What should be the design criteria for multi-sensor detector
@pritoventure33842 ай бұрын
Upon applying standard formula of R=.7Sd , Fig.1 & Fig.2 will have the same measurement of 21Ft. I'm open to learn if I got wrong.
@irfancfps2 ай бұрын
Can any one reply to his query?
@harisahmad17336 ай бұрын
When will you upload next video? I have been waiting for a long time
@irfancfps6 ай бұрын
I was focusing on nfpa20. Sure I will post second part of this smoke detector rules very soon.
@reniz4u3 ай бұрын
@@irfancfps Waiting
@SaraDubamo5 ай бұрын
thank you sir for you uploading this video. and now sir pls upload a video which show us the practical Example how to place HD,SD HORNS and other in the building. and how to make fire alarm riser diagram for each floor and zone classification in English
@irfancfps5 ай бұрын
Sure. Very soon. Thanks
@SaraDubamo5 ай бұрын
@@irfancfps thank you sir
@tariqulislam63412 ай бұрын
Pls upload another video. Topic about smoke Heat and Multi detector installation location .
@irfancfps2 ай бұрын
Sure. Apologies for late response.
@mariomabaga20149 ай бұрын
Thanks sir for this
@irfancfps9 ай бұрын
Most welcome
@md.zahidkhan56906 ай бұрын
How can I talk to you Boss.
@EzliePerez6 ай бұрын
R = 21' x = 30' y = 30' ?? = 15'
@irfancfps6 ай бұрын
Nice!
@alirfan51658 ай бұрын
X=30ft Y=30ft R=15ft
@irfancfps8 ай бұрын
U are correct. However, please check there are 3 questions in the video. please verify once again and put your answers in comment section. I will wait for you.
@mohammedhaneef5297 ай бұрын
@@irfancfps R is not 15ft. Its is 21ft
@adnaniqbal3610Ай бұрын
@@mohammedhaneef529correct r is 21ft and x and y is 15 ft