Hello Mr. Apc fix I wanted to ask you this question since can I know the function of the variable found on the battery compartment of the sua 750i because I changed my the batteries to lithium ion so it’s normal lead acid battery is 27.3 volt and lithium ion 28.9 volt. Can it be the charging voltage variable? If no please tell what’s that.
@ApcFix11 ай бұрын
Use Teraterm software for this purpose.
@mez472Ай бұрын
I see you answer to comments, so there's something I want to ask: some time ago, I replaced the batteries in my apc ups 1500 with 2 victron superback batteries, 12V 20Ah, and did a recalibration via discharging the batteries. Everything went good, but when the low voltage kicked in, both load and battery leds were blinking together. All 10. I know the batteries were low because I restarted the ups and the vacuum cleaner I used as load powered on just for a split second and that was it. This time however, leds didn't started to blink. Ups was stuck on battery led plus one led to battery. Now to the question: what these 10 leds ( load plus battery available capacity ) blinking together is supposed to mean? Calibration failure or something like that?
@ApcFixАй бұрын
Please share short video of this fault on my email address, email mentioned in about section.
@mez472Ай бұрын
@ApcFix ok, I will, but I don't know when. Currently, my life is extremely busy
@goan8010 ай бұрын
Hi @Apc Fix, found your video looking for solution for my SMT750i. I have opposite problem actually, it faults with "Output over volt" error while a main line goes down (power is disconnected). I cannot find any service manual describing the problem. Can you maybe have some advice? Thanks in advance.
@ApcFix9 ай бұрын
First of all, sorry for the late reply. I only make videos on the SUA series. I have no solution for this problem.
@danielpfmarinho10 ай бұрын
Hello, Mr APC. My smartups has the same issue. I watched the video and saw that ralay has 6 pins, but the link you have supplied is for an eight pin relay, which one is the correct? Sorry for any english mistake.
@ApcFix10 ай бұрын
Some models use a 6-pin relay, and some models use an 8-pin relay. Both are correct, if your model use 6-pin relay then remove two pins from 8-pin relay. For your kind help see these 2 photos in the given below link: drive.google.com/file/d/1kNR25gG1SG6I63OtqdbzBKzu3zUlGMJb/view?usp=drive_link
@danielpfmarinho10 ай бұрын
@@ApcFixthx for previous reply. One more question: you showed 2 types of relay, one with a single line and the other with a double line. Can I use either one? Or is there one of them that is correct?
@ApcFix10 ай бұрын
@@danielpfmarinho Only use double points rely for light blink issue. Double point relay has different from single point relay in term of connection type. I showed single point relay for information only.
@bartoszgrzegorczyk12134 ай бұрын
Hello, i have APC SmartUPS 1500 model DLA1500I and have same problem. When I take out motherboard I see 3 relays - one 6 pins - 450 2151A and two 8 pin relays - az 755 1c 24de. Should I change all 3 relays ? Please give your e-mail i will send you picture of motherboard. I cant find it in about section. Will be gratefull for your help.
@ApcFix4 ай бұрын
nadeemsarwar733@gmail.com
@simushisimushi9260Ай бұрын
Hello, did you sort your problem?
@bartoszgrzegorczyk1213Ай бұрын
Yes, i changed all relays and UPS start work properly. One of them was broken.
@arbabali547210 ай бұрын
Relay 24vdc 16a 8pin hai ye lahore miljayege ?
@ApcFix9 ай бұрын
Yes, Available in hall road.
@arbabali547210 ай бұрын
Ya es ki jaga koi 24vdc 8a 8 pin laga sakty hai ?
@ApcFix9 ай бұрын
No.
@MrTufflife Жыл бұрын
Hello sir. Can you tell me which relay for SU 1000i
@ApcFix Жыл бұрын
The relay number for SU1000i is RP920124 6Pin Relay 24v Coil 250VAC 8A. Thanks for comment.
hi i use apc 1100 va does it output with two site not output with one site
@ApcFix Жыл бұрын
?
@Moroo1976 Жыл бұрын
useful video
@ApcFix Жыл бұрын
Thanks
@alexm173611 ай бұрын
What does it mean when all LEDs are flashing on the right side from the on/off button?
@ApcFix11 ай бұрын
This issue happen due to AC output capacitor fault.
@alexm173611 ай бұрын
@@ApcFix you are right. I change the capcitor and now it works. Thank you
@Real_serdique Жыл бұрын
Hello APC fix actually can you help me by trying this task, Just try in pluging your apc calibrated ups of it then cold start it without it being plug to mains. Then tell me the output frequency whether it is 50 or 60hz.
@ApcFix Жыл бұрын
Email me a picture of the front of the UPS. Email given in about section.
@Real_serdique Жыл бұрын
@@ApcFix I din't see the email I'm a little bit far from it but it's SUA series 700va smart sine wave.
@Real_serdique Жыл бұрын
What I meant is that I just want to change it output permanently frequency to 50Hz so I can on it in 50Hz eve if there is not mains available. Please read it carefully.
@HassanRaza-wv9xm3 ай бұрын
Sir mery APC 1500VA me same issue hy jab k ups battery mode me bilkul sai chalta but jesy wapda in kry to sari lights blink krny lag jatti but restart krny se thori deer k leye sai ho jata but phr kisi b time sari lights blink krti or output bnd ho jati kia ye relay ka e issue???
@ApcFix3 ай бұрын
Yes, yee relay ka fault hai just relay ko replace krdy issue Hal ho gayee ga.
@HassanRaza-wv9xm2 ай бұрын
Relays change kewa di but issue resolve ni huwa pehly wapda dene foran all lights blink krti thi ab 1 hour chal k krti hy ap ki opinion me kia issue hy???
@gracelibertino86905 ай бұрын
Bhai pure sine wave?
@ApcFix5 ай бұрын
Yes bro, All Apc UPS models are pure sine wave.
@Moroo1976 Жыл бұрын
Hello Sir--Can you tell me relay number for APC(back-ups pro 1000) i will be thanks for you
@ApcFix Жыл бұрын
Can you share the picture of the relay, and UPS on Email? Email is given in about section.
@Moroo1976 Жыл бұрын
@@ApcFix Thank you sir for your e-mail and for your support its same relay for 1500 aps ,,
@ApcFix Жыл бұрын
@@Moroo1976 Yes, it's same as like 1500VA UPS
@vietduongquoc Жыл бұрын
Shop bác ở đâu
@ApcFix Жыл бұрын
ở lahore
@davidkwamemensahtawiah170326 күн бұрын
Thanks
@ApcFix26 күн бұрын
Most welcome
@arbabali547210 ай бұрын
Aoa bhai mere pass apc ups 1000 hai all lights blink karta hai jab power connect karta hun
@ApcFix9 ай бұрын
Just replace the relay (24V 8A double point) the problem will be solved.
@arbabali54729 ай бұрын
@@ApcFix thanks for rply but existing relays are 24v 16a single point . Can we use double point??
@ApcFix9 ай бұрын
@@arbabali5472 If existing relay is single point then use single point relay.Thanks