Calculating Cooling Loads and Room CFM

  Рет қаралды 319,632

VRF Wizard

VRF Wizard

Күн бұрын

How to Calculate Cooling Loads and Figure Room CFM for commercial buildings.
What are the basic components that make up a Cooling Load?
How do you calculate the CFM for a room?
How many tons of cooling are required?
Visit the www.VRFWizard.com for additional information related to commercial & Residential HVAC & VRF/VRV Systems.
#coolingloads #engineering #hvac

Пікірлер: 155
@ramnareshsharma6160
@ramnareshsharma6160 4 жыл бұрын
Its a great pleasure to understand excellent experience most relevant to HVAC people.
@VRFWizard
@VRFWizard 4 жыл бұрын
You can also visit our other company which provides free training for the HVAC, Electrical & Plumbing Trades at www.mepacademy.com
@zohraali7230
@zohraali7230 5 жыл бұрын
Thank u so much really helpfull for me I like it good work thank u once again please give more information about HVAC.
@steveowen5143
@steveowen5143 Жыл бұрын
Very helpful info thank you. This is helpful for basic sizing of cooling coils.
@VRFWizard
@VRFWizard Жыл бұрын
You're Welcome. Thanks for watching.
@WxRod77
@WxRod77 2 жыл бұрын
Excellent and vrry useful video. Those others saying just multiple room dimensions and multiply by a "factor", should clearly qualify that as only a very rough estimation for sizing a room window AC!
@VRFWizard
@VRFWizard 2 жыл бұрын
Thanks.
@engineeringmaniac9696
@engineeringmaniac9696 2 жыл бұрын
That was really cool explanation. Made it very understandable.
@VRFWizard
@VRFWizard 2 жыл бұрын
Glad you liked it. Please see our other channel for more great HVAC, Electrical and Plumbing Training Videos at MEPAcademy
@robertjavier398
@robertjavier398 5 жыл бұрын
Thanks for this video and its really helpful to our family business which is related to technical (aircon services) we are an authorized dealer installer and supplier of any acu brand here in the Philippines.. THIS IS ADDITIONAL KNOWLEDGE.. thanks for sharing
@VRFWizard
@VRFWizard 5 жыл бұрын
Robert, where are you located in the Philippines? We were there in January 2019 in Manila and Coron. Next time we visit the Philippines, we would love to stop by and see your facility.
@Mohan1960
@Mohan1960 Жыл бұрын
Excellent.informative for fresh graduates.
@HVACTutorial
@HVACTutorial 4 жыл бұрын
You are doing a great job, keep it up
@Gelos_vlog0706
@Gelos_vlog0706 5 жыл бұрын
Thank you for sharing the right heat loads calculations
@resurgensix
@resurgensix 3 жыл бұрын
That is the info I needed! THANKS
@TheAbdallah89
@TheAbdallah89 3 жыл бұрын
Very thorough and clear explanation. Thank you for your effort.
@ProfCharltonAcademy
@ProfCharltonAcademy 4 жыл бұрын
thanks for this wonderful lecture.. hope to have more sample calculations like this....
@shailendramulgaonkar2980
@shailendramulgaonkar2980 4 жыл бұрын
Thanks very much for wonderful & simplified explanation. i would like to have complete design for VRF system.
@jessehollenbeck4607
@jessehollenbeck4607 2 жыл бұрын
Very helpful. Thank you.
@VRFWizard
@VRFWizard 2 жыл бұрын
You're Welcome
@Arieldny
@Arieldny 4 жыл бұрын
excellent tutorial! is helping me understand better how to calculate heat loads! thanks
@mohamedragab4828
@mohamedragab4828 6 ай бұрын
Very helpful info thank you . need to ask why did not u use the floor area of the building . its need to be used if its on a unconditioned space
@tanghingkwong4396
@tanghingkwong4396 5 жыл бұрын
Very good for teaching & learning purpose. Tqvm
@leslieroberts4436
@leslieroberts4436 3 жыл бұрын
Good job! thank you for the video
@dtg8672
@dtg8672 Жыл бұрын
How are loads calculated if the room is centrally located in the building with no windows? Do you still do the solar load for the building envelope?
@jaykesapalaran5434
@jaykesapalaran5434 2 жыл бұрын
Good teaching
@VRFWizard
@VRFWizard 2 жыл бұрын
Thank you
@palmabeatriksan7600
@palmabeatriksan7600 2 жыл бұрын
What are the book recommendations that you often use to learn VRF
@VRFWizard
@VRFWizard 2 жыл бұрын
ASHRAE is the industry leader and they have a chapter in their handbook on VRF that provides a good explanation.
@wyleaziz5050
@wyleaziz5050 4 жыл бұрын
Thank you for the Amazing information. A whole career in just 16 Min. Could you please attach the SCL Chart from ASHRAE and an example of how to use it?
@barramedaalberto319
@barramedaalberto319 6 жыл бұрын
Thanks sir for the very needed information about.
@mohammadqattawi8911
@mohammadqattawi8911 7 жыл бұрын
thanks .. very simple & useful
@shahriarraeisidehkordi4957
@shahriarraeisidehkordi4957 2 жыл бұрын
thank u so much so so much
@VRFWizard
@VRFWizard 2 жыл бұрын
Your Welcome
@naglaahamdy3796
@naglaahamdy3796 3 жыл бұрын
Great .thanks 👍
@VRFWizard
@VRFWizard 2 жыл бұрын
You are welcome!
@ironguard4048
@ironguard4048 2 жыл бұрын
What about second floors? How does that factor in? Would I just measure temperature gain through the floor?
@VRFWizard
@VRFWizard 2 жыл бұрын
If the floor above or below is air conditioned then there is no load. If you have a floor above or below that is not conditioned, like a garage, then you would do the same calculation with the heat gain and loss through the floor.
@saqibazad2237
@saqibazad2237 2 жыл бұрын
excellent
@VRFWizard
@VRFWizard 2 жыл бұрын
Thank you
@techhdan
@techhdan Жыл бұрын
Hello, I've been finding your video on calculating cooling loads extremely informative. I have some specific queries about the Solar Cooling Load (SCL) component of the calculation. I understand that SCL is influenced by factors such as the orientation of the glass, the month, and the time of day, and it's a dimensionless ratio typically ranging from 0 to 1. However, in your equation, you've utilized a value of 250 for the SCL. Could you please explain how this number was derived and why it's used instead of a value between 0 and 1? Is this value a constant, or does it change based on certain variables? If it does vary, how would I go about calculating or finding the appropriate value for my own home's specific conditions? Your clarification on these matters would be greatly appreciated. Thank you for your time and assistance in advance!
@salemalzofiri2404
@salemalzofiri2404 2 жыл бұрын
Do we need to consider the roof as well?
@VRFWizard
@VRFWizard 2 жыл бұрын
Yes of course. Anything that effects the heat gain or heat loss to the space, including interior spaces that are unconditioned and share a wall with the conditioned space.
@Chaomhainn
@Chaomhainn 3 жыл бұрын
VRF Wizard thanks . I recall this many years ago . But this is more for someone as an engineer is it not ? Not all people as installers and techs are processing this in to a work order .Their job is as noted , installation and technical repair .Though your material presentation is important more for sales and management ?
@VRFWizard
@VRFWizard 3 жыл бұрын
Kevin, we believe anyone in the HVAC business from dispatchers to technicians should understand the basics of their business, which includes how loads are calculated. It helps in the discussions with customers as many issues in commercial construction can be related to improper zoning, which is related to the heating and cooling loads, such as block loads and zone loads. An informed technician can be more effective at his/her job by understanding the basics of cooling loads. Thanks.
@ramongeruldo4186
@ramongeruldo4186 3 жыл бұрын
Nice..
@samlee4382
@samlee4382 5 жыл бұрын
Dear Sir, Is this calculation including the cooling load that required to cool the space? Please kindlly advise. Thank you!
@VRFWizard
@VRFWizard 5 жыл бұрын
Yes, Calculating the CFM for the space provides for cooling the space. Latent heat (Moisture) will be taken care of at the cooling coil.
@samlee4382
@samlee4382 5 жыл бұрын
Noted with thanks! I always thought that calculation the cooling demand for a space is considered as the total cooling require to cool the space in sqt +sensible heat +radiation heat +latent heat. Learn a lot from your kindly sharing tutorial. Thank you!
@mohamaddalidig9678
@mohamaddalidig9678 3 жыл бұрын
Thank you
@spruce_goose5169
@spruce_goose5169 Жыл бұрын
I live in the land of leaky houses where air leakage is a MAJOR source of heat loss in winter. Do you have any actual evidence that the air infiltration is a small sum of the load in cooling mode?
@VRFWizard
@VRFWizard Жыл бұрын
We mostly handle large commercial properties. For an older home, infiltration or exfiltartion could be much greater, depending on the quality of construction, window and door types, etc.
@keithwo1
@keithwo1 3 жыл бұрын
How do you get or where do you get the supply air design temp? Thank you,
@VRFWizard
@VRFWizard 3 жыл бұрын
The Supply Air Temperature is based on the type of Equipment your using, for instance a Packaged DX Unit might deliver 55 (F) Degrees Supply Air, while a Chilled Water System might deliver 42 (F) Degree chilled water to an Air Handler Coil where the Supply Air Temperature would be the results of how much Outside Air was mixed with Return Air, resulting in a Mixed air temperature passing over the cooling coil. The supply air temperature is always going to be a function of the mixed air temperature and the temperature of the heat transfer medium (Refrigerant, CHW, HHW, etc) The room temperature set point is determined by the OPR (Owners Project Requirements) if there are any, or industry standards such as ASHRAE. Hope I answered your question.
@keithwo1
@keithwo1 3 жыл бұрын
@@VRFWizard thank you for answering, i have a follow up question, what if you are designing the room, and you really dont know the supply air temperature delivered from the coil? How will you get that value? Or is there a table of it from ASHRAE? Or you can assume for the value? Lets just say we need to maintain the design temperature to 75°F at 50%RH. Thank you for accomodating my quiries.
@VRFWizard
@VRFWizard 3 жыл бұрын
@@keithwo1 Maybe if you think of the process in order. The first thing you would do is run a Heating and Cooling Load. This would tell you how many BTU/Hr the room needs to maintain your conditions of 75 F at 50%RH. Then you would search AC manufacturers Performance Submittals for a unit that would give you the values you need. At that point you really don't need to think about supply air temperatures as long as the AC unit meets your BTU/Hr requirements. Hope that helps.
@keithwo1
@keithwo1 3 жыл бұрын
@@VRFWizard thank you for this info's i really appreciate it,
@elijahravikiran976
@elijahravikiran976 2 жыл бұрын
Clear content,Grate Job. Shalom.✍🏻🇮🇱
@VRFWizard
@VRFWizard 2 жыл бұрын
Thank you
@khalidelpendery8830
@khalidelpendery8830 2 жыл бұрын
Thanx
@VRFWizard
@VRFWizard 2 жыл бұрын
Welcome
@jonathancraccenn
@jonathancraccenn 5 жыл бұрын
Much needed fundamentals
@alazizykaarshe3637
@alazizykaarshe3637 6 жыл бұрын
Thank you very much greet job
@princebojji6964
@princebojji6964 3 жыл бұрын
thanks
@anthonymohammed4957
@anthonymohammed4957 3 жыл бұрын
What about the ceiling load 🤔 sensible heat is a lot from the roof.
@VRFWizard
@VRFWizard 3 жыл бұрын
Yes of course the roof is included. Anywhere there is an exposure to the outside conditions would need to be considered. This would include floors above an unconditioned space. Thanks
@VRFWizard
@VRFWizard 2 жыл бұрын
You're correct. Any area including the roof which is exposed to the outside conditions will be included in the calculations. The example was of a floor in a high-rise between other conditioned floors. You would also include the heat gain from any unconditioned space adjacent to your conditioned space.
@isaacenobun6370
@isaacenobun6370 3 жыл бұрын
Nice
@chandrachhetri1624
@chandrachhetri1624 3 жыл бұрын
Is it the standard value that consumed by 1 watt equal to 3.14 Btu/watt
@VRFWizard
@VRFWizard 3 жыл бұрын
3.412 BTU/Watt
@etc-and-more
@etc-and-more 3 жыл бұрын
Very interesting discussion. Does this also work for heating? The numbers seem like they would be considerably higher if you use a delta-T in the winter time for instance NYC winter design temp is around 17 degrees F. If we want to make the inside temp 70 degrees F are we supposed to use 53 as the temp difference in the calculations?
@VRFWizard
@VRFWizard 3 жыл бұрын
Yes, the temperature difference is also used in the heating load calculations for conductance through exterior walls, windows and the roof, and the 1st floor if you have an occupied space over an unheated garage or similar space. That's why insulation is really important along with a properly sealed building envelope.
@mikaelbasha1992
@mikaelbasha1992 4 жыл бұрын
thank you!
@VRFWizard
@VRFWizard 4 жыл бұрын
Welcome!
@engineeringtrainingideas2334
@engineeringtrainingideas2334 4 жыл бұрын
Usefull information , can you tell me how we calculate the 0F water raise temperature 215 F , how many BTu required
@VRFWizard
@VRFWizard 4 жыл бұрын
Are you asking how many BTU's it takes to raise water from 0 degrees to 215 F? For water, which at atmospheric conditions starts from 32 degrees until 212 degrees F, it depends on the pounds of water you have, so that for each pound of water it takes 1 BTU to raise the 1 Pound 1 degree F. After the water reaches 212 degrees it then enters the Latent Heat of Vaporization stage where any additional heat causes the water to change into vapor. Water from 32 degrees to 212 degrees is all sensible heat as it involves only a change in temperature, after that it is all latent heat which involves a change in state from water to vapor at atmospheric conditions.
@janibashamolla
@janibashamolla 6 жыл бұрын
Good information
@porfiriofranco5070
@porfiriofranco5070 4 жыл бұрын
Hello, thanks for the video, great explanation. Could you explain how to size the coil in order to deal with latent heat and to keep the desired tempetature??
@VRFWizard
@VRFWizard 4 жыл бұрын
Check out ou other video where we cover this topic. If you still have a question, please let us know. kzbin.info/www/bejne/ZniTg56Nfb5kgMk
@bryceelmore8190
@bryceelmore8190 5 жыл бұрын
How would you find the Rvalue of the insulation in an exterior wall if you dont have a set of plans for an existing home?
@VRFWizard
@VRFWizard 5 жыл бұрын
One option would be to make an exploratory hole in the wall to discover what type if any insulation was used. Make a hole that is hidden from view.
@bryceelmore8190
@bryceelmore8190 5 жыл бұрын
@@VRFWizard o okay that makes sense. Thank you
@nabilalaelyani9311
@nabilalaelyani9311 4 жыл бұрын
Hi, thank you vey much for this simple explanation :) . May you please explain more about the room area isn't that become a contributor too? and how to include that in the calculation?
@VRFWizard
@VRFWizard 4 жыл бұрын
The area of the room becomes a factor only because it increases the lighting and plug loads and it may increase the occupant load (More People). The larger the Interior rooms are the greater is the load from internal sources of heat (People, Lights, Plug Loads). If the larger space includes more exterior wall area, then you have an increase in solar and transmission load through the walls and windows. Hope this helps
@ramongeruldo4186
@ramongeruldo4186 3 жыл бұрын
Btw what is the unit of temp.?
@VRFWizard
@VRFWizard 3 жыл бұрын
F for Fahrenheit
@sajnshe
@sajnshe 6 жыл бұрын
Thanks very much for your simplified explanation! So do I care about ventilation and to neglect the #latent heat as its done by other factors in the system and does this run for most regions if they are "modern designed buildings" as you have said ? "knowing that iam in the middle east" also please tell me how to contact you for more information later Sincerely thanks back to you =)
@VRFWizard
@VRFWizard 6 жыл бұрын
The latent heat from your ventilation will be handled by your cooling coil at the equipment. Your cooling coil will be sized to handle the outside air brought into the building for ventilation/fresh air requirements and any infiltration that is considered. This is where the moisture in the air that reaches the dew point temperature of the cooling coil will condense into liquid and become part of the condensation. I hope I have answered your question. Please feel free to contact us through our website at www.vrfwizard.com
@bryceelmore8190
@bryceelmore8190 5 жыл бұрын
So by using the cfm formula for 12,000 btu/h i get 555 cfm. I was always told you need 400 cfm per ton. So if you needed a 1 ton system hypothetically speaking would you be able to put out 555 cfm by providing large enough duct work?
@VRFWizard
@VRFWizard 5 жыл бұрын
400 CFM per ton is just a rule of thumb. Actual CFM should be calculated based on actual conditions. With the formula CFM = Q / 1.08 x Delta-T, if you keep Q constant at 1-Ton (12,000 btu/hr) then CFM and Delta-T work inversely, meaning when one goes up the other goes down. By keeping 12,000 Btu/hr (1-Ton) as a constant value while using different Delta-T’s, higher Delta-T’s will require less CFM/Ton because the system has to do less work per CFM. CFM = 12,000 (Q) / 1.08 x 20 = 555 CFM CFM = 12,000 (Q) / 1.08 x 25 = 444 CFM CFM = 12,000 (Q) / 1.08 x 30 = 370 CFM CFM = 12,000 (Q) / 1.08 x 35 = 317 CFM Hopefully this was helpful.
@bryceelmore8190
@bryceelmore8190 5 жыл бұрын
@@VRFWizard yes that does make sense. Thank you
@55540
@55540 4 жыл бұрын
Sir how to get Delta temperature please explain me
@VRFWizard
@VRFWizard 3 жыл бұрын
The temperature difference is between your design indoor temperature and the Outdoor Design Temperature as indicated by ASHRAE or some other weather data source.
@iqbalfadillah124
@iqbalfadillah124 6 жыл бұрын
Thank you for your video I have one quetion. Can we use these formula in metric system or we have to convert it
@VRFWizard
@VRFWizard 6 жыл бұрын
Sorry, but you will have to convert these formulas to metric
@nimbo9492
@nimbo9492 3 жыл бұрын
Wouldn't it be better to propose a lower supply air temperature (50F), so in this way, with the same cooling load and larger delta T, airflow CFM would be lower therefore smaller MUA or AHU footprint?
@VRFWizard
@VRFWizard 3 жыл бұрын
Great question. The answer is not as simple. It’s best to use Energy Modeling software to explore the options. There are many factors that go into that decisions including the local climate where the building will be installed and the utility rate structure. Lower temperature Supply Air can reduce economizer usage in some milder climates, such as California. The thought to reduce fan energy is a good one but at what cost to drive the supply air temperature down? Now, if you couple the lower supply air temperature with some form of Thermal Storage system then the energy profile looks much better and might make more sense. This will also allow you to shift peak electrical demand to a better utility rate structure. It is best to model your options as there is no straight answer that covers all situations and all geographical locations.
@TanweerAhmed
@TanweerAhmed 6 жыл бұрын
Good
@engineeringtrainingideas2334
@engineeringtrainingideas2334 4 жыл бұрын
Please subscribe my KZbin Channel
@JOQInfo
@JOQInfo 5 жыл бұрын
Good job bro
@ShoaibKhan-ik6it
@ShoaibKhan-ik6it 7 жыл бұрын
Can we use this practically during designing cfu and ahu or this is only basics
@VRFWizard
@VRFWizard 7 жыл бұрын
These are the basic steps for calculating the room load and room CFM. When sizing the Air Handler, you will need to consider the additional load from Ventilation Air (Fresh Air brought into the building per code), including infiltration (Thermal load that leaks into the building). Here is a link to a 61 page document on "Heating & Cooling Loads" that might help. www.cedengineering.com/userfiles/Cooling%20Load%20Calculations%20and%20Principles.pdf
@ShoaibKhan-ik6it
@ShoaibKhan-ik6it 7 жыл бұрын
thank you sir for sharing that knowledgeble page with us
@TanweerAhmed
@TanweerAhmed 5 жыл бұрын
Informative
@wendellblanco3250
@wendellblanco3250 5 жыл бұрын
How about the size of the room? Is it can affect the design?
@VRFWizard
@VRFWizard 5 жыл бұрын
Yes, the size of the room will definitely affect the quantity of CFM required; If you just increase the interior portion of the room you will increase the cooling load due to more lighting and plug load wattage, and more people. If you increase the size of the exterior wall then you would also have an increase due to the solar load and conductance.
@wendellblanco3250
@wendellblanco3250 5 жыл бұрын
For example of 300 cubic feet room, how many btu? Thanks a lot for your reply.
@VRFWizard
@VRFWizard 5 жыл бұрын
@@wendellblanco3250 to determine the Total BTU of an exterior room you would need to know all about the location of that room in the building and its orientation and location in the world, including the quantity and U-Values of the construction components of the wall and windows. Then you need to know how many people, how much lighting and plug loads are in the room. A 300 Cubic Foot room is a small space and if it's an interior space the calculation is much easier as their is no exterior elements to influence the cooling load.
@wendellblanco3250
@wendellblanco3250 5 жыл бұрын
@@VRFWizard Thank you so much for your clear answer. God bless 🙏.
@driftx2
@driftx2 5 жыл бұрын
Why don't you include latent loads in airflow calculations in a room? Is it because the air is exhausted or returned?
@VRFWizard
@VRFWizard 5 жыл бұрын
Latent loads are taken care of at the cooling coil.
@vixenviolet
@vixenviolet 5 жыл бұрын
​@@VRFWizard The video is great. So the airflow you're calculating is that recirculated by a VRF unit... and the cooling coil you refer to, presumably in an AHU supplying the imaginary office, would be sized only for latent cooling load (the AHU coil won't provide any sensible cooling)? Is that right? I've had a look at your site, good range of tutorials. Thanks
@VRFWizard
@VRFWizard 5 жыл бұрын
@@vixenviolet Yes, Latent heat is taken care of by the cooling coil, while the calculation for the room CFM includes the sensible load. The example used was for a typical central station air handler. Either way the moisture is taken care of by the cooling coil and not with the CFM delivered to the room. Moisture comes mostly from the ventilation requirement for outside air, but can also come from infiltration or process loads.
@saidurrahman2662
@saidurrahman2662 7 жыл бұрын
Thanks
@GBabu-xo4ry
@GBabu-xo4ry 7 жыл бұрын
Saidur Rahman
@gnanantkp4400
@gnanantkp4400 5 жыл бұрын
What is BTU?
@VRFWizard
@VRFWizard 5 жыл бұрын
BTU stands for British Thermal Unit. It is a measure of heat. It is defined as the amount of heat it takes to raise the temperature of 1 pound of water 1 degree Fahrenheit
@mohsinzubair4129
@mohsinzubair4129 7 жыл бұрын
helpful
@engineeringtrainingideas2334
@engineeringtrainingideas2334 4 жыл бұрын
Please subscribe my KZbin Channel
@md.zaberalimran315
@md.zaberalimran315 5 жыл бұрын
why wall outside temperature and inside temperature different is (100-75) =25? how
@VRFWizard
@VRFWizard 5 жыл бұрын
The design outside air temperature for the example is 100 degrees, while the inside temperature is designed to maintain 75 degrees. Depending on where your building is located geographically there will be historical weather data that indicates the expected outside air temperature for that region of the world. Obviously the coastal areas will have a lower outdoor design temperature than the desert. The inside temperature is based on local energy codes, ASHRAE standards or standard practice. For this example we choose 75 Degrees. The difference in the temperature between the outside and inside is what drives the heat transfer.
@ubadaashaeib8237
@ubadaashaeib8237 4 жыл бұрын
I thought that the heat been produced by people is considered a latent heat, not a sensible heat. I am confused now
@VRFWizard
@VRFWizard 3 жыл бұрын
People produce both Latent (Moisture) and Sensible Heat. When calculating room CFM we take into consideration the Sensible Heat. The latent heat will be taken care of at the Cooling Coil.
@zohraali7230
@zohraali7230 5 жыл бұрын
HI this SOHAIL ALI I M HVAC TECH pleaser share more information about HVAC how to the calculation to unit tons to area thank u so much for help.
@hlyautey
@hlyautey 5 жыл бұрын
You are putting 2 tons of a/c into a room that only needs 1/2 ton. The purpose of going through these calculations is to prevent oversizing. I rate this an epic fail.
@VRFWizard
@VRFWizard 5 жыл бұрын
The purpose of the exercise is to show what goes into a cooling load calculation. With the current focus of jurisdictions on building envelop energy performance, the cooling load calculation will be dictated by the "U" values of the building assemblies and the code required maximum allowable "U" values. There are many rooms in the commercial and industrial industry that require much more CFM per Ft2 than the example in this video. So it is not unheard of to have this many tons in this small of a space. Most cooling load calculations are done with software, so this video is just to show the basics of what is considered in a cooling load.
@johntempest267
@johntempest267 4 жыл бұрын
Exactly. My house is 1200 square feet, and I have a 2.5 ton Goodman with efficient ductwork. Here in sticky hot SC, it works great. This guy's calculations conclude I'm undersized by 4 tons! Baloney.
@trinidadjaimes4037
@trinidadjaimes4037 4 жыл бұрын
is this based on the wall that has the biggest square footage
@tyl8ter
@tyl8ter 7 жыл бұрын
So would the CL be equivalent to thermal inertia?...
@anonlakh3388
@anonlakh3388 3 жыл бұрын
Roof ? 🤔
@VRFWizard
@VRFWizard 3 жыл бұрын
Of course the load from the roof would be added if you are on the top floor.
@scottm3552
@scottm3552 3 жыл бұрын
What is EAT - LAT?
@VRFWizard
@VRFWizard 3 жыл бұрын
EAT = Entering Air Temperature, LAT = Leaving Air Temperature
@roberttavernier71
@roberttavernier71 5 жыл бұрын
When they showed the outlet 1:24 , did anybody get bothered about the screw not being straight?
@gebresam001
@gebresam001 5 жыл бұрын
OCD is rough lol
@amarabd7947
@amarabd7947 5 жыл бұрын
niec
@ronmaren4135
@ronmaren4135 Жыл бұрын
I thought the playback speed was on 0.5
@VRFWizard
@VRFWizard Жыл бұрын
Everyone listens at different speeds. The good thing is that the user can always adjust the speed to fit their own preference.
@ronmaren4135
@ronmaren4135 Жыл бұрын
@@VRFWizard thanks for the video mate I am just being silly
@stefanosega7280
@stefanosega7280 9 ай бұрын
You are confusing energy with power. BTU is energy (heat). Watt is power (heat/time). So, at minute 3.00, 1 watt should equal 3.41 BTU PER HOUR.
@armindoferreira5886
@armindoferreira5886 6 жыл бұрын
Like
@bkairconditioner
@bkairconditioner 5 жыл бұрын
14/2/2020
@dpool7416
@dpool7416 Жыл бұрын
How the hell do you calculate SCL though, that was a very poor explanation of it.
@R0yL33
@R0yL33 2 жыл бұрын
get rid of the windows!
@VRFWizard
@VRFWizard 2 жыл бұрын
No windows, I think they call those prisons. I'm sure you're joking, but your right windows are a main factor in heat gain, but the window manufactures have gotten better at creating high visibility, low "U" factor windows.
@AblazeWorship
@AblazeWorship 6 жыл бұрын
Does AREA OF wall include the ceiling/roof if it’s an outside wall?
@VRFWizard
@VRFWizard 6 жыл бұрын
Yes, there would also be a heat gain calculation for the roof of a single story building and for the top floor in a multi-story building. The example given was just to show the main factors contributing to the calculation of room CFM.
@leovarghese3657
@leovarghese3657 6 жыл бұрын
Fools 4 Christ can I get ur contact or mail
@VRFWizard
@VRFWizard 6 жыл бұрын
admin@vrfwizard.com You can visit our website at www.vrfwizard.com for more information
Commercial Load Calculations for HVAC
48:55
CaptiveAire
Рет қаралды 62 М.
UFC 310 : Рахмонов VS Мачадо Гэрри
05:00
Setanta Sports UFC
Рет қаралды 1,2 МЛН
sizing ductwork, quick and easy shortcut
13:47
Able Distributors - Your HVAC Solutions Delivered!
Рет қаралды 109 М.
How to Calculate Air Changes per Hour
5:40
VRF Wizard
Рет қаралды 142 М.
HVAC AIR FLOW CALCULATIONS
26:41
Kingenuity
Рет қаралды 75 М.
Understanding HVAC (For Non-Technical People)
16:01
ACCA
Рет қаралды 378 М.
How Solid State Cooling Could Change Everything
16:01
Undecided with Matt Ferrell
Рет қаралды 1,5 МЛН
Cooling Load | hand calculation example | HVAC 13
20:33
AMJ Engineering
Рет қаралды 97 М.
Psychrometrics Made Simple
48:04
CaptiveAire
Рет қаралды 118 М.
How to Calculate Ventilation Air
10:58
MEP Academy
Рет қаралды 4,8 М.
Simple Cooling Load Calculation Procedure
7:07
aircondlounge
Рет қаралды 543