How to diagnosis multi-outdoor-unit error using monitor mode 14 | Daikin VRV3

  Рет қаралды 14,230

Bon Mj

Bon Mj

Күн бұрын

Пікірлер: 66
@hossainurrahman6700
@hossainurrahman6700 2 жыл бұрын
finally i get a great teacher thank you so much sir thanks from india
@BonMj
@BonMj 2 жыл бұрын
Welcome
@JuanTodoli
@JuanTodoli 2 жыл бұрын
Oh my God... this was The Big Party of The Faulty Thermistors! 🥳 One after another!
@hanyaberbagi9124
@hanyaberbagi9124 2 жыл бұрын
Hi sir bon , i love your explanation . 🙏 . Im beginner in Daikin VRV . Say hello from BALI
@BonMj
@BonMj 2 жыл бұрын
Thanks
@m.haslam8495
@m.haslam8495 2 жыл бұрын
Hi everyone, I've working on Daikin VRV for many years. I have one question, why does the Daikin VRV have a lot more problems with their systems than any other equivalent VRF Systems, like Mitsubishi Electric, Mitsubishi Heavy, Fujitsu, Toshiba, plus many others. Just the parts department of Daikin are so extensive and very busy., especially here in the UK 🇬🇧. One example, replaced many, many compressors for Daikin VRV, but for other manufacturers, just a few in my time. What I have personally found that if a Daikin VRV System is professionally installed and commissioned and well maintained afterwards, there will be a lot less breakdown and thus less repairs. We have installed Daikin VRV Systems and they have been running trouble free for many years. Anyway, it keeps me very busy especially working on Daikin VRV Systems.
@khim1jivit691
@khim1jivit691 2 жыл бұрын
Hello sir bon😍I like you ..i’m from Cambodia
@BonMj
@BonMj 2 жыл бұрын
Thanks
@RamKrishna-zb5ng
@RamKrishna-zb5ng 2 жыл бұрын
Very nice sir,from India, ,
@BonMj
@BonMj 2 жыл бұрын
Thanks 🙏
@boonyeun2056
@boonyeun2056 2 жыл бұрын
Thx's for ur explaination :)
@BonMj
@BonMj 2 жыл бұрын
Welcome
@karaors8970
@karaors8970 2 жыл бұрын
Hi, it's a very explanatory video again bro.👏👏👏🙏
@BonMj
@BonMj 2 жыл бұрын
Thanks
@sarfarajshaikh4582
@sarfarajshaikh4582 2 жыл бұрын
Great job brother
@BonMj
@BonMj 2 жыл бұрын
Thanks
@kashibaba521
@kashibaba521 Жыл бұрын
Bon sir lot of thanks 💓
@BonMj
@BonMj Жыл бұрын
Welcome
@janshaw5472
@janshaw5472 2 жыл бұрын
very nice teach....
@BonMj
@BonMj 2 жыл бұрын
Thanks 🙏
@peramaraj2763
@peramaraj2763 2 жыл бұрын
Thanks for your update sir i would like to expert Mitsubishi outdoor function settings video sir
@asangajayalath1665
@asangajayalath1665 2 жыл бұрын
Good job
@BonMj
@BonMj 2 жыл бұрын
Thanks
@davecoolaircon
@davecoolaircon 2 жыл бұрын
Hi Mr Bon ,like to check with you .What does the acceptable range of ohms reading of the thermistor when ambient at 30°c?
@BonMj
@BonMj 2 жыл бұрын
Daikin 16K ohm for gas pipe thermistor
@theluunguyen1234
@theluunguyen1234 Жыл бұрын
You have video setting of normal to emergency mode for inveter for singer unit. Thank you.
@BonMj
@BonMj Жыл бұрын
Same setting
@arunachalammk743
@arunachalammk743 2 жыл бұрын
Dear sir, I am Arunachalam from Chennai, Tamilnadu, India. Glad to chat with you. Now I am servicing rxyq 18 pay6 +rxyq 18 pay6 +rxyq 10 pay6 Daikin VRV. rxyq18pay6 is a master. When on the unit rxyq 10 pay6(master) runs for 10 min without error. After 10 min it gave a u4 error and the unit stopped. When I clear the error in the remote control it will start again. Sometimes slave one inverter compressor starts. But, only one fan starts running for 10 seconds, stops, and again starts after 30 seconds and stops within 10 seconds. slave condenser coil gets high heat. slave gas flow gives more sound. slave 2 is dead silent. total 40 indoor units. when I load more than 10 units it will give a u4 error. Please suggest an idea to rectify it.
@CCL13984
@CCL13984 Жыл бұрын
In this case,need to bypass the master unit?
@DanielRomero-cu1ht
@DanielRomero-cu1ht 6 ай бұрын
Hola será q me pueden ayudar no consigo la configuración de los ds de la placa a1p. Vrv4 RXYMQ8AY1. NO VINO con el papel y no los consigo
@BonMj
@BonMj 6 ай бұрын
Your email?
@velikarakaya8620
@velikarakaya8620 Жыл бұрын
Merhaba Daikin Vrv 4 error L1_U3 veriyor Problemi nasıl çözülür
@BonMj
@BonMj Жыл бұрын
Check inverter pcb,fan motor, compressor
@sahiljuned3762
@sahiljuned3762 2 жыл бұрын
Please one video uj 01 urgent explain daikin vrv 4
@allanacebartican7715
@allanacebartican7715 2 жыл бұрын
Can you help me for PJ error vrv3 but install of sub parts accu Fan pcb 2 pcs. For master and 2 pcs. For Slave.. I also replace accu main pcb with correct dip switch settings
@BonMj
@BonMj 2 жыл бұрын
Check inverter and fan driver Any wire connections wrong. PJ is improper combination between inverter and fan driver
@johnnyroxannebautista2063
@johnnyroxannebautista2063 2 жыл бұрын
Sir Bon i just notice that red to black is 96 ohms red to white is 5 mega ohms what about white to black? is there a resistance reading fo that?
@BonMj
@BonMj 2 жыл бұрын
Red Black = 96K ohm Red white = 5M ohm Normally white and black i never measure, next time i get the reading in the video too.
@johnnyroxannebautista2063
@johnnyroxannebautista2063 2 жыл бұрын
@@BonMj thanks sir Bon.
@Mj-iu6yx
@Mj-iu6yx 2 жыл бұрын
Hi Bon, how do you recognise how much the reading of thermistor or sensor should be, tq
@BonMj
@BonMj 2 жыл бұрын
16K ohm(temperature sround 30°c?)
@Mj-iu6yx
@Mj-iu6yx 2 жыл бұрын
@@BonMj one more thing, where can I get the vrv combination, what is the resources, thank you.
@BonMj
@BonMj 2 жыл бұрын
@@Mj-iu6yx from manufacture
@Mj-iu6yx
@Mj-iu6yx 2 жыл бұрын
@@BonMj hi Mr Bon, I need to do troubleshooting on cassette, the problem is, after working for 2 hours, the aircon causes to NCB trip, what do you think the problem is, please help me on this, thank you so much.
@BonMj
@BonMj 2 жыл бұрын
@@Mj-iu6yx check compressor ampere. May be over current or wire poor contact,also can be MCB got problem
@theluunguyen1234
@theluunguyen1234 Жыл бұрын
Good jop
@BonMj
@BonMj Жыл бұрын
Thanks
@bhaveshsapat7032
@bhaveshsapat7032 2 жыл бұрын
Who error of outdoor control pcb faulty
@shahnawazalam3081
@shahnawazalam3081 2 жыл бұрын
Sir please provide us to pdf & image of how toh rest pcb and all sitting
@noelreyes2771
@noelreyes2771 2 жыл бұрын
Sir we changed ah bord from ah single deep switch to a new board double deep switch sir can't you please help me how to install this.sir this is the model RXMQ8AYL VRV4
@BonMj
@BonMj 2 жыл бұрын
I need to check. I only got RXYQ, RXQ, RZYQ, RZUR, RXUQ,
@VinodKumar-ix7rt
@VinodKumar-ix7rt Жыл бұрын
thans sir do you have any group
@BonMj
@BonMj Жыл бұрын
FB
@یسمحمدسفیان
@یسمحمدسفیان Жыл бұрын
Sand pdf sir vrv3 mode satting
@noelreyes2771
@noelreyes2771 2 жыл бұрын
Sir how to set double deep switch to ah new board?
@BonMj
@BonMj 2 жыл бұрын
Follow the list. This list inside new pcb box
@noelreyes2771
@noelreyes2771 2 жыл бұрын
@@BonMj sir there's no list inside the box only pcv sir if it's ok too you can't I get your email.add so that I can't sent it on your messenger
@BonMj
@BonMj 2 жыл бұрын
@@noelreyes2771 bonmj81@gmail.com
@ESCHILLFACTOR
@ESCHILLFACTOR 2 жыл бұрын
Sir bon can i apply in your company im filipino
@mohdmaqsoodshaikh5234
@mohdmaqsoodshaikh5234 2 жыл бұрын
Sir Daikin vrv3 salev1 on but master unit not working salev on continue but master not on sir rigen on errors no problem but master unit not start
@BonMj
@BonMj 2 жыл бұрын
Why master not working? Error?
@uyexdu4646
@uyexdu4646 2 жыл бұрын
Sir bon how are you
@BonMj
@BonMj 2 жыл бұрын
I m good.Thanks bro
@tabresztabu562
@tabresztabu562 2 жыл бұрын
Hi brother
@BonMj
@BonMj 2 жыл бұрын
VRV4 | Emergency maintenance | error E2-01 L5-14 J5-01
13:29
Daikin VRV3 | error E4 | LPS switch
8:43
Bon Mj
Рет қаралды 21 М.
Support each other🤝
00:31
ISSEI / いっせい
Рет қаралды 62 МЛН
Lamborghini vs Smoke 😱
00:38
Topper Guild
Рет қаралды 68 МЛН
Cat mode and a glass of water #family #humor #fun
00:22
Kotiki_Z
Рет қаралды 26 МЛН
Unbelievable Secrets to Mastering Daikin VRV Field Settings
5:33
Mechanical Pros
Рет қаралды 6 М.
Daikin VRV 3 Malfunction Diagnosis Using Outdoor PCB
12:32
Arista Air Conditioning Training Videos
Рет қаралды 11 М.
Diagnosing Daikin H3 E3 Error (EP 1)
14:05
Mitch Attwood
Рет қаралды 17 М.
Support each other🤝
00:31
ISSEI / いっせい
Рет қаралды 62 МЛН