Can You Run Southwire Romex NM-B Cable in Conduit Without Sheath?

  Рет қаралды 15,333

abrelectric

abrelectric

Күн бұрын

Пікірлер: 45
@brianjmortensen
@brianjmortensen 3 ай бұрын
Excellent explanation and information. Thank you for explaining in such detail why unsheathed Romex in conduit is not acceptable. Liked & subscribed as requested !
@JeffBanfield-t6v
@JeffBanfield-t6v 9 ай бұрын
Type NM cable is permitted only in dry locations. The outside J-box must be raintight, not rainproof, and the conductors inside the conduit to the shed must be rated for wet locations, such as THWN, THHW, or THWN-2. MTW is approved only for machine tool connections and THHN is rated for dry and damp locations only (Table 310.4). Most single conductors now have multiple ratings, such as all three he mentions in the video so you can keep one reel in your truck for many applications.
@abrelectric
@abrelectric 9 ай бұрын
Thank you!!
@paulashley3732
@paulashley3732 Жыл бұрын
I bought you a cup of coffee! ☕. enjoy!
@leestokes6761
@leestokes6761 Жыл бұрын
Helpful information. I’m contemplating running wire from my outdoor service entrance to a free-standing shed, a straight-line distance of maybe 20’ . My preference is buried conduit rather than direct burial of Cale rated for such. 30-60 amps 120 volts is still a fair am of current for me to feel comfortable with direct burial.
@abrelectric
@abrelectric Жыл бұрын
I'm with you regarding conductors in conduit vs direct burial. And, direct burial requires a deeper trench :(
@DavidHalko
@DavidHalko Жыл бұрын
@@abrelectric how deep for direct burial? Can direct burial go directly into house & shed? or are 2x JBoxes required?
@abrelectric
@abrelectric Жыл бұрын
@DavidHalko 24" deep to top of the UF cable. You could go directly through the interior framing like Romex. It's just a bit more difficult to strip and more expensive.
@DavidHalko
@DavidHalko Жыл бұрын
@@abrelectric - I am wanting to dig a hole outside to place a battery box to hold lithium ion batteries for a whole house UPS… about 34.4kw of batteries… need low voltage 48v wires. (Not interested in li-ion being inside the house.) Since this is D/C, would thick direct burial cable or a large conduit be better? (250 amps @48v continuous is possible with the 12k inverter, would be a 6 foot run or so, maybe 10 foot.) Not sure what the code would be for such a beast.
@abrelectric
@abrelectric Жыл бұрын
@@DavidHalko normal stuff: all needs to be listed and approved for your application. I would go with conductors in conduit just for ease of replacement.
@mancave7
@mancave7 Жыл бұрын
Ok Gurus, DIY with simple scenario, need advice. 3 circuits, 15A max each 24ft run (panel to receptacle) Dry location, under a carport, 8 ft above ground Can 12/2 Romex be used in 1 1/2 PVC conduit?
@joseaguirre4169
@joseaguirre4169 Жыл бұрын
Thank you for your informative videos. In your example, wouldn't it be better to do the transition by installing the J-box indoors to insure that the NM romex never sees the outdoors?
@abrelectric
@abrelectric Жыл бұрын
And transition to a THW or MTW or UF conductor before outside? Yes, that would be a more complete solution.
@jaydee3046
@jaydee3046 10 ай бұрын
I can see your point for wet locations. Since inside conduit is not a wet location, can I run romex inside a gray pvc conduit along my garage ceiling? And if I drill holes in the conduit for heat dissapation, does it cease to be "conduit" and OK for protecting the romex? Suppose I do this inside the ceiling?
@abrelectric
@abrelectric 10 ай бұрын
If you're running romex inside of conduit inside (dry environment), just check the fill volume (i .e.12/2 romex cross sectional area vs that of 3/4" pvc pipe). Don't drill holes in it. That works against your overall goal of doing it right 😀
@pld8993
@pld8993 7 ай бұрын
There's no need for heat dissipation when romex is installed in conduit. It will never overheat simply because it's in conduit.
@williamrafferty6811
@williamrafferty6811 2 ай бұрын
So, THHN is good for damp locations?
@abrelectric
@abrelectric 2 ай бұрын
@@williamrafferty6811 because it is also typically rated THW or MTW.
@JohnThomas-lq5qp
@JohnThomas-lq5qp Жыл бұрын
Here's a curve ball: At an IAEI continuing education class the instructor told us that it's never legal to run Type MM ( Yea Romex ) outdoors even to feed a wall mounted luminare. Told us to only use UF cable. Reason being outdoors is considered at least a damp location & type NM cable was never approved for damp locations. Have received the AHJ approval in house basements to install maybe 3' of Romex thru a piece of 1/2" EMT that's secured to a painted 1 by 4' wood board to a 1900 box for one or two duplex receptacles. Here's a question why are you not allowed to say install a Romex connector into a 1/2" heavy wall coupling to make the transition from Romex to EMT ? And yes I have done that hundreds of times over the years and yes I know they make a one piece transition approved fitting but it's just more things to stock in an overloaded work van .
@abrelectric
@abrelectric Жыл бұрын
You work with your AHJ. I have similar challenges here. You adapt, and keep getting green tags
@JohnThomas-lq5qp
@JohnThomas-lq5qp Жыл бұрын
@@abrelectric Worst part Pa does not have a state electrical license and in some small hick towns the only electrical contractor issues the license and often fail job after your very qualified inspector passes the job.
@JeffBanfield-t6v
@JeffBanfield-t6v 9 ай бұрын
Your instructor may have misinterpreted the code. 334.10 - Uses permitted: Inside single, two family and multi-family buildings. The exterior outlet box that your exterior light secures to is installed inside the building and therefore compliant. There is nowhere in the code that tells us we must do what your instructor says.
@JohnThomas-lq5qp
@JohnThomas-lq5qp 9 ай бұрын
Had a hick town inspector call me up to tell me that I had 3 violations after my inspector passed the job. Told the hick inspector that if I had three legitimate violations that I would find another trade. First violation was because I spliced a #14 wire in a circuit breaker panel in order to reach the circuit breaker. Gave him the code article that allows it so he said that he would let me get away with it this one time. Other two violations were on company that installed an outdoor sign and ran power to it. Told him that was not on my permit and not performed by me.
@spacecoastkid5033
@spacecoastkid5033 5 ай бұрын
I need install a 50amp rv plug on the end of my house. My breaker panel is in the garage on the opposite end of the house. Would it be legal to run 6/3 Romex NM-B from the panel, into the attic, through the attic to the end of the house, then come out of the wall and on the exterior run inside comduit? It would terminate inside the 50amp receptacle panel at about 30" above ground? OR do I need a junction at the exterior and then change to the THHN or W wire and still run in conduit? I am not getting this inspected, so if all Romex is illegal, am I honestly ever going to have an issue as long as. the joints are glued properly?
@abrelectric
@abrelectric 5 ай бұрын
@spacecoastkid5033 Romex is illegal by Code in the outdoors (damp/wet locations). You're not really asking a Code question, right? You know that answer. Do what's right, and keep moving on.
@spacecoastkid5033
@spacecoastkid5033 5 ай бұрын
​@@abrelectricThank you!
@waylandjennings4073
@waylandjennings4073 Жыл бұрын
Does this apply exclusively to Southwire brand cable?
@abrelectric
@abrelectric Жыл бұрын
I don't know. They're the only manufacturer I looked up, because I was familiar with their wire.
@ElectricianMagician
@ElectricianMagician Жыл бұрын
No. It's code, no matter the manufacturer
@davidszakacs6888
@davidszakacs6888 Жыл бұрын
I'm getting ready to run a 240 volt 6/3 cable to a hot tub which will be on a deck. I want to use flexible Liquidtight one-inch conduit and fittings from just inside the basement, through the joist box, about 5 feet up to a spa pack w/GFCI then down under the deck to the spa, (about 6-7 feet). Is this allowable and do I have to keep the sheathing on the cable? Also, would one-inch diameter conduit be enough? Thanks. Enjoying your videos.
@abrelectric
@abrelectric Жыл бұрын
David, 1" is large enough for 6/3 romex. The technical issue is that the individual conductors inside the sheath are not outdoor or damp rated. So, taking off the sheath makes it easier to pull, but does not change the rating of the conductors. Ideally, you would transition to individual conductors rated MTW or THW or something with a W. Thanks for the question, and subscribe to the channel.
@admirableawesome2317
@admirableawesome2317 Жыл бұрын
great video!`
@abrelectric
@abrelectric Жыл бұрын
Thanks!
@scotttribout1150
@scotttribout1150 7 ай бұрын
Here's my issue. NM ROMEX is usually SOLID WIRE. Regardless of the sheeting of the individual wires it's gonna be hard to pull..... Even with a replacement insulated ground wire.
@abrelectric
@abrelectric 7 ай бұрын
I've seen a lot of jacked up romex, forced through conduit (usually water pipe with 90s:)
@pld8993
@pld8993 7 ай бұрын
Solid wire is frequently used in conduit but as individual conductors, and it's much easier to pull 3 solid #12s than a single 12-2 cable. You can legally pull romex through 500' of conduit, not a smart move though.
@meeponinthbit3466
@meeponinthbit3466 Жыл бұрын
Haven't watched the video yet, but if i recall, didn't this already get clarified in a previous video? If the insulation isn't marked, then it isn't allowed.... (Mostly just posting this to feed the algorithm)
@abrelectric
@abrelectric Жыл бұрын
You are absolutely right. But the questions kept coming, just in slightly different ways :)
@ryanb159
@ryanb159 Жыл бұрын
So if you have something like a generator inlet box mounted on stucco, are you able to directly run 8/3 (or 6/3) romex from the main panel to the inlet box without using a jbox since it’s mounted directly to the house?
@spacecoastkid5033
@spacecoastkid5033 5 ай бұрын
That's what I did... without permit! Maybe it would have failed inspection, but it will probably be there until I die! Lol It's been about 5yrs and I've had no issues with it.
@williamrafferty6811
@williamrafferty6811 2 ай бұрын
You’re showing THHN in a damp location
@abrelectric
@abrelectric 2 ай бұрын
@williamrafferty6811 yes, if you look at the labeling on the wire, it is also rated THHW, or MTW. The W being for wet locations. By practice, most electricians saying THHN, understand it to include the W ratings
@MrCbell57
@MrCbell57 Жыл бұрын
Don’t walk on wire or water.
Stripping Romex into Conduit- Bringing in the Sheaths
9:04
abrelectric
Рет қаралды 48 М.
Сестра обхитрила!
00:17
Victoria Portfolio
Рет қаралды 958 М.
How to treat Acne💉
00:31
ISSEI / いっせい
Рет қаралды 108 МЛН
Don’t Choose The Wrong Box 😱
00:41
Topper Guild
Рет қаралды 62 МЛН
99.9% IMPOSSIBLE
00:24
STORROR
Рет қаралды 31 МЛН
Dirty Secret about the New 2024 Romex Wire Colors
5:34
Silver Cymbal
Рет қаралды 290 М.
Did ROMEX Cable Change Again? (NM-B Update)
5:29
Backyard Maine
Рет қаралды 497 М.
Electrical Home Runs
7:37
Electric Pro Academy
Рет қаралды 95 М.
#1 DIY Electric Mistake - Can you use Romex Wire in Conduit?
3:44
Silver Cymbal
Рет қаралды 1,2 МЛН
ROMEX Cable Support Requirements (2024)
11:38
Backyard Maine
Рет қаралды 355 М.
#1 UNKNOWN Conduit and UF Cable Rule you Need to Know! Electricians In Action
8:46
How to Wrap Cables Like a Pro: Over/Under (Roadie Wrap) Method Explained!
14:59
Rattlesnake Cable Company
Рет қаралды 59 М.
Сестра обхитрила!
00:17
Victoria Portfolio
Рет қаралды 958 М.