@jayalvin43 жыл бұрын
instaBlaster...
@pravinbidgar25266 жыл бұрын
Thanks sir, panel design ke video other channel pe nahi dekhe maine abhi tak thank you sir
@ElectricalInfinity6 жыл бұрын
You are welcome.
@harishbelchandan74286 жыл бұрын
thanq sir super video ...control circuit ka diagram dikhaiye sir .. this is best video sir
@palakodetichandrasekhar41723 жыл бұрын
Very very informative. Very well explained. Thanks.
@ElectricalInfinity3 жыл бұрын
Thanks palakodeti 😊
@jayaramparida67214 жыл бұрын
Very very educative. If possible please upload one practical vedio basing on the energy bill one of one industry where power factor is in between 0.5 to o.8 & how that is improved to 0.99 after installation of apfc panel & avoided paying for low p.f penalty. Rather got incentive for good p.f. Regards Jayaram Parida
@ElectricalInfinity4 жыл бұрын
Thanks for the idea. Will do one soon.
@abhijeetkuwar053 жыл бұрын
@Electrical Infinity Why did you used 2 x 1000A ACB in the electrical diagram? I am not getting that part.
@ananddeshpande80704 жыл бұрын
Hello Sir, very informative video, thanks. One question, while dividing fixed capacitors in two sections, one for CB (50 KVAR + 50KVAR) & other for (25 KVAR), can we not take one CB for one 125 KVAR capacitor connection, as 250AMP MCCB?
@PEACEINNATUR4 жыл бұрын
Vvery good explanation bro
@mahtabalam8525 жыл бұрын
Very good explained bro. Thanks
@akashmanusmare71986 жыл бұрын
very nice,,, best pracical video ever,,,
@ElectricalInfinity6 жыл бұрын
Thank you 😊
@akashmanusmare71985 жыл бұрын
Why we consider 40% only
@haldeeppatle96373 жыл бұрын
Very helpful video sir
@ElectricalInfinity3 жыл бұрын
Thanks haldeep.
@RajeshYadav-be7ds5 жыл бұрын
Great and superb explanation boss
@ElectricalInfinity5 жыл бұрын
Thank u
@dadu82656 жыл бұрын
Awesome video, really good...
@ElectricalInfinity6 жыл бұрын
Thank u ❤
@prakashpaul49926 жыл бұрын
Very Morvalas video understand very easy,thanks.
@jatinchatterjee22196 жыл бұрын
very nice explanation ,but a simple doubt is that for the ACB rating selection for transformer we multiply 1.4with transformer's kva rating,but what is 1.4,is it√3?, & where is the power factor corrector equipment,& how does capacitors operate automatically (on & off) when inductive loads are increase & decrease ,plz plz plz reply brother
@herrytech16445 жыл бұрын
Kw*1.4 ≈max. Current It is thumb rule. And apfc relay compares actual pf and targeted power factor and calculates how much KVAR will be needed and sends signal to cdc contactor and that contactor when gets supply that capacitor gets connected to bus and improves pf
@elmekfoujar80434 жыл бұрын
Load current for 1000Kva=(1000000/(1.732*415))=1391.25A Here 1.732 is square root of 3 there for, 1kVA The Load current will be 1391.25/1000=1.39125 this value is approximated as 1.4
@elmekfoujar80434 жыл бұрын
@@herrytech1644 Load current for 1000Kva=(1000000/(1.732*415))=1391.25A Here 1.732 is square root of 3 there for, 1kVA The Load current will be 1391.25/1000=1.39125 this value is approximated as 1.4
@amitmodi20355 жыл бұрын
in capacitor bank inductor also use between contactor and capacitor bank in many industry so please tell the selection of inductor.
@dkverma674 жыл бұрын
It used to save the capacitor as capacitor will act as short circuit at the time of switching and draw very high current. Inductor will limit this current. Regards dkverma67@rediffmail.com
@marsdenbakubhai87556 жыл бұрын
very expanatory and helpful video. I have 1 que.. Why Transformer rating is multiplied by 1.4 while selecting circuit breaker for transformer?? how did you get 1.4 multiplier?
@ElectricalInfinity6 жыл бұрын
Will explain in nxt video. Nxt video is based on this topic .
@marsdenbakubhai87556 жыл бұрын
2nd que is that.. CDC you used for variable capacitor is capacitor duty contactor or only a simple contactor?? because as per my information both are different.
@ElectricalInfinity6 жыл бұрын
Its capacity duty contactor.
@kirantiwari7046 жыл бұрын
very good & explanatory very well... Thanks
@ElectricalInfinity6 жыл бұрын
Thank u 😊.
@ElectricalInfinity6 жыл бұрын
Hope you have like the video and subscribed to our new channel.😊
@hareshkhandaskar11986 жыл бұрын
Very nice explanation.
@ElectricalInfinity6 жыл бұрын
Thanks
@engmalikaltayeb35195 жыл бұрын
Awesome explanation
@ElectricalInfinity5 жыл бұрын
Thanks
@jaydhokai83642 жыл бұрын
Nicely explained..can you tells how you decide the size of variable capacitor bank to fulfill the demand of. 375kvar....means example you can take all 25kvar bank to fulfill but selected in combination of 50 & 25...
@ROHITPATEL-jh4sk6 жыл бұрын
Thanks lot Best explanation
@kashmirengineeringvision6 жыл бұрын
sir little bit confusion why u have used 2 acb for apfc panel
@herrytech16445 жыл бұрын
Same question
@sriconstruction58594 жыл бұрын
One from inside of main panel. And a other one inside APFC panel
@nageshketkar78696 жыл бұрын
NAGESH KETKAR. thank you sir, your lecture is very explanatory , give also the circuit diagram of apfc panel of 250kvar 300kvar etc and also other video related wit hMCC ,PCC panels.
@suvankardas73703 жыл бұрын
If my transformer rating is more high or less there our kvar consideration formula will same ( 30% for variable or 10% for fixed load) or any other formula will be applying there?
@nagarajumep2 жыл бұрын
Thank you so much sir, 1)if we go with 1phase capacitor how can we distribute.
@abhinavprabhat88655 жыл бұрын
Sir capacitor bank see pehle choke bhi lgate h ,uske bate me bhi bataiye
@pranitsurte17064 жыл бұрын
Thanks for the video sir, but i have a question sir why fixed capacitor is not connected to APFC relay
@khushiiyadav28055 жыл бұрын
Thanks sir. This video helped me a lot. Thank you very much sir.
@ElectricalInfinity5 жыл бұрын
Welcome
@sheelaverma29913 жыл бұрын
Thank you sir 🙏
@ElectricalInfinity3 жыл бұрын
Most welcome
@nipendrasaini47685 жыл бұрын
Sir please make a video on. DG start panel wiring ....
@mirzasaqib42204 жыл бұрын
In calculation value of 1.31 why we take 2 as multiplying factor
@krishnasamykesavan48164 жыл бұрын
Very useful
@ElectricalInfinity4 жыл бұрын
Thanks
@dkverma674 жыл бұрын
Please specify following in the video:- 1) the 2000 Amp switch after transformer is remote incomer for main panel just after transformer. 2) The first 1000 Amp switch is the O/G of APFC panel 3) The second 1000 Amp switch is I/C of APFC panel. 4) The fixed capacitors may also be connected by contractors.
@ElectricalInfinity4 жыл бұрын
Thank you for comment buddy. exactly true
@rasengan97433 жыл бұрын
Thank you so much, I had some doubts about those two switches. Explained In a way perfect way. One question : why do we need to connect contactor to fixed capacitors?
@PramodSingh-wr9ou6 жыл бұрын
Great job sir ji...thank you
@ElectricalInfinity6 жыл бұрын
Welcome 😊
@ahmedosman96996 жыл бұрын
Great job thank you so much ,, I have one question in the APFC panel side I think it should be an isolator not another ACP ?? Am I right ?
@pravinbidgar25266 жыл бұрын
Very good sir please make other type of panel design video also.there is unique video
@ElectricalInfinity6 жыл бұрын
Sure new videos coming soon
@rkprasadbhookya18783 жыл бұрын
Nice
@kumarachhami20406 жыл бұрын
Sir Namaste please upload video of apfc control panel wiring
@MrSai276 жыл бұрын
Sir, pls explain ct connected to apfc reay, which phase we have to choose and why?
@Shreyaa20234 жыл бұрын
Thank you sooo much
@ElectricalInfinity4 жыл бұрын
Welcome
@vaithiyanathanmanokaran4496 жыл бұрын
Sir why we take 40 % of capacitor.please explain or it is thumb rules
@prodiptamajumder54256 жыл бұрын
Nice explanation. it is power circuit of pfc . where i get Control Circuit of pfc .
@RajeshKumarYadav-pr1yv5 жыл бұрын
Thanks a lot
@sohilshaikh6483 жыл бұрын
I want to ask load connection or incoming & outgoing of apfc panel.
@mohammedezaj10186 жыл бұрын
Sir 1kvar=1.31A So, why you substitute 2 in the place of 1.31
@herrytech16445 жыл бұрын
Same question
@96007722014 жыл бұрын
Same
@true31205 жыл бұрын
Thank u bro
@akshaysahu4585 жыл бұрын
Awesome
@manjunathh55405 жыл бұрын
Please make a more vedios on this
@ag-bu9zs6 жыл бұрын
Thumps up👍👍
@niketvora94016 жыл бұрын
It's helpful video...we also can find required KVAR through below equation, Capacitor reactive power Qc = P * ( tanφ1 - tanφ2) P is actual power (demand load) is in KW (it can calculate from load summary) φ1 = Initial or actual p.f. (Value can obtain from supply company bill or can consider 0.75) φ2 = Target p.f. ( To be decided by customer or can consider 0.95) Pl. provide some information about heavy duty capacitors bank with 7% series reactor for detuned filters...and why generally we used TP ( 3 Pole) mccb for APFC incomer?
@elmekfoujar80434 жыл бұрын
I THINK IT IS NOT 40% IT IS 0.421 THIS VALUE IS OBTAINED FROM CALCULATING CORRECTION FACTOR FOR IMPROVING PF 0.8 TO PF .95
@riteshpatil75486 жыл бұрын
thank you sir
@rubultalukdar38613 жыл бұрын
Can u provide a video on how to select the step size for APFC panel????
@Mukeshkumar-do7ot6 жыл бұрын
Sir substation me capacitor selection kaise karte hai
@impactodelsurenterprise24405 жыл бұрын
How do I calculate what amp rating my contactors and relays should be?
@pragneshpatel77093 жыл бұрын
Hello Sir, I have learnt much more than other channels, I have 1 doubt here, In this video at 4.30 min u have said 1 kavr = 2 amp than how i cant understood...please help sir
@ranjan14365 жыл бұрын
what is 1.4, used in the sizing of breaker size?
@sadamth67145 жыл бұрын
What is 1.4 when u calculate with transformer circuit breaker?
@elmekfoujar80434 жыл бұрын
Load current for 1000Kva=(1000000/(1.732*415))=1391.25A Here 1.732 is square root of 3 there for, 1kVA The Load current will be 1391.25/1000=1.39125 this value is approximated as 1.4
@sndable5 жыл бұрын
Can you explain reason for taking 2 No 1000 A ACB
@ElectricalInfinity5 жыл бұрын
One for main panel and other for sub panel
@bujairpbn5 жыл бұрын
Can you make a video on selection of a transformer for providing 24 volt supply to a contactor. How much current will drawn by a 24 volt coil contractors
@ranjan14365 жыл бұрын
I don't understand when you have 2000 Amp CB as the Main ACB in the panel then what is the use of 2nd 1000 Amp ACB in the same panel?
@sriconstruction58594 жыл бұрын
I want to know when finding ampere. why you multiplied KVA X1.4 Need to know about 1.4. I am accatable KVAR X 2 as per formula we are getting.
@ElectricalInfinity4 жыл бұрын
check this to know about it kzbin.info/www/bejne/a4Grqn-LfNCfZ5Y . Thanks.
@dkverma674 жыл бұрын
One KVA is 1000 VA So current shall be 1000/1.73*415= 1.39 So 1 kVA =1.4 Amp
@dkverma674 жыл бұрын
You have to consider voltage fluctuations factor 1.3 and fluctuations due to tolrence in in Capacitor 1.5 So 1.3x1.5x1.4= 2.18 Say approx 2 Regards dkverma67@rediffmail.com
@vikramdeshwal78124 жыл бұрын
Sir, please explain concept of 1.5 and 1.3
@kapilgautam33885 жыл бұрын
Sir please upload more videos...
@harishbelchandan74286 жыл бұрын
sir jhon e traister ki book btaye please sir ...handbook of electeical design detail me 2 books h uski
@manojsharma-zk3mc4 жыл бұрын
Can you please clear my doubt why you took Apfc relay aux supply from 2000 amp ACB please
@ElectricalInfinity4 жыл бұрын
A current transformer is used
@videosfunnyvideos2114 жыл бұрын
make a video on designing of starters used for ind. motor plz...... or guide me to get designing information
@ElectricalInfinity4 жыл бұрын
Sure
@Rpm-zb1fv6 жыл бұрын
Why you're fix the ct in between incomer of capacitor panel. It will taken between transformer and incomer of main panel.
@tamilamuthanthangavel55683 жыл бұрын
Sir please explain AMF control panel wiring
@ElectricalInfinity3 жыл бұрын
Sure 😊
@tamilamuthanthangavel55683 жыл бұрын
Thank u sir
@rajatzade17006 жыл бұрын
Sir how to find the size of capacitor if I have a total load of 500A motor load ( HVAC Application) ??
@divac81804 жыл бұрын
sir, Can u please explain about "RMG/VCB/LT PANEL/SLD"
@swaroopmohanty9634 жыл бұрын
Sir why u added sin 90
@irenethomas24836 жыл бұрын
Sir why are you using two nos of 1000 A ACB s..in design calculation we used only one
@tewodrosdemeke51316 жыл бұрын
Hi Sir I want to Work On APFC, And Your Video is So Supportive And I Have Better Knowledge now, But If You Have Documents That Helps Me to Gain Extra Knowledge Please send me. thank you in Advance.
@krishnagaikwad60786 жыл бұрын
sir how this bank's are connected in 3 phase
@ElectricalInfinity6 жыл бұрын
Watchout practical video 😊 of apfc panel wiring
@sreeram92205 жыл бұрын
How 25kvar is multiply by 2 into 15amps.
@surajlugade8864 жыл бұрын
I have one question is that suppose my motor is 200HP and I want fix it capacitor bank so how to calculate the rating of capacitor bank ????
@dkverma674 жыл бұрын
If pf is considered 0.8 then sin phi shall be 0.6 Maximum KVAR for Compensation 200x746x0.6=89.52 Then we have to take 80% of this as the motor p. f will not be always same. It depends on load and RPM too.So we shall take 71 KVAR capacitor bank fr 200 HP motor.
@funwithit98653 жыл бұрын
Whats 0.6
@gaju1484 жыл бұрын
How you get to know the value such that 40% for capacitor rating and for circuit breaker you used 1.4 times of KVA?? can you please explain
@elmekfoujar80434 жыл бұрын
Load current for 1000Kva=(1000000/(1.732*415))=1391.25A Here 1.732 is square root of 3 there for, 1kVA The Load current will be 1391.25/1000=1.39125 this value is approximated as 1.4
@elmekfoujar80434 жыл бұрын
I THINK IT IS NOT 40% IT IS 0.421 THIS VALUE IS OBTAINED FROM CALCULATING CORRECTION FACTOR FOR IMPROVING PF 0.8 TO PF .95
@sajalmahmud72866 жыл бұрын
why we not use 150A C.B in last variable Capacitor bank
@gaju1484 жыл бұрын
Some time APFC panel is not working or its capacitor will not on at right time when required, What is the possible reason for this ?? could you please share
@pravinbidgar25266 жыл бұрын
Sir cdc 100 amp hi kyue liya 200amp kyue nahi please guide
@ElectricalInfinity6 жыл бұрын
Cdc selection is done based on capacitor value. For example we are using a 50 kvar capaitor then we can use same value 50amp cdc . FOR circuit breaker we have to double the value 50 kvar × 2 so 100 amp mccb is selected as 1 kvar = 2A.
@kalpeshpathak24826 жыл бұрын
Sorry but the same current will flow through the CDT which is through MCB so the size of the CDC should be 200 amp only
@kalpeshpathak24826 жыл бұрын
Bcz u have considered coman capacitor for 2 nos capacitor
@kalpeshpathak24826 жыл бұрын
*Common CDC
@ElectricalInfinity6 жыл бұрын
As your wish . Go on. Iam going according to standards
@kumarachhami20405 жыл бұрын
Control wiring of Apfc control panel
@91Jawad5 жыл бұрын
What does APFC stand for ?
@ElectricalInfinity5 жыл бұрын
Auto power factor control
@syedimtiyazimtiyaz993 жыл бұрын
CT coil were u shown in figure it may not correct I think
@abhigangarde49885 жыл бұрын
My load is 50KVA.... how much cap. Bank do I need to maintain PF at 9
@dkverma674 жыл бұрын
Please find out the pf of your load. 80% of that kvar of lagging pf to be considered fr capacitor bank.
@kumarachhami20405 жыл бұрын
Apfc control wiring diagram, please upload sir
@busraahmed17083 жыл бұрын
to select the circuit breaker of transformer u multiply 1250 by 1.4. my question is from where u get 1.4
@rasengan97433 жыл бұрын
P= ✓3.V.I.n Where n is efficiency Hope this helps
@rajdeepbhowmick12282 жыл бұрын
Can anyone please explain the reason behind 40%? Yaha Qc = P * ( tanφ1 - tanφ2) iss formula se alag rating mil rahi or 40% se calculation karne pe alag value mil rahi.
@parimalrode85724 жыл бұрын
ACB 1000A, but total of all CBs (200AX4 +150A + 100A =)1050A, please explain?
@harishgudepu12966 жыл бұрын
OK,,, 25 25 25 kvar 75 kvar how mccb rating,,,,,
@rakeshkumarpalai22666 жыл бұрын
Why 40% @ 06:20 , why 2×1000
@mirzasaqib42204 жыл бұрын
for apfc panel calculation value is 1.31 where comes 2
@nasiruddinhimu50754 жыл бұрын
sir i know kvar=60%of kva value....why u use 40%
@sajalmahmud72866 жыл бұрын
1kvar = how 2 A plz I am confused
@ranjan14365 жыл бұрын
how? is 40% of 1250 KVA transformer is 500 KVA, not KVAR. please explain.
@dkverma674 жыл бұрын
It is assumed the maximum kvar to be compensated as pf of transformer depend on load. This is included the kvar due to transformer internal magnetic losses dkverma67@rediffmail.com
@samajwadipartyhai3885 жыл бұрын
Ye mujhe hindi me chahiye kya mil sakta hai
@Kk-hs4qf Жыл бұрын
phase, neutral and earth wire should be of same size for single phase loads. Current for three phase load can be taken as 2A and for single phare 6A can be taken. What you are saying is completely wrong.
@nafeesakhtar7966 жыл бұрын
CB for Tr 1250*1.4=1750 kvar ok but ACB rating for Tr 2000A???? How its done. which logic???
@ElectricalInfinity6 жыл бұрын
Rated acb is of 2000A so i had take 2000 A acb . Good doubt 👏👏
@nafeesakhtar7966 жыл бұрын
Sir according to your thumb rule to find the ACB rating... ie *2, 1750*2= 3500 so the Tr. ACB rating would be slight higher than 3500 A . but why you used 2000A??? This was my doubt. Plz explain
@ElectricalInfinity6 жыл бұрын
Thumb rule is only valid for capicator circuit breaker selection for transformor c.b selection we have to only multiply transformer kva rating with 1.4 . Hope you got mine answer 😊
@nafeesakhtar7966 жыл бұрын
Thanks for your quick response
@jatinchatterjee22196 жыл бұрын
Nafees Akhtar Bhai transformer's rating is 1250 not 1750,so we multiply 1250 by 1.4 (1250*1.4) we get 1750 ,as the nearest rating of ACB is of 2000 amperes, so we take 2000 amperes ACB, I think u got it
@sidheswarparida93725 жыл бұрын
Due to Clearly not visible I m not pleasure. And understanding process is not normal.
@jagdishsingh-di3nr6 жыл бұрын
hindi me tumko sarm aati hai, hindustani nahi ho kye