able to find a kit with the same float. Help and thanks again.
@backflowsupplyslcut93946 ай бұрын
I am not sure which size you have. 1" is most common, but here is a link to the parts for the 3/4" backflow-supply.com/collections/all?filter.p.m.custom.watts_models=800M4&filter.p.m.custom.sizes=3%2F4%22 and the 1" backflow-supply.com/collections/all?filter.p.m.custom.watts_models=800M4&filter.p.m.custom.sizes=3%2F4%22 just depends on if you want just that part or a complete kit. Call me if you have questions Sean 801-355-6736
@lindastretch25226 ай бұрын
i good looking
@shanew73616 ай бұрын
What if it's not leaking water but the pressure test failed to submit to tne County?
@backflowsupplyslcut93946 ай бұрын
I am not sure I am following your question. You had the assembly tested and it failed? That is a possibility. The air inlet could have opened below the required 1.0 or the check valve in the bottom could have leaked or not held at 1.0 or above. This would require perhaps a simple cleaning or rubber parts or complete parts. Hard to determine without seeing the components and knowing what the issue was in the first place. You are welcome to call me at 801-355-6736 and ask for Sean or email me at [email protected]
@shanew73616 ай бұрын
@@backflowsupplyslcut9394 Yes I had the pressure tested and it failed. Otherwise, its functioning fine zero issues.
@backflowsupplyslcut93946 ай бұрын
@@shanew7361 Maybe I need to clarify. Did someone come out to do a specific backflow test, using a gauge and they hooked a hose up to it? Did they leave a copy of the report?
@shanew73616 ай бұрын
@backflowsupplyslcut9394 Correct, and no report was given. I'm having a different plumbing company retest it.
@backflowsupplyslcut93946 ай бұрын
@@shanew7361 Make sure you ask them to explain why and how it failed so you know what you need to fix it.
@lindastretch25226 ай бұрын
i good looking
@lindastretch25226 ай бұрын
and a good looking one +
@lindastretch25226 ай бұрын
a nice looking too
@lindastretch25226 ай бұрын
i got it
@kev70176 ай бұрын
I’ve learned a lot from this video. And now I know that the guy who installed mine didn’t know what he was doing. So now I will have to have it re-installed. I wish there was a way I could show you a picture of mine.
it is not uncommon for a new install to leak. There could have been debris, such as rocks, sand or rust in your pipes that when turned on got stuck in the #1 check. I am assuming this is on a lawn sprinkler system. If so turn a zone on that will get more flow going through the heads than what is coming out of the relief valve. If it stops leaking out of the relief valve when the zones are running the problem is in the #1 check assembly. If it doesn't it is in the relief valve. Almost always it is in the #1 check assembly. If you determine it is in the #1 check take it apart and look for rocks, rust, even teflon tape or pipe dope. Clean it out, flush the line for a minute or so with the part out and the cover off then reassemble and try again. If you still need assistance you are welcome to call me at 801-355-6736.
@tonyleopard66106 ай бұрын
I have a brand new backflow just out of the box that’s leaking just like that
@mikeheilman33687 ай бұрын
I installed a new RP4A, bled the input and I'm sure its installed in the right direction but as soon as I turn the water on it starts gushing out the bottom. The unit is brand new so what might be the problem.
@backflowsupplyslcut93947 ай бұрын
Maybe you have resolved this already. But the first thing to do is to get a flow going through the backflow assembly greater than what is coming out the relief valve. I am assuming this is going to a lawn sprinkler system. Even though it is dumping water turn a zone on that will get the required flow of water and observe if it stops dumping. If it does you know there is an issue in the first check valve. If it doesn't it is an issue with the relief valve. It is not uncommon on a new install for debris in the line, rocks, rust or other debris gets flushed into the first check. Take it apart and see if that is your issue, inspect the rubber and the seat to make sure they didn't get damaged and put it back together and turn it on again. Hopefully it doesn't dump again. But sometimes it will and it could still be more debris in the line. I have seen a few issues with the relief valve in the last year in brand new units. So far I have not been able to determine the cause but have provided those that brought the unit from me with a new relief valve and it has solved the issue. This is rare. You are welcome to call me at 801-355-6736 if needed. Ask for Sean.
@riverraisin17 ай бұрын
I wish you hosted all how to videos on KZbin. Outstanding job!
@backflowsupplyslcut93947 ай бұрын
Thank you very much.
@zeero627 ай бұрын
Is it an optical illusion or does the apparatus on the right look bigger than the one on the left? I don't see any size specification on the 720-A that I'm looking at here at home.
@backflowsupplyslcut93947 ай бұрын
If you are referring to the two assemblies in front of me in the video, the old one is a 1" and the new one (the left) is 3/4". But the bodies are the same for 1/2", 3/4" and 1". You will be able to find the size raised in the brass on each of the ball valves. It will be marked as a 3/4" or 1" most likely.
@zeero627 ай бұрын
@@backflowsupplyslcut9394 Thank you, I will take a 2nd look.
@bulletchicken7 ай бұрын
Great video. Very informative. Thank you!
@diverutah7 ай бұрын
Excellent video, very informative! Thank you
@riverraisin17 ай бұрын
Correction. Yes you are a videographer. You just don't realize it. This instruction video is as good as it gets on KZbin.
@LindaHeck-rs3jq7 ай бұрын
I have a Wilkins Zurn Model # 975XL It is leaking out of the diaphragm in the center hole. What is causing this?
@backflowsupplyslcut93947 ай бұрын
The leak out of the hole on the RV cover is one of three reasons or a combination. When you take that cover off the nipple end of the RV assembly may still be stuck in it. The part that fits into the cover has a plastic piece with an o-ring on it. Either the plastic could be cracked or broken or the o-ring is damaged. Lastly, it could be the cover plate inside where the o-ring seals is corroded or pitted. If the corrosion can be cleaned out and it has not pitted the brass you may be good or you may need a new o-ring. But regardless it is one of those reasons or a combination of them. Call me if you need to 801-355-6736
@wittmf7 ай бұрын
GREAT instructional video!!! My exact unit and NOW I understand it well, Thank You!
@GaryUllmer-dk2tk7 ай бұрын
How do you drain the supply line? do you need too?
@backflowsupplyslcut93947 ай бұрын
IF you are referring to winterizing, I guess it would depend on your system. For example, I have a stop and waste and it should all run out of that. If your valve is in your home there should be a way to drain it as well.
@neilwoller7 ай бұрын
Thank you for this. I now understand why it's only 1/4 turn.
@uptoolate27938 ай бұрын
Thank you. My valve, which I installed myself to please the water district, is 16 years old. This leak happened only once before today. That was 10 years ago. I forgot what what I did to fix it last time. I watched a more technical video earlier today that gave me the confidence to tackle the leak. It amazing what I remembered. But your video confirmed for me I made the repair correctly. No stones or debris. Nothing I could see but a depression of wear in the washer so I flipped it over. Repaired for zero cost. Again, thank you.
@backflowsupplyslcut93947 ай бұрын
You are welcome. Just know flipping the disc won't last as long as before you flipped it as it is hitting in the same spot as the side you just flipped. It now doesn't have any support or strength on the other side. It is intended to be a temporary fix.
@andyrowe14248 ай бұрын
Great ...now you have homeowners repairing backflows...they arent trained and qualified to repair and test any testable backflow device !!! Thats why plumbers have licenses to protect our public water utility
@backflowsupplyslcut93948 ай бұрын
I understand your concern. However, they are going to do it anyway and in many places codes allow them to do it. These videos are also not just for them but those that are licensed to do it. Many of them do not understand how to do it either and know very little about installation requirements for them.
@uptoolate27938 ай бұрын
Union plumber much?
@johnmccracken80238 ай бұрын
Thank you for this very important video repair guide.
@chrisroberts87398 ай бұрын
You mentioned that the washer has a "beveled edge" that goes under the head of the screw. The washer just looked flat to me. Do you mean it is slightly concave? In either case, could you be more specific on what way that the metal washer should go? What are we looking for? Thanks, Crzzy1
@backflowsupplyslcut93948 ай бұрын
The washer shouldn't be concaved. It should be flat. But one side should extend a fraction wider than the other side. The side that should go against the washer is the longer side. And the edge of this side feels a little more sharp. The other side that is away from the rubber disc is more rounded. I have found out since that according to Wilkins it doesn't matter, but I have had an experienced technician of several decades tell me it does matter. I think over time the washer might not be as easy to distinguish the edges as I think they wear away. You should be able to tell by the staining on the washer from the water what side was not against the rubber disc. Not sure if this helped, but I really think putting it on will not be noticeable.
@chrisroberts87398 ай бұрын
@@backflowsupplyslcut9394 Thank you for the prompt reply! 🙂
@qing78 ай бұрын
Thank you for your sharing. I have the same pressure breaker and I am having hard time to take the bonnet off, it is so tight and maybe rusty. I have tried oil on it but it doesn’t help. Do you have any suggestions? Thank you!
@backflowsupplyslcut93948 ай бұрын
Take a hammer and gently tap around the outside of the housing at the top where the threads of the bonnet go down into the body. See if that will help loosen it up. if you are not using a long bar of some sort to put in between the three "legs" that the screws go into that the canopy attaches to I am not sure how else to get it out.
@qing78 ай бұрын
@@backflowsupplyslcut9394 It works!!! THANK YOU SO MUCH!!
@backflowsupplyslcut93948 ай бұрын
@@qing7 Glad it worked, but what worked specifically? The tapping with the hammer, the long bar to turn it with or both?
@k24accord19938 ай бұрын
Did he just use a tool for a shut off valve....video skipping in 3,2,1
@partyhotline8 ай бұрын
Shut off SOV#2 is all you forgot.
@backflowsupplyslcut93948 ай бұрын
What did I forget about the #2 SOV??
@Cody-e1v8 ай бұрын
What does the number 4 test cock have to do with the number 1 check valve? You failed to explain how the number 4 test cock stopping the relief valve from leaking means that. Your number one check is bad?
@backflowsupplyslcut93948 ай бұрын
Opening the #4 test cock or if necessary opening a valve down stream that gets a greater flow through the assembly than what is coming out of the relief valve is a means of trouble shooting if the issue is the #1 check or the relief valve. It in effect allows the relief valve to fully close if it is a number one check issue. But if it is a relief valve issue it doesn't matter if water is flowing or not and you will know where to focus your efforts in your repair or cleaning.