Heads up, 2 stage gas valves on carrier rtu have been failing alot lately 😕 midwest at least
@zekenzy64867 ай бұрын
Great Video. Thank you for sharing
@Brutis-19833 жыл бұрын
Hate when guy are too lazy to clean up their mess. Had a Carrier do the same thing with internal control fault. Replaced board. Day later same thing. Thinking bad board . Talked a guy at Mingledoffs , we buy Carrier units from them. Turned out the Effect switch was going pad. Showed me best way to check them. Glad I don’t have to work in the cold and snow much. Enjoy your videos.
@HughesManHVAC3 жыл бұрын
Awesome man! It just worked after I reset it. I'm gonna look into that for sure
@Jeff-Lawrence3 жыл бұрын
Curious, what’s an effect switch
@HughesManHVAC3 жыл бұрын
Proving switch on combustion blower
@evasmechanical39022 жыл бұрын
Brutish how do you check that effect switch?
@Brutis-19832 жыл бұрын
With power on unit with no call for heat unplug Hall effect switch. With your meter on DC scale. Connect negative lead to pin 3 and positive lead to pin one should read 7.5-10 volts DC. Move positive lead to pin two. Should read 21-24 volts. If not bad board. With plug plugged in connect negative lead to pin three and positive lead to pin one. Slowly rotate draft motor. On half a turn should read less than one volt DC. OTHER half of turn should read 6.5-9 volts DC. Then move positive lead to pin two. Should read 16.5-21 volts DC. If not replace Hall switch. Hope this helps
@forlast523111 ай бұрын
Check airflow. Some customers shut vents off in the building.
@EverythingHVACR3 жыл бұрын
Nice job man! Those retaining plates always go first.
@HughesManHVAC3 жыл бұрын
Thanks! Even new units start to get crispy after a year.
@NewEnglandReptile2 жыл бұрын
Thank you !!!
@gregbowman35983 жыл бұрын
Good one Ryan 👍
@HughesManHVAC3 жыл бұрын
Thanks Greg
@RichGT350r3 жыл бұрын
That’s a cold one brother! Thanks for sharing! 👍
@HughesManHVAC3 жыл бұрын
Thanks for watching Rich
@RichGT350r3 жыл бұрын
@@HughesManHVAC No worries Brother! I subbed as well, so I’m catching up on your videos! 👍
@kenbassett59423 жыл бұрын
Not only faulty hall sensor but a faulty gas valve causes 8 flashes. Most times it’s stage 2, pink wire on valve. Should have jumped W2.
@HughesManHVAC3 жыл бұрын
Good advice 👍 thanks
@dn821802 жыл бұрын
Just saw this and tech support said to change the gas valve. So far so good but it also worked for a few days after I changed the board. Also told me about the combustion fan. Said if you block the exhaust and it fires its the combustion motor hall effect sensor. He says the gas valve has a bridge rectifier in it that goes bad and it disables the board with 8 flash code. For something that appears to diagnose itself these are some pretty funky ways of failing. He says a lot of companies will just change the board, comb motor, and gas valve to ensure it's fixed.
@bobberger9183 жыл бұрын
Good idea to change p.s. and sensor with board low cost
@HughesManHVAC3 жыл бұрын
Thanks Bob!
@tedpert87863 жыл бұрын
Great video buddy keep up the good work!
@HughesManHVAC3 жыл бұрын
Thanks man!
@turbolag98 Жыл бұрын
I’ve come across 2 GrandAire RTU’s new installs throwing different error codes like internal control fault, pressure switch fault, high limit fault, rollout fault. What’s going on? Anyone have experience
@tedhicks54312 жыл бұрын
We have 2 identical units big 16s code 8 wouldn't reset after several trys replace LGC board like book said still code error 8 whats up anyone
@sknight03913 жыл бұрын
Intrnal lockout board code fault applejack cinnamon toast. That's definitely a bad canooter valve. Write it up 😎👍
@HughesManHVAC3 жыл бұрын
Lol, you want to do a livestream with me sometime? I think I would be hilarious 🤣