As shown in video, missing a wiring step. You show correctly the supply wiring method’s EQUIPMENT GROUNDING CONDUCTOR wired to GREEN GROUNDING SCREW. MISSING STEP: Because you ALSO show a GREEN BONDING JUMPER terminated at the RECEPTACLE’S TERMINAL, you did NOT show that GREEN BONDING JUMPER MUST be “PIGTAILED” to the supply wiring method’s EQUIPMENT GROUNDING CONDUCTOR, implying that that supply wiring method’s EQUIPMENT GROUNDING CONDUCTOR can be DIRECTLY terminated at the RECEPTACLE’S TERMINAL WITHOUT a BONDING JUMPER.
@brianerock4 ай бұрын
As shown in video, missing a wiring step. You show correctly the supply wiring method’s EQUIPMENT GROUNDING CONDUCTOR wired to GREEN GROUNDING SCREW. MISSING STEP: Because you ALSO show a GREEN BONDING JUMPER terminated at the RECEPTACLE’S TERMINAL, you did NOT show or even mention that the GREEN BONDING JUMPER MUST be “PIGTAILED” to the supply wiring method’s EQUIPMENT GROUNDING CONDUCTOR, implying that that supply wiring method’s EQUIPMENT GROUNDING CONDUCTOR can be DIRECTLY terminated at the RECEPTACLE’S TERMINAL WITHOUT a BONDING JUMPER, in violation of NEC® 250.148(B), 250.148(C), and 250.146.