Estimado Carlos excelente video y más por usar productos de la marca Balluff. Saludos!
@CarlosAbner2 жыл бұрын
Muchas gracias Marco, son pocos a los que tengo acceso pero trato de sacarle provecho, sobre todo al tema de IO Link...
@zezardjwordpresscom Жыл бұрын
hola te pudo pedir una consulta
@CarlosAbner Жыл бұрын
Si
@zezardjwordpresscom Жыл бұрын
Analog mode F0hex The mode of the input ports can be set with this ISDU register. Accessing the ISDU register through the subindex 0, the settings for all ports can be read/written. Accessing the ISDU register through subindex 1-8, the port mode for the corresponding port (P0-P7) can be read/written. 00hex = Voltage input, 0V - 10V 01hex = Current input, 4mA - 20 mA 02hex = Voltage input, 5V - 10V 03hex = Voltage input, -10V - 10V 04hex = Voltage input, 0V - 5V 05hex = Current input, 0mA - 20 mA 06hex = Voltage input, -5V - +5V 07hex = Pt100 08hex = Pt1000 09hex = Type J thermocouple 0Ahex = Type K thermocouple 0Bhex = Type C thermocouple* FFhex = Port is switched off *available from FW3.0 Subindex 0: Byte 0 1 2 3 4 5 6 7 Mode Port 0 Mode Port 1 Mode Port 2 Mode Port 3 Mode Port 4 Mode Port 5 Mode Port 6 Mode Port 7 index subindex y data cue valores serian los que pondria en el webserver para ponerlos en 4-20 ma
@zezardjwordpresscom Жыл бұрын
modelo BNI00AJ
@CarlosAbner Жыл бұрын
Mejor pon el modelo de tu equipo
@zezardjwordpresscom Жыл бұрын
Bni006a es el modelo del máster, BNI00AJ es el modelo del multiperto análogo , quiero cambiar el tipo de configuración de todos los puertos a 4-20ma
@zezardjwordpresscom Жыл бұрын
04hex según el manual, pero cuál es el Index y sub Index, y es por puerto, o todos los puertos
@CarlosAbner Жыл бұрын
@@zezardjwordpresscom Por lo que dice el manual, debes poner en write: Index:0XF0 SubIndex:0 Data:01 Como en el minuto 4:58