Salamat Sir Benz sa explanation. Sir about sa maintainance alarm 1 Dili ma reset sa board monitor bisan g reset na Nako 40kva Cummins china
@benzblogsVlogsАй бұрын
Need laptop para ma reset sir
@nagib360Ай бұрын
Why do my Cummins generators, each equipped with a Deep Sea controller, experience abnormal behavior when integrated into the system? Whenever we introduce one particular generator, it induces overcurrent in the previously operating generators, and itself produces excessive current (around 900 amps per phase) even with a light load. Upon removing this generator from the system, the remaining generators return to normal operation. Whether it's just this generator alone on load or multiple units, the problem arises consistently whenever we close the breakers specific generator and introduce load. What could be causing this issue, and how can we address it to ensure smooth operation of the system?
@benzblogsVlogsАй бұрын
What only i can say is check the configuration check ct configuaration kw,current and volatge in the system to make sure perfecly work
@nagib360Ай бұрын
@benzblogsVlogs thank you sir Before I close the breaker The generator is fine normal voltage 400v, frequency 50hz rpm.also ok The problem its just the when I close breaker
@benzblogsVlogsАй бұрын
@@nagib360 most common is aux contact inside ither not working or no suppy
@nagib360Ай бұрын
@@benzblogsVlogs thanks for your answer
@richardsantillan-qe5ldАй бұрын
,sir?kahit b baliktad ung xa winding side?wlang problema
@benzblogsVlogsАй бұрын
Pwedi naman sir baliktarin mo din yung ikot para ok sir meaning di pwedi heheh peace lang sir
@benzblogsVlogsАй бұрын
Kc maaring instead mg labas ng voltage yung alternator wala sir mababa kc baliktad ang comnection