@@benzblogsVlogs kumpari mi ni sisoy, co-woker me sauna sa klift
@SurajSingh-wb6vq4 күн бұрын
Good evening sir.. I have deep see 7320 everything is ok fail to stop No oil pressure connect (disable) Charging alt voltage 0 Ac voltage.o Temperature sensor disable Why he come ..sir Remove the main fuse DC after clear sir ..why..?
@benzblogsVlogs4 күн бұрын
Sir why all disable all protection this after carban you know why this happen no proper maintainance
@SurajSingh-wb6vq4 күн бұрын
We are use one other controller caterpillar Genset.. 7320useing only AMF Function Main fail.give the command state rely after rely use the contact no.nc..then normal state caterpillar Genset... frequency and normal everything....but which time I stop da Genset...normal stoping also normal .after come fail to stop...
@agent70vids34 күн бұрын
Yung DSE 8610 MKII ng cummins genset namin, pag start mo nag crank sya at umaandar, ang problema wala syang display na voltage, speed, frequency as in no display ng parameters. Ano kaya problema??
@benzblogsVlogs4 күн бұрын
Check mo sir gamit multi meter para sure kong may volatge talaga after kong meron check mo sa likod ng module yung wire na V1 kong may pomasok na voltage okay po
@agent70vids34 күн бұрын
@@benzblogsVlogs wala sya kahit ano, hindi lang po voltage wala, pati rpm, frequency wala din
@agent70vids34 күн бұрын
Ang nasukat ko 2-3V lang po. Hindi po kaya loss of excitation?? Paano po mag excite??
@feisalabdul88975 күн бұрын
I need soft copy of this training can I get it?
@benzblogsVlogs4 күн бұрын
Yku can download in the internet
@ziakhattab66876 күн бұрын
No introduction for setup , purpose of initial AVR adjust, Nothing about software, for putting Load what you use, How you make leakage current , what was Alarm and trip setting . Bro simply no Information is there. But keep it up 🎉
@benzblogsVlogs6 күн бұрын
Bro during the config you most know the earth leakage acceptable in area been use for generator u most know the percntage depends on what customer need where always refer to the set poing what they needs
@benzblogsVlogs6 күн бұрын
If u need the setpoint i can assist you just message me
@benzblogsVlogs6 күн бұрын
No worries i expalin it to you if inhave extra time you know that my tome is to short to have this video
@MechanicalSHAFT-nr9cj6 күн бұрын
Thank you very much. But the quality of the video is poor you move a lot. it will be better if you work and somebody else film for you. Also please mention the software and the device you hooked your computer to.
@benzblogsVlogs6 күн бұрын
This avr we use here is der1 and for the connection to computer
@benzblogsVlogs6 күн бұрын
And the software is dxr reader
@jubsofficialvlog14736 күн бұрын
Nice one again idol Ikaw na talaga...
@benzblogsVlogs6 күн бұрын
Trying hard lamg lods to achieve our job
@achillembock38837 күн бұрын
alarme gen short circuit electrical trip cause et cmmnt le résoudre
@benzblogsVlogs7 күн бұрын
Short cercuit is just double the amount of your fl
@achillembock38837 күн бұрын
bonjour besoin stp le logiciel pour la config des cartes dse et un turto sur cmnt configurer
@benzblogsVlogs7 күн бұрын
In plc yes can be configure
@DanushkaLakshan-jz8mx7 күн бұрын
❤🎉
@benzblogsVlogs7 күн бұрын
Shukran
@jubsofficialvlog14737 күн бұрын
Nice one lodi
@benzblogsVlogs7 күн бұрын
Salamt lods
@mianasif33628 күн бұрын
❤
@johannwentzel112510 күн бұрын
Where is the link on how to fix the corrupted memory please?
@benzblogsVlogs10 күн бұрын
No need the link just follow update the firmware that it just make sure that you softeware is updated
@CAHBOSOK10 күн бұрын
Good night sir i have problem about my oil pressure sensor in my 900kva generator diesel engine. How i can consultation about my engine?
@benzblogsVlogs10 күн бұрын
Hi sit
@benzblogsVlogs10 күн бұрын
How are you if you have pil pressure problem din check first the wiring check the oil viscosity chrck whin you change oil or maintenance thin after that if same problem replace it
@user-qj8yh9ef6v11 күн бұрын
Great
@benzblogsVlogs10 күн бұрын
Thank
@adelineofficialtv208812 күн бұрын
nice tutorial
@benzblogsVlogs12 күн бұрын
Hallo po thank yoj
@casterjackson241012 күн бұрын
Is it the same with the china version sir? Im having problems where no voltage output on the actuator. Cant raise the speed.
@benzblogsVlogs12 күн бұрын
Meaning if no output from the speedcontroller from the actuator not mean the speed controller is defective checkbfirst the mpu
@jubsofficialvlog147313 күн бұрын
Ikaw na talaga lodi..
@benzblogsVlogs13 күн бұрын
Trabaho lang lods
@ali.dieselenginesmechanic635615 күн бұрын
Thanks brother Please can you give me whats app number thanks
@jerryfixxx16 күн бұрын
I have a machine that was using the alternator with a D350 AVR and I changed the alternator on the same machine with a 230 KVA with R150 AVR and The machine board only recognized the old alternator
@benzblogsVlogs16 күн бұрын
What you mean you replace the avr?R150
@MdSabuj-fw4ie16 күн бұрын
Very nice
@benzblogsVlogs16 күн бұрын
Shukran
@zhantannaador17 күн бұрын
good morning sir, i have genset , 220v - single phase with smartgen hgm6120n , can i connect directly MAINS VOLTAGE(ESAMELCO) to port 31 - 34,?... salamat po
@benzblogsVlogs16 күн бұрын
Yes only the sensing to the module to know if any blockout so generator automaticly start but it should be automativ breaker
@zhantannaador17 күн бұрын
good morning sir;; i have a genset 220v single phase with smartgen hgm6120n, can i connect directly from the mains voltage (ESAMELCO) to port 31 - 34, ??
@benzblogsVlogs16 күн бұрын
V2
@basharmohamad17 күн бұрын
How can I restore the factory settings because an emergency stop appears before the operation process, despite the emergency stop diving lever being checked and it is in working order and working well?
@benzblogsVlogs17 күн бұрын
Make sure any lose connection and make sure supply is properly distributed
@benzblogsVlogs17 күн бұрын
If you want to restor factory set thin ypdate the firmware before updating save first the file
@abdiazizmuse56718 күн бұрын
Alternator is leroysomer and voltage is fluctuating. I did change both filters and oil still problem exist.
@abdiazizmuse56718 күн бұрын
Avr is r150 our genset is jet from jubaili
@benzblogsVlogs18 күн бұрын
Ok if fluctuating check the engine condation if stable at 50-60 hz thin after that go to avr and adjuat the stability okay it will be fine
@abdiazizmuse56717 күн бұрын
Engine rpm is fluctuating then avr is fluctuate. When rpm became stable voltage also became stable. This is not always this is just one's every hour.
@benzblogsVlogs17 күн бұрын
@@abdiazizmuse567 if engine is hunting means it affect the voltage even if avr is good that y i ask if engine stable
@benzblogsVlogs17 күн бұрын
@@abdiazizmuse567 in order to fix the problems first fix the engine hinting check any leakage fuel from intake thin make sure fuel is clean ,fulter is chnage and should be well maintain
@abdiazizmuse56718 күн бұрын
Thanks benz, i have 45kva perking 1103 family with dse 8610 and l series actuator. Every this is oky starting, loading and speed is stable. But after same time engine is hunting if i bleed one injectors it will become normal, same times when hunting same minute it will became stable by it is own. I removed govener wires from deepsea still problem existing. Any suggestions or steps that i will take to sort this problem out. Thanks sir.
@benzblogsVlogs18 күн бұрын
Did you do the maintenance for this generator right did you clean the fuel tank and clean the fuel filter check the fule intake if any lose air and fuel mix can cause hunting and what alternator your using and avr
@jubsofficialvlog147319 күн бұрын
Ayos lodi salamat sa pag bahagi ng videong ito..god day lodi
@benzblogsVlogs19 күн бұрын
Bless you too lods
@user-pu4lb1sr2h19 күн бұрын
Thanks for the video) Very interesting) Like! ) I want to ask. What is the point of this air valve? After all, it is an additional resistance to air flow! We use these valves as emergency valves! They close the air and turn off the engine. Just if there is shooting in the engine! This already indicates a malfunction in the engine! And it must be used! This valve will create, during the shot, high pressure in the intake manifold! And the collector can simply break!
@benzblogsVlogs19 күн бұрын
Yes its important this application to oil and gas refinery to avoid runaway and spark that comes out to the muffler that can cause explosion to the site where combustion gas are percent in the area,this is highly recommended
@user-pu4lb1sr2h18 күн бұрын
@@benzblogsVlogs Thank you) Everything is clear!) Safety is always above all !
@chigozie.o199119 күн бұрын
How to do it
@benzblogsVlogs19 күн бұрын
Update firmware that it
@jubsofficialvlog147319 күн бұрын
Lodi talaga
@nelsonpalomo268821 күн бұрын
Hola gracias por compartir yus conocimientos. Yo tengo un generador donde el pin numero 6 tiene coneccion directa con en pin numero uno de alimentacion de baterua ... ¿ Que funcion cumpliria esta alimentacion en el pin numero 6 ?
@benzblogsVlogs21 күн бұрын
Numero 6 que functiom 50/60 swichable
@A.kHUNNOH21 күн бұрын
Hi sir ask lang po,naka 360d po ba lahat ng engine pag install ng mpu?
@benzblogsVlogs21 күн бұрын
Yes ok lang po
@JohnPaulDorado22 күн бұрын
Salamat Sir Benz sa explanation. Sir about sa maintainance alarm 1 Dili ma reset sa board monitor bisan g reset na Nako 40kva Cummins china
@benzblogsVlogs21 күн бұрын
Need laptop para ma reset sir
@egwuatuuwalaka664122 күн бұрын
Good job sir, i have a problem with dse 6020 CAN version 2.1 on my generator Perkins 2500. If i put it to Auto in other to start from Totalizing panel dse8610. The 8610 will start counting cranking, but generator won't crank out side. What shall i do? Thanks master.
@benzblogsVlogs22 күн бұрын
Meaning 8610 give crank timer to the generator but it wont give crank is this you mean?
@benzblogsVlogs22 күн бұрын
If this what you mean so this posible that starter relay is not working or fuse supply is busted or starter itself is faulty
@benzblogsVlogs22 күн бұрын
Use multi meter to check the boltage and the relay suply and ouput
@egwuatuuwalaka664122 күн бұрын
If start directly from the module 6020 both Auto and manual it will crank and start running, but from dse 8610 totalizing panel will be showing cranking attempt but is cranking the Engine out there. Thanks
@egwuatuuwalaka664122 күн бұрын
@@benzblogsVlogs you mean the Relay or fuse from the Totalizing panel 8610? Thanks master for your assistance.
@danielcalaod606822 күн бұрын
Sir, ganyan controller nmin nag aalarm ng no gens frequency?
@benzblogsVlogs22 күн бұрын
Ok first make sure that during engine run there volatge correctly thin if there is mpu installed check and check ngine speed if correct
@benzblogsVlogs22 күн бұрын
Just sinoly start check the voltage amd the speed if normal if no voltage thin rectify first
@danielcalaod606822 күн бұрын
@@benzblogsVlogs diko po ma start yung genset hanggang crangking lng po sya, after non lumalabas na yung fault nya na no gens frequency Regarding po sa mpu 900 something yung reading
@nagib36022 күн бұрын
Why do my Cummins generators, each equipped with a Deep Sea controller, experience abnormal behavior when integrated into the system? Whenever we introduce one particular generator, it induces overcurrent in the previously operating generators, and itself produces excessive current (around 900 amps per phase) even with a light load. Upon removing this generator from the system, the remaining generators return to normal operation. Whether it's just this generator alone on load or multiple units, the problem arises consistently whenever we close the breakers specific generator and introduce load. What could be causing this issue, and how can we address it to ensure smooth operation of the system?
@benzblogsVlogs22 күн бұрын
What only i can say is check the configuration check ct configuaration kw,current and volatge in the system to make sure perfecly work
@nagib36022 күн бұрын
@benzblogsVlogs thank you sir Before I close the breaker The generator is fine normal voltage 400v, frequency 50hz rpm.also ok The problem its just the when I close breaker
@benzblogsVlogs22 күн бұрын
@@nagib360 most common is aux contact inside ither not working or no suppy
@nagib36022 күн бұрын
@@benzblogsVlogs thanks for your answer
@mubbee53623 күн бұрын
HI FRIEND HOW ARE YOU CAN YOU PLEASE EXPLAIN ME I HAVE A MODULE MKII 8610 IT HASE HA BOOTLOADER ERROR CAN YOU PLESE TELL ME HOW CAN I SOLVE THIS PROBLEM THANKS
@benzblogsVlogs23 күн бұрын
Meaning during the configuration ither unfortunately off the supply or remove the usb that why its happen
@benzblogsVlogs23 күн бұрын
But still have a solution on this just update firmware that it
@ahmadsyarif986223 күн бұрын
how to fix deep-sea 7320 module memory corruption, please teach me
@benzblogsVlogs23 күн бұрын
Just simpky update firmware that it
@ahmadsyarif986222 күн бұрын
@@benzblogsVlogs I have tried updating the firmware from version v4.1 to v5.0 but the display failed to appear (communications link to unit lost. Firmware update has failed. Module is inoperable. please try again) even though my USB cable is connected
@benzblogsVlogs22 күн бұрын
@@ahmadsyarif9862 failure because you got the wrong firmware
@ahmadsyarif986222 күн бұрын
@@benzblogsVlogs where can I find the correct firmware Sir? Please help me
@marwa971023 күн бұрын
I have a question please i have 2500A Abb motoraze the problem is it was work auto but now it doesn’t i need to charge it to work? do you have any solutions please
@benzblogsVlogs23 күн бұрын
Not posible without charge even manual you need to charge
@jubsofficialvlog147323 күн бұрын
Good explanation lods galing talaga lodi nsmin
@benzblogsVlogs23 күн бұрын
Salamt lodi pangtsamba lang
@richardsantillan-qe5ld23 күн бұрын
,sir?kahit b baliktad ung xa winding side?wlang problema
@benzblogsVlogs23 күн бұрын
Pwedi naman sir baliktarin mo din yung ikot para ok sir meaning di pwedi heheh peace lang sir
@benzblogsVlogs23 күн бұрын
Kc maaring instead mg labas ng voltage yung alternator wala sir mababa kc baliktad ang comnection
@richardsantillan-qe5ld23 күн бұрын
,salamuch sir!!
@benzblogsVlogs23 күн бұрын
@@richardsantillan-qe5ld welvome sir
@ravindraperera209023 күн бұрын
Excellent explanation
@josjirah305324 күн бұрын
How will I get the software
@benzblogsVlogs23 күн бұрын
Sir no need for the sofeware if you have the dse sofeware connect your laptop and yodatwbyour firmware and follow instaruction while doing the update
@nelsonnwachukwu925724 күн бұрын
How to do it
@benzblogsVlogs24 күн бұрын
Simply update firmware
@hermantoofa186824 күн бұрын
Hi bro What about overvoltage?what is the different causes ?
@benzblogsVlogs24 күн бұрын
Over voltage only happen if you have shockload or defective avr both under over
@benzblogsVlogs24 күн бұрын
You can check in my vedio all have
@hermantoofa186824 күн бұрын
@@benzblogsVlogs i have overvoltage when no load , i check my avr, weeding of alternator and stator exctitatrice is good
@benzblogsVlogs24 күн бұрын
Thin first thing you have to adjust the avr to the voltage u need make sure your configuration is correct to which you need to follow that while your adjuat your nominal voltage after that put delay for over and under voltage
@user-cm3yt5hs2e25 күн бұрын
Good afternoon sir I want to know how to use laptop for troubleshooting for generator
@benzblogsVlogs25 күн бұрын
Sir simple just connect open your sofeware and go to scada there you can see all the digital input and ouput if active or not active what are the alarms
@RaleighWhelan25 күн бұрын
Hello, I got a ASKA model 110C, it keeps locking up and giving an alarm called Input D, any ideas on how to fix it?
@benzblogsVlogs24 күн бұрын
Meaning you you have to check the digital in D after that if you know how to config read the module and go to the digital in there you can find that di is active but mistake to put the name of a sw wich active fault
@RaleighWhelan24 күн бұрын
@@benzblogsVlogsI found it was high water temp alarm, I found there was water in the radiator so I flushed it and got new coolant into the system