I think he used the flexible wire for the phase indicators.
@multiskilledelectrician1 Жыл бұрын
You absolutely right. I figured it out when I tracing the various cables. Thank you so much.
@GhcelebsHUB-TV Жыл бұрын
I think there is 1 neutral or live wire getting contact with the exposed metallic part of either the DB or the Change-Over. The dressing in the DB and the change over is very poor.
@multiskilledelectrician1 Жыл бұрын
That will cause an electrical issue called short circuit and short circuit wouldn't be able to trip an RCD but MCB. Thank you so much for the observation and input. I really appreciate you.
@benjamin123477711 ай бұрын
yeah the wiring is very bad,some Ghanaian artisan menn
@ibrahimmohammed-hn4gm Жыл бұрын
Check very well , maybe water enter some sockets or switches
@multiskilledelectrician1 Жыл бұрын
Noted! Thanks.
@WilliamsAdjei-r2l9 ай бұрын
Yes whiles it normally happens when raining it can happen water enters somewhere in the electrical garget
@WilliamsAdjei-r2l9 ай бұрын
Please help me where would you connect the neutral in the changeover switch whiles you single phase meter?
@yussifabdulrafiw69363 ай бұрын
Sometimes the RCD also tripped when there is water in the outside light