Pls upload video on busbar protection for one and half breaker scheme
@relayprotectionelectrical2 ай бұрын
Okay I will
@binodburman21374 ай бұрын
At 09:21 you said by tripping tbc cb fault will be isolated. Pls check incomer 1 will continue feeding fault. Pls write formula for zone a b & c
@relayprotectionelectrical4 ай бұрын
Since Incomer 1 is diverted to TBC..due to bus fault TBC 96 will operate as well as it will send DT to the HV or LV of the Transformer whichever is applicable and thereby it will isolate fault.
@binodburman21374 ай бұрын
@@relayprotectionelectrical correct
@binodburman21374 ай бұрын
Your video are very easy to understand. Thanks. Your introduction pls