Hello there thanks for the good video but i cant find here that how to do setting of auto reatart of this vfd after power failure .. Can you explain that setting plz .
@tuyenhmi10 жыл бұрын
Thank you about video training. it is help me very more in my work. Thank again!
@GalcoIndustrial10 жыл бұрын
Glad that we were able to be of help! Thank you for the feedback.
@filipecostamartins26983 жыл бұрын
How to backup the parameters?
@shankark13315 жыл бұрын
I need following option.What are all the parameter need to set this application 1.Forward High speed(DI1)-40HZ 2.Forward low speed(DI2)-10HZ 3.Reverse High speed(DI3)-40HZ 4.Reverse low speed(DI4).-10HZ
@yuezpurdue5 жыл бұрын
Analog current Input signal (4-20mA) of ACS355 Drive is from OMEGA CN735 Temperature Controller and is connected to Pin5 (AI2) and Pin6(GND or COM) in order to control a FAN. I tried all Macros applications and none of them is working. I mean none of them can really received this signal from OMEGA controller even though I disconnected this signal from OMEGA CN735 and FAN is still running remotely. My question is that how can I control the fan by really running this Analog Current Signal rather than using Macros. What is the correct hardware wiring connection? Thanks.
@dhananjaymahajan718911 жыл бұрын
For my Machine I need variable speed With Remote opration. On remote ON,OFF.Speed UP & Speed Down Push Button. I need Wiring Diagram & Required Parameters
@badrabdelfattahhassan65424 жыл бұрын
Please 🙏 you can help me... A want how make factory settings for ACS 150 ABB DRIVE
@Kimbosdk1qc4 жыл бұрын
After of did it reset appeared " panel text flash error ". What have I do to see the parameters on display again?
@GalcoIndustrial11 жыл бұрын
If you contact a sales associate with the number listed in the description page 800-337-1720, our drives technical support can help assist you in getting your machine up and running.
@sourenamehr60876 жыл бұрын
Hi I have installed an ACS355 with advanced control pad. It is aimed the drive runs a 5.5KW pump through the solar panels. Currently for testing purposes, I have connected a 504V, 10KW DC power supply as the input. The drive in Local mode works as it should be but in Remote mode, the operation frequency never exceeded then 40Hz (The pump should work with 50Hz). The relevant set points are all set on 50Hz. I have searched a lot and have contacted to ABB as well but no one could help me. Just wondering if I can get my answer here..
@GalcoIndustrial6 жыл бұрын
Please send me the following information: The complete part number of the drive. Which macro are you using, this can be found with parameter 9902. The list of changed parameters which can be found using the “CHANGED PAR” function in the keypad. What is connected to the I/O terminal strip of the drive for remote operation.
@sourenamehr60876 жыл бұрын
Hi.. Thanks a lot for your consideration, Here there are the information you've asked about: Part Number: ACS355-03E-31A0-4+N827 Parameter 9902: ABB STANDARD Changed Parameters: REF1 MIN: 10HZ, FAULT RESET CELL: COMM, PQ CURVE P2: 3KW, PQ CURVE P1: 2KW, FAULT RESET TIME: 60S, DRY RUN TRP TIME: 60S, MIN LOAD CURRENT: 1A, BOOST FACTOR: 1.25, BOOST VOLT: 500V, PUMP MINIMUM SPEED: 500rpm, PV CELL MIN VOLT: 415V, MINIMUM SPEED: 500rpm, MA CURRENT: 9.5A, UNDER VOLT CTRL: DISABLE, ACCELER TIME: 10S, RAMP INPUT 0: DI2, IR COMP VOLT: 0V, U/F RATIO: SQUARED, STALL FUNCTION: ALARM, STALL FREQUENCY: 15Hz, EFB STATION ID: 2, START DC VOLT: 350V, MOTOR NOM POWER: 5.5KW, MOTOR NOM SPEED: 3000rpm, MOTOR NOM VOLT: 440V, COMM PROT SEL: STD MODBUS, MOTOR NOM CURR: 12A, PUMP EFFICIENCY: 85%, Moreover, the activation signal is provided from 24V terminal on driver to DI1 through an on/off switch. I hope these information can help to solve the issue. Kind regards
@rami16129 жыл бұрын
Thank you for the video. I installed a 5.5KW ACS355 solar drive. I received the drive with basic control panel. I put all parameters and limits. I used Scalar frequency control. My problem is that the drive is not regulating the frequency output based on the sun irradiation, but it just follows the value which I set on "Ref" on the basic control panel. I am using the drive in local control mod and without external I/O signals. Please any help to make the drive work automatically? or How can I remove this "ref" control in order for the drive to seek the operating frequency by itself?
@GalcoIndustrial9 жыл бұрын
Rami H Try setting parameter 1103, REF1 SELECT to SOLAR. The manual defines SOLAR as“The inverter takes the speed reference calculation from MPPT.” MPPT is maximum power point tracking, which is an algorithm that controls the inverter to obtain maximum power from the PV cells at any instant.
@rami16129 жыл бұрын
GalcoTV Thank you for reply. It is already selected to solar and all settings selected according to solar. if you have email i can send u the details. my email: ramihijaz@hotmail.com
@manojrawat10354 жыл бұрын
Please help me abb3 phase motor drive display fault code f0021 show
@zikomoon245010 жыл бұрын
Hi Galco, Thank for this valuable video. Please, can explain how to control the ABB ACS355 through a computer by using Drive windows Light 2.
@GalcoIndustrial10 жыл бұрын
Hi Ziko Moon. I saw that you have also posted this under the ABB ACS550 video as well. Since the program operates similarly on both drives, I can answer that within this comment's section. I will need a little more information than what you have provided. What exactly are you trying to do and what kind of difficulties are you coming across? Do you have the appropriate software and connections?
@zikomoon245010 жыл бұрын
Hi Calco, thank you for your quick response. Yes, I have the appropriate software and connections which I bought from the ABB Company. how to apply speed changes in each of step function and Ramp function and how to apply delay time. Thank you for your assistance and compliance regards zyad
@GalcoIndustrial10 жыл бұрын
ziko moon The step function is set on the pull down menu on top with drive--->step function-->step function settings. As for ramp function, the accel/decel rate are in parameter 22. You can change any values by double clicking the number and typing it in. Delay time is also a little ambiguous since there are a lot of different parameters that use the term 'delay time'. For example, parameter 2113 is for a start delay, parameter group 14 allows for delay time on relay outputs and 3103 is for setting the delay time after a fault. I hope this puts you in the right direction.
@zikomoon245010 жыл бұрын
Hi, thank you very much for your response. this information has helped. thanks a lot
@sivasuryareddy60173 жыл бұрын
I have abb acs 355 drive.the falut code is f1006
@kefrenferrer67777 жыл бұрын
hi I want start stop from remote control but i wish set the reference in panel , what can i do?
@GalcoIndustrial7 жыл бұрын
Go to parameter, set 1103 = 0 and will select keypad/control panel for speed command. For the start/stop in remote, set with your Macro selection. If ABB Standard is selected (default macro) then all you have to change is 1103 for your speed command. Let us know if you have any additional questions.
@kefrenferrer67777 жыл бұрын
Thanks, it works I am using frec control but i want to use speed control and i can not disengage the motor from the machine to make ID test, what can i do?. Finally sometimes the converter shows shorts circuit fail and reset until some time and pushing éxit button, could it be interference ? the drive is new. I apreciate your help.
@GalcoIndustrial7 жыл бұрын
Well if you can't uncouple the motor from the machine don't run "ID run". If you need to run the motor at low speeds you will need ID run, but if you don't need operation below say 50% speed, just put it in "Vector Speed and see how it performs. Otherwise, guess what,,,, you have to uncouple the motor! This allows the drive to get a good picture of motor the characteristics to control it properly in Vector mode. If uncoupling is absolutely not possible, you may be better off leaving in Scalar FREQ mode. But try speed first, some applications are more forgiving than others, ok?
@kefrenferrer67777 жыл бұрын
Ok, thanks, and what about short circuit fail 4
@GalcoIndustrial7 жыл бұрын
As far as the short circuit fault goes, first double check all your power connections to the drive and the motor make sure they are tight. Could also be the mode you are running in without proper tuning too.
@maaran94966 жыл бұрын
F0035 displayed in vfd i want to reset that fault how