Testing of Allen Bradley 1794-IE12 and 1794-OE12 - 12 point Analog input and output modules on Flex I/O. Testing both voltage and current individually to ensure that all channels work properly
Пікірлер: 27
@jimmywatson42302 жыл бұрын
I have an IE12/A with three devices wired to it. A temperature transmitter (4-20mA) return is landed on A0, Pressure transmitter (4-20mA) return landed on A2, and a dew point analyzer landed on A6 and 23(?). The first two devices are powered from separate fuses. I don't know why the module is wired this way, or if they ever worked. The DPA appears to be reading correctly in the PLC, but I don't read any voltage on the leads. When I introduce moisture into the system the current increases and so does my PLC reading. The temperature and pressure devices do not read, but show 5.8mA and 12.27mA respectively. The pressure transmitter is a 0-3000 PSI device and the display reads 2058 PSI. i need to get the two working but I am confused by the wiring? Can you suggest another video?
@abplctestbench7592 жыл бұрын
Best site that I can recommend is www.plcs.net/ - very helpful group there. Have you had a look at your programming to make sure that the configuration is correct? Each channel of the IE12 can be configured for either voltage or current. Looking at the wiring diagram online A0 & A2 are correct for 4-20mA inputs on those channels. Search for Publication 1794-IN106D-EN-E - January 2014 for the install manual. Page 8 for details. A6 and 24 is correct not 23.
@abplctestbench7592 жыл бұрын
Hi Jimmy: Just wondering if you were able to get this working?
@automationstartup740 Жыл бұрын
Hi sir can you please help me, why my 1794- OE12 generating output only for few seconds and then o mA output what may be the reason
@abplctestbench759 Жыл бұрын
Hello - Without being there it is really hard to tell. But - you are running a current loop. It is possible that you have a loose connection somewhere between the module and the field device? Also check your programming to make sure that the output register is not getting overwritten. Check to see if your fault conditions are not resetting the channel to 0. Otherwise it is impossible for me to tell what is going on. Hope you can figure it out.
@automationstartup740 Жыл бұрын
@@abplctestbench759 thanks sir i got the issue with wire open fault on the channels and plc is disabling these channels
@abplctestbench759 Жыл бұрын
@@automationstartup740 That makes sense to me. You need to check and make sure every connection is secure and properly done. Most problems with analog signals is poor wiring techniques. Hope you got it all sorted out.
@MuhammadFaisalTalib2811 ай бұрын
Hi I have a 1794-IE12 that is flashing green and showing FieldPowerOff as a 1. I have it configured properly. What can I do to fix this issue?
@abplctestbench75911 ай бұрын
Hello: That is normally the error when you have a broken wire / open connection between the device and the module.
@guilhermerocha28463 жыл бұрын
Hey, whats the difference between a isolanted module (IF4I) and a selectable (this module)?
@abplctestbench7593 жыл бұрын
The isolated module IF4I is 4 separate channels that are not connected to each other. No common terminals. The IE12 & OE12 and many others have a single row of common terminals that are tied together in the base and the module. Both have advantages but depends on the equipment they are being used on.
@vijayeee65302 жыл бұрын
In 1794 ie12 module LEI -4 transformer getting damage, let me know the rating and technical details of transformer
@abplctestbench7592 жыл бұрын
Hello: Sorry I do not have access to the technical details you are asking for. It is a 0►20 mA input - so 20mA would be the highest current on the current input terminals. Voltage is -10 ► +10 VDC on the voltage input terminals.
@milfslayer32022 жыл бұрын
Normally most analog input and output devices are 3 wire correct? need a +24v and a COM to complete the sensor circuit and then the other wire to connect to the I/O?
@abplctestbench7592 жыл бұрын
Hi Jeff: Not always. There are 2 - 3 & 4 wire configurations depending on the device and on the module that it is tied into. Voltage and current devices vary depending on the application. Thanks Bruce B
@CaminoYVerdad14 жыл бұрын
Hello are you familiar with the 1746-BTM? If so I have a question if you dont mind helping me out.
@abplctestbench7594 жыл бұрын
Hello Camino: I have never worked with the BTM module. I have only seen it online and in manuals. Not sure I can assist you with this one as I do not have any experience with this specialty module.But ask away I may be able to help if I see your question, or maybe someone else that is subscribed to my channel.
@CaminoYVerdad14 жыл бұрын
@@abplctestbench759 thank you for trying. Here goes. So I successfully did an autotune on all 4 loops. The application is for a barrel heating application. The only problem I have is my cooling fans come on way to late If I pass my SP by like 15 degrees F they still dont come on. The cooling TPO is working because if I lower my SP by 100 degrees it kicks in but thats way to late. My high CV is set at 100% and my low CV is set at -100%.
@abplctestbench7594 жыл бұрын
@@CaminoYVerdad1 Hi: Not sure how much I can help. It sounds to me like you should be latching the output for the cooling once the temp is greater than the setpoint. I would monitor the setpoint and once it is lower than the setpoint by an amount that you are happy with and for an amount of time then unlatch. Since I have never used these cards I am unsure what the CV is used for. If they are metal barrels in my experience they cool slowly and heat up quickly depending on multiple factors. Hope that this helps. Bruce
@CaminoYVerdad14 жыл бұрын
@@abplctestbench759 thanks for trying have a good one
@abplctestbench7594 жыл бұрын
@@CaminoYVerdad1 Your welcome - Sorry I could not help more, but no experience with that module.
@OnlineIncome5228 ай бұрын
Sir, may i ask if the terminal A0 and 17 will normally have a 24v voltage?
@abplctestbench7598 ай бұрын
Hi - Input or output module?? The wiring diagram shows all of the connections.
@OnlineIncome5228 ай бұрын
@@abplctestbench759analog input module sir, connected to 4 wire flowmeter
@abplctestbench7598 ай бұрын
The wiring diagrams and documentation is on the Rockwell website. I suggest you go there and download the document for the module . www.rockwellautomation.com/search/ra-en-US;keyword=1794-IE12;startIndex=0;activeTab=Literature;spellingCorrect=true;facets=doc_type_full_s%253A%2528%2522Installation%2520Instructions%2522%2529;languages=en;locales=en_GLOBAL,en-US;sort=bma;isPLS=false;sessionID=7d520837-6fe7-6066-20ff-de0ddee07dab;deepLinking=false
@singh6645 Жыл бұрын
Hi I have a 1794-IE12 that is flashing green and showing FieldPowerOff as a 1. I have it configured properly. What can I do to fix this issue? I have a gas meter hooked up to it but I am seeing a comm error.
@abplctestbench759 Жыл бұрын
Hello Jasspreet: Without seeing your field wiring diagram and how you have it all connected it is not really possible for me to troubleshoot from here in Canada.