Voltage input has been set At 1:53. But the input type is a K-type element. Isn't it?
@AutonicsCorp4 жыл бұрын
Thanks for your comment. You are right. We created the situation for voltage input. It is just an example.
@cakadd10212 жыл бұрын
Excuse me sir, I have a problem setting the temperature controller parameter, i want to the temperature controller Autonics TZN4S can give the analog signal (for example 0°C - 100°C = DC 4-20 mA) , i have done setting the parameter like in the manual book, but the temperature controller can't out the analog signal. can you help me, please?
@AutonicsCorp2 жыл бұрын
If the 4-20mA you mentioned is the transmission output, it is not supported by TZN4S. (For the purpose of transmitting the measured temperature value to other controllers) Please review the product with transmission output function. Thank you.
@cakadd10212 жыл бұрын
@@AutonicsCorp can you tell me what autonics temperature controller supports analog output to send signal to PLC?
@AutonicsCorp2 жыл бұрын
If you want the same size product, TK4S-R4□□ or TK4S-A4□□ is suitable for you. For more details, please visit our website(www.autonics.com) and refer to the product manual.
@cakadd10212 жыл бұрын
@@AutonicsCorp ok, thank you sir
@yudha19713 жыл бұрын
How to set the time of the temperature operational? Is it include in this TZN series?
@AutonicsCorp3 жыл бұрын
It does not support setting the operating temperature. Thank you.
@arifrahmansaleh25943 жыл бұрын
How to setting as a cooler controller and set the gap with sv?
@AutonicsCorp3 жыл бұрын
First, set [o-Ft] of parameter 2 group from [HEAt] to [CooL]. Then, set [P] of parameter 1 group to [0.0]. (This means using it as an ON/OFF control.) Lastly, set [HYS] of parameter 1 group. (This means a gap with the Set Value.)
@josemiguelmachadomendoza26074 жыл бұрын
Excelente informacion. Demostracion suficiente.
@dimassetyoadjie98844 жыл бұрын
i was setting to input type K Thermocouple but display status still open, how to fix it?
@AutonicsCorp4 жыл бұрын
Please check the sensor wiring once again. In case of thermocouple, connect (+) to terminal B and (-) to terminal B'.
@dimassetyoadjie98844 жыл бұрын
I was make sure the sensor Wiring on that terminal and the display still open. how should i do ?
@AutonicsCorp4 жыл бұрын
If so, it could be a problem with temperature sensor or temperature controller. Please test by replacing the temperature sensor or temperature controller.
@amanhanif55824 жыл бұрын
Can i change my old model which is datalogic qs/qd series with tzn4s-14r
@AutonicsCorp4 жыл бұрын
Actually, TZ/TZN series is also an old model. Please check with the TK4S-14RN or TX4S-14R.
@TechTricks7864 жыл бұрын
Amazing 👌
@raulmendozachichoky95113 жыл бұрын
buenas una pregunta tengo un controlador de temperatura tnz4s-r14 si le conecto la termo coupla tipo j queda intermitente LLLL si se la quito queda igual que podría ser me podrían ayudar gracias
@AutonicsCorp3 жыл бұрын
Compruebe si [In-t] del grupo de parámetros 2 está ajustado a [JIC.H].
@yersonantezana16502 жыл бұрын
Yo temgo uno igualito pero me marca open k puede ser la termocupla es de tipo k 1200
@AutonicsCorp2 жыл бұрын
[OPEN] significa que el sensor está desconectado. Compruebe los terminales de cableado del sensor de temperatura. Compruebe si el tipo de entrada [In-t] coincide con el tipo de sensor de temperatura utilizado.
@yersonantezana16502 жыл бұрын
@@AutonicsCorp ok gracias estimado
@ulfabramantya65363 жыл бұрын
how to fix error LLLL tzn4s-14s ?
@AutonicsCorp3 жыл бұрын
'LLLL' is displayed when an input lower than the measurable value is entered. (For example, 4~20mA is measured, but 0mA is input) Please check the sensor wiring and check if the sensor is broken.
@asepsaepuloh85726 жыл бұрын
Cara setting temperatur celcius ke farenhait
@saithan666132 жыл бұрын
Bisakah tzn4s 14r pakai ssr..???
@AutonicsCorp2 жыл бұрын
TZN4S-14R is a relay output and SSR is not available. Please use the TZN4S-14S product.
@juniorquerevalurojas72893 жыл бұрын
Thanks for the video
@emipvargas386 жыл бұрын
Hola quiero que ayude soy de Chile yo tengo un conteo de temperatura modelo TZN4M QUIERO A SER FUNCINAR CON UN CONTACTOR DE 380V.×50A PODRÍA MANDARME UN DIGRAMA ME ENTEREZA PORFA QUIERO INSTALAR EN UN BAÑOS SAUNA GRACIAS MUCHAS GRACIAS
@AutonicsCorp6 жыл бұрын
Please contact our Chile customer service at sales@autonicsusa.net
@emipvargas386 жыл бұрын
Espero su respuesta.
@abosreaamohmed6865 жыл бұрын
Programmable counter tzn4h
@sedomar28935 жыл бұрын
Work good
@saithan666132 жыл бұрын
Panasnya naik terus tidak mau turun
@AutonicsCorp2 жыл бұрын
Sorry. We need a little more information. (Model name, Condition, Other symptoms...) Please check if the heater is operating as the OUT indicator on the front part turns on.