1)1.5 ton inverter AC 2fan 2 LED light 220 liter refrigerator எத்தனை கிலோ வாட் சோலார் போடலாம் அண்ணா
@7hdsolars115 ай бұрын
5kva inverter with 3kw panel
@harikrishna89325 ай бұрын
Budget
@ramuv48055 ай бұрын
@@7hdsolars11இதுக்கு எவ்வளவு செலவாகும் சார்
@7hdsolars115 ай бұрын
@@harikrishna8932 rs.3.45lak
@mohanrajraj12744 ай бұрын
@ramasamy_murugan5 ай бұрын
32amps DC mcb is never down because panel max output is 13amps pls correct that mcb ratings.
@7hdsolars115 ай бұрын
U r wrong mr. Ramasamy, this is 2 in 1 out MCB box. It means 2nos of 16A fuse and 1no of 32A MCB. I used 8nos of 550w panel . Per panel max voltage is 49v and short circuit current is 13.8A . I separated 8 panel into 2 string Per string voc is195v and 13.8A short circuit current. Now I given 2 string into 2 fuse rated as 16A Those 16A fuses output are in parallel connection. Therefore parallel connection of 2 fuses, max we can get 27.6A . This 27.6A current goes to the 2 pole DC 32A MCB . For 27A current we should not use 25A MCB, because MCB Ampere rating should be 25% greater than actual current. So we should use 32A only. Note: MCB have tolerance of + or - 25%
@HappyKing-si9rm5 ай бұрын
How much it will cost to run 02 nos of 2 ton AC for home