Brand : Daikin inverter model : RKS25GVMG (CU) model : FTKS25DVM(Wallmouted) error code : F3 fault : Condenser coil choke by dust. solutions : wash Condensing unit. #Daikin #VRV3 #VRV #VRV4
Пікірлер: 60
@sotirisgrig14063 жыл бұрын
Good morning Mr. Bon from Greece! Watching the video we see once again how important the maintenance of air conditioning units is! Well done very good work!
@BonMj3 жыл бұрын
Thanks bro
@noumankhalid85483 жыл бұрын
@@BonMj plz I lost my mitsubishi city multi indoor PEFY-P100VMA-E wiring diagram
@BonMj3 жыл бұрын
@@noumankhalid8548 what is your aircon problem
@noumankhalid85483 жыл бұрын
@@BonMj model satting and function setting sw1 sw2 sw3 sw4 I lost wring diagram cower
@noumankhalid85483 жыл бұрын
@@BonMj main problem is expician valve is not open
@icopel2584 ай бұрын
daikimeu ar condicionado quando funciona depois de um tenpo area disjuntor
@jmdavid5981 Жыл бұрын
Mr. Bon, I did the first procedure then it worked, but after 2hrs, it stopped working again. What could be the problem? My AC was cleaned just 2 weeks ago
@BonMj Жыл бұрын
Hi,Any error code ? Indoor stop working or outdoor stop working?
@jmdavid5981 Жыл бұрын
@@BonMj F3 is that error code, indoor stops working when on "cool" but it is working when it's on "fan only"
@BonMj Жыл бұрын
@@jmdavid5981 F3 can be insufficient gas, outdoor unit coil clogged or discharge thermistor not functioning well.
@jmdavid5981 Жыл бұрын
Thank you Mr. Bon. I will ask local technician to check it. Big thanks!
@@BonMj cu discharge thermistor 的om 应该是比其他thermistor 高很多对吧?
@BonMj2 жыл бұрын
@@janshaw5472 通常在100多
@谢兴旺-n9j2 жыл бұрын
@@janshaw5472 那个discharge thermistor和其他都是一样的
@mdtaslimalam85953 жыл бұрын
Good information
@BonMj3 жыл бұрын
Thanks
@liang20383 жыл бұрын
Boss, pls help. My daikin aircond show error code f3 too. Both inside n outside machine are running but no cool air. Outside machine started to make some loud noise after 20/30 mins. Req for service, the guy say thr is no gas at all in my aircond. He suspect leaking but can't find any oil residue. Tried pump in some gas but still no cool air, he said seems like the compressor automatic cut off gas. He advise me to buy new aircond. Pls advise if I should let other ppl take another look o it's really a lost case. Thank you. 🙏🙏
@BonMj3 жыл бұрын
First, must check the pressure, if pressure low,after top gas should cold. 2nd,may other part got problem ,like EEV valve is faulty, also can cos low pressure. 3)what is the pressure reading?before and after.
@liang20383 жыл бұрын
@@BonMj Thanks for your reply. Aiks, he didn't tell me the pressure n I don't have equipment to check. At first, he thought must be serious leakage but then he was able to pump refrigerant in. Then after running about 10 minutes, the outdoor unit started to have loud n weird noise, sound like car engine can't startup. Then the compressor gave up n have green light blinking on indoor unit. To be direct, the service person didn't make much effort to check. He think not worth to go into detail, just buy new one. That's y I still thinking whether it's worth to call other service o just change a new aircond. Is it gonna cost a lot to fix my aircond in most possible scenario? I mean, based on ur experience. Or is there anything I can check before calling a professional.
@BonMj3 жыл бұрын
@@liang2038 if insufficient gas,compressor running should be normal, if compressor loud noise like somewhere clogged and pressure drop.this need technician to check. Where you from .
@definlukose24503 жыл бұрын
@@BonMj i purchased a new 1 ton daikin ac yesterday and same issue that you are facing F3 error both indoor unit and outdoor unit working but no cooling but the discharge pipe is chilled and is leaking water (moisture)
@BonMj3 жыл бұрын
@@definlukose2450 check pressure,may insufficient gas or EEV problem or hand valve not fully open.
@IceTeaCrackHeadАй бұрын
Turning it on and off is truly the answer to everything
@anisahmad8252 Жыл бұрын
Daikin non inverter f3 error R22 lp 55 HP 180 working 3 minutes and trip like that 3 minutes working 2 minutes stop like that after doing this 1 hour or 1 and half hour error show f3 help
@BonMj Жыл бұрын
Like insufficient gas
@demoshow9504 Жыл бұрын
Sir, my unit daikin inverter FTKD25DVM isn't cooling and shut down itself after 30+ mins. Have F3 error code. Technician came try to recharge gas. But they said compressor turn on shortly but shut off. Can see the copper piping is freezing. Technician suspect compressor is gone. Told me to buy new one. Is there still chance it can be fix? Thanks
@BonMj Жыл бұрын
Single split? If single split may be can try check lev
@demoshow9504 Жыл бұрын
@@BonMj yeah single split. At the end it was the eev that causing the F3 error code. Thanks for making all these great video!
@BonMj Жыл бұрын
@@demoshow9504 great 👍. You are welcome
@netnoob77 Жыл бұрын
Hi, my Daikin inverter (FTKD35DVM) is experiencing the same symptoms as your aircon. Technician also did the same and recharge the gas but the compressor will run for a short while and then shut off. Did your technician manage to fix your aircon in the end by replacing the EEV? I am seriously considering on buying a new aircon but this aircon has served me well and would like to keep it if possible.