Just had a central control is installed with unshielded comm wire, unit would connect and control system but would go into 6607 after about 10 minutes, luckily all M-net had shielded cable, so I was able to get temporary operation without central control.
@NotOurRemedy5 жыл бұрын
Thanks man I watch all your vids. Anyway you can do a video detailing all the procedures for doing a maintenance. What to benchmark. What to look for? Do you command the whole system to stop to zero out your sensors? Do you ever put drain spray on your units? XYZ it would help a lot.
@vrfviewpoint61995 жыл бұрын
I can put it on the list.
@NotOurRemedy5 жыл бұрын
VRF Viewpoint pulease bossman.
@jonathansabaco81753 жыл бұрын
How do I troubleshoot error 6600? I just installed an additional FCU and had this error showing after every 5mins. After doing alot of test and check, I just couldn't solve it. I also tried to connect the transmission to the other outdoor unit and then the error changed to 6607. Thank you.
@GamertagAKACUZ5 жыл бұрын
Lol!! Wrong compressor. Nice. I had LG send me a 460v compressor for a 208 system. Numbers on box where good but the numbers on the compressor where not. Lucky I caught it before installing. Wondered how it would work...
@Modello404 жыл бұрын
Had 6607 this morning, as well as a 7100. Currently have a master/slave pury-500 giving me a 1500 (overcharge) issue. Unit has been running over a year, and the problem has literally come up in the last 3 weeks. Happens sporadically. Running 14 indoors (cassettes) all lev/shell temp/discharge temp:pressures check out. Accumulator ices up pretty badly, leading me to think it’s letting liquid back from bc box. Any other help would be appreciated 👍🏻