Can You Run Southwire Romex NM-B Cable in Conduit Without Sheath?

  Рет қаралды 12,139

abrelectric

abrelectric

Жыл бұрын

Did this video help you out? if so www.buymeacoffee.com/abrelectric and help keep this type of video content for homeowners and electricians .
ABR Electric in McKinney TX
214-690-1941 @@
abrelectric.com
Previous Videos on Romex:
• Can Romex Cable be run...
• Stripping Romex into C...
• Save the Children! Use...
Looking for reliable and professional electricians in McKinney, TX? Look no further than ABR Electric! Our team of licensed, bonded, and insured electricians have the knowledge and tools to tackle any electrical installation or repair project safely and efficiently.
At ABR Electric, we take pride in delivering top-notch customer service and unbeatable workmanship at fair and affordable prices. From single pole 20 amp breaker installations to complex rewiring projects, we're equipped to handle electrical jobs of all sizes and scopes in the Collin County area.
Don't put your residential property at risk by attempting to work on your electrical system on your own. Trust the experts at ABR Electric to get the job done right the first time, every time. Contact us today at 214-690-1941 @for all your residential electrical needs in McKinney, TX.

Пікірлер: 36
@paulashley3732
@paulashley3732 Жыл бұрын
I bought you a cup of coffee! ☕. enjoy!
@user-ll1vj7qo1m
@user-ll1vj7qo1m 4 ай бұрын
Type NM cable is permitted only in dry locations. The outside J-box must be raintight, not rainproof, and the conductors inside the conduit to the shed must be rated for wet locations, such as THWN, THHW, or THWN-2. MTW is approved only for machine tool connections and THHN is rated for dry and damp locations only (Table 310.4). Most single conductors now have multiple ratings, such as all three he mentions in the video so you can keep one reel in your truck for many applications.
@abrelectric
@abrelectric 4 ай бұрын
Thank you!!
@admirableawesome2317
@admirableawesome2317 Жыл бұрын
great video!`
@abrelectric
@abrelectric Жыл бұрын
Thanks!
@mancave7
@mancave7 7 ай бұрын
Ok Gurus, DIY with simple scenario, need advice. 3 circuits, 15A max each 24ft run (panel to receptacle) Dry location, under a carport, 8 ft above ground Can 12/2 Romex be used in 1 1/2 PVC conduit?
@ryanb159
@ryanb159 11 ай бұрын
So if you have something like a generator inlet box mounted on stucco, are you able to directly run 8/3 (or 6/3) romex from the main panel to the inlet box without using a jbox since it’s mounted directly to the house?
@scotttribout1150
@scotttribout1150 2 ай бұрын
Here's my issue. NM ROMEX is usually SOLID WIRE. Regardless of the sheeting of the individual wires it's gonna be hard to pull..... Even with a replacement insulated ground wire.
@abrelectric
@abrelectric 2 ай бұрын
I've seen a lot of jacked up romex, forced through conduit (usually water pipe with 90s:)
@pld8993
@pld8993 Ай бұрын
Solid wire is frequently used in conduit but as individual conductors, and it's much easier to pull 3 solid #12s than a single 12-2 cable. You can legally pull romex through 500' of conduit, not a smart move though.
@leestokes6761
@leestokes6761 Жыл бұрын
Helpful information. I’m contemplating running wire from my outdoor service entrance to a free-standing shed, a straight-line distance of maybe 20’ . My preference is buried conduit rather than direct burial of Cale rated for such. 30-60 amps 120 volts is still a fair am of current for me to feel comfortable with direct burial.
@abrelectric
@abrelectric Жыл бұрын
I'm with you regarding conductors in conduit vs direct burial. And, direct burial requires a deeper trench :(
@DavidHalko
@DavidHalko Жыл бұрын
@@abrelectric how deep for direct burial? Can direct burial go directly into house & shed? or are 2x JBoxes required?
@abrelectric
@abrelectric Жыл бұрын
@DavidHalko 24" deep to top of the UF cable. You could go directly through the interior framing like Romex. It's just a bit more difficult to strip and more expensive.
@DavidHalko
@DavidHalko Жыл бұрын
@@abrelectric - I am wanting to dig a hole outside to place a battery box to hold lithium ion batteries for a whole house UPS… about 34.4kw of batteries… need low voltage 48v wires. (Not interested in li-ion being inside the house.) Since this is D/C, would thick direct burial cable or a large conduit be better? (250 amps @48v continuous is possible with the 12k inverter, would be a 6 foot run or so, maybe 10 foot.) Not sure what the code would be for such a beast.
@abrelectric
@abrelectric Жыл бұрын
@@DavidHalko normal stuff: all needs to be listed and approved for your application. I would go with conductors in conduit just for ease of replacement.
@JohnThomas-lq5qp
@JohnThomas-lq5qp Жыл бұрын
Here's a curve ball: At an IAEI continuing education class the instructor told us that it's never legal to run Type MM ( Yea Romex ) outdoors even to feed a wall mounted luminare. Told us to only use UF cable. Reason being outdoors is considered at least a damp location & type NM cable was never approved for damp locations. Have received the AHJ approval in house basements to install maybe 3' of Romex thru a piece of 1/2" EMT that's secured to a painted 1 by 4' wood board to a 1900 box for one or two duplex receptacles. Here's a question why are you not allowed to say install a Romex connector into a 1/2" heavy wall coupling to make the transition from Romex to EMT ? And yes I have done that hundreds of times over the years and yes I know they make a one piece transition approved fitting but it's just more things to stock in an overloaded work van .
@abrelectric
@abrelectric Жыл бұрын
You work with your AHJ. I have similar challenges here. You adapt, and keep getting green tags
@JohnThomas-lq5qp
@JohnThomas-lq5qp Жыл бұрын
@@abrelectric Worst part Pa does not have a state electrical license and in some small hick towns the only electrical contractor issues the license and often fail job after your very qualified inspector passes the job.
@user-ll1vj7qo1m
@user-ll1vj7qo1m 4 ай бұрын
Your instructor may have misinterpreted the code. 334.10 - Uses permitted: Inside single, two family and multi-family buildings. The exterior outlet box that your exterior light secures to is installed inside the building and therefore compliant. There is nowhere in the code that tells us we must do what your instructor says.
@JohnThomas-lq5qp
@JohnThomas-lq5qp 4 ай бұрын
Had a hick town inspector call me up to tell me that I had 3 violations after my inspector passed the job. Told the hick inspector that if I had three legitimate violations that I would find another trade. First violation was because I spliced a #14 wire in a circuit breaker panel in order to reach the circuit breaker. Gave him the code article that allows it so he said that he would let me get away with it this one time. Other two violations were on company that installed an outdoor sign and ran power to it. Told him that was not on my permit and not performed by me.
@joseaguirre4169
@joseaguirre4169 11 ай бұрын
Thank you for your informative videos. In your example, wouldn't it be better to do the transition by installing the J-box indoors to insure that the NM romex never sees the outdoors?
@abrelectric
@abrelectric 11 ай бұрын
And transition to a THW or MTW or UF conductor before outside? Yes, that would be a more complete solution.
@davidszakacs6888
@davidszakacs6888 Жыл бұрын
I'm getting ready to run a 240 volt 6/3 cable to a hot tub which will be on a deck. I want to use flexible Liquidtight one-inch conduit and fittings from just inside the basement, through the joist box, about 5 feet up to a spa pack w/GFCI then down under the deck to the spa, (about 6-7 feet). Is this allowable and do I have to keep the sheathing on the cable? Also, would one-inch diameter conduit be enough? Thanks. Enjoying your videos.
@abrelectric
@abrelectric Жыл бұрын
David, 1" is large enough for 6/3 romex. The technical issue is that the individual conductors inside the sheath are not outdoor or damp rated. So, taking off the sheath makes it easier to pull, but does not change the rating of the conductors. Ideally, you would transition to individual conductors rated MTW or THW or something with a W. Thanks for the question, and subscribe to the channel.
@jaydee3046
@jaydee3046 4 ай бұрын
I can see your point for wet locations. Since inside conduit is not a wet location, can I run romex inside a gray pvc conduit along my garage ceiling? And if I drill holes in the conduit for heat dissapation, does it cease to be "conduit" and OK for protecting the romex? Suppose I do this inside the ceiling?
@abrelectric
@abrelectric 4 ай бұрын
If you're running romex inside of conduit inside (dry environment), just check the fill volume (i .e.12/2 romex cross sectional area vs that of 3/4" pvc pipe). Don't drill holes in it. That works against your overall goal of doing it right 😀
@pld8993
@pld8993 Ай бұрын
There's no need for heat dissipation when romex is installed in conduit. It will never overheat simply because it's in conduit.
@meeponinthbit3466
@meeponinthbit3466 Жыл бұрын
Haven't watched the video yet, but if i recall, didn't this already get clarified in a previous video? If the insulation isn't marked, then it isn't allowed.... (Mostly just posting this to feed the algorithm)
@abrelectric
@abrelectric Жыл бұрын
You are absolutely right. But the questions kept coming, just in slightly different ways :)
@waylandjennings4073
@waylandjennings4073 8 ай бұрын
Does this apply exclusively to Southwire brand cable?
@abrelectric
@abrelectric 8 ай бұрын
I don't know. They're the only manufacturer I looked up, because I was familiar with their wire.
@ElectricianMagician
@ElectricianMagician 6 ай бұрын
No. It's code, no matter the manufacturer
@MrCbell57
@MrCbell57 11 ай бұрын
Don’t walk on wire or water.
Stripping Romex into Conduit- Bringing in the Sheaths
9:04
abrelectric
Рет қаралды 40 М.
Why Romex Doesn't Belong in Conduit: Quality and Longevity
6:20
abrelectric
Рет қаралды 55 М.
Smart Sigma Kid #funny #sigma #comedy
00:25
CRAZY GREAPA
Рет қаралды 16 МЛН
#1 UNKNOWN Conduit and UF Cable Rule you Need to Know! Electricians In Action
8:46
Debunking the Pros: Can WAGO Lever Nuts Handle Heavy Electrical Loads?
9:17
Everyday Home Repairs
Рет қаралды 359 М.
Arlington | BLACK BUTTON - Push-In Connectors
3:09
Scott Electric
Рет қаралды 788
How to Pigtail Electrical Wires
11:33
abrelectric
Рет қаралды 82 М.
Different Types of Romex Wire or NM Electrical Cable
12:06
Phillip Bridges
Рет қаралды 120 М.
Avoid These 5 DIY Electrical Mistakes
8:28
Everyday Home Repairs
Рет қаралды 396 М.
Won't These Melt?!? 15amp Receptacles on 20 amp Circuits!!!
11:47
Electrician U
Рет қаралды 1,2 МЛН