This video contains information regarding the engineering concept behind the ESFR sprinklers. • Concept behind fire sp... • How Water Control the ...
Пікірлер: 29
@anindian46013 жыл бұрын
mashah alla bro, u r very GOOD Teacher, i understood clearly after watch ur video, please do more such videos bro
@sprinklerdesigner34363 жыл бұрын
Tq very much.This is the honor for my work
@Satishkumar-lm1sm3 жыл бұрын
good sprinkler
@tauseefshaikh50633 жыл бұрын
Please make one video in brief, the difference between ESFR and ELO Sprinkler.... And classification of both with Calculation
@sprinklerdesigner34363 жыл бұрын
Tq for response.Sure bro I will do it
@md.mominulislam64562 жыл бұрын
if ceiling height is 20 feet then possible to protect rack storage by only ESFR ceiling sprinkler
@sprinklerdesigner34362 жыл бұрын
Good question, Proposal of warehouse protection contains many things. Moreover Concept Rack storage sprinkler are kind of addition sprinklers caused by obstruction In accordance fire protection handbook (you can imagine additional sprinkler provided under duct width exceeded 1.2 meter)
@sprinklerdesigner34362 жыл бұрын
However ceiling sprinklers are always preliminary .We could not skip
@Satishkumar-lm1sm3 жыл бұрын
Good video
@sprinklerdesigner34363 жыл бұрын
Tq very much
@rajesh_psgM3 жыл бұрын
Thanks for the video.What is the major difference between CDMA and ESFR sprinklers.
@naingoo13443 жыл бұрын
Thanks for sharing your knowledge here. Do you have any design information about how to design for In-Rack Sprinkler system (Using Pre-Action system/ ESFR/ Deluge system) under warehouse/coldroom/factory using racking system ? If yes, please do help & share to us. Have a good day 👍🏽🙏
@sprinklerdesigner34363 жыл бұрын
Tq for yr response.Yes I can design warehouse sprinkler system but do need for particular projects or general design informations
@naingoo13443 жыл бұрын
@@sprinklerdesigner3436 general design idea concepts for similar projects
@justinmyname7734 Жыл бұрын
What is the diff of esfr and qr sprinkler?
@surasamkaravelkumar50554 жыл бұрын
Good work... Keep going sir.
@sprinklerdesigner34364 жыл бұрын
Thanks for yr support 😊😊
@erdhananjaypathe1344 жыл бұрын
Please make a detailed video on how to calculate and design a MVWS system
@sprinklerdesigner34364 жыл бұрын
Thanks for your comment bro. MVWS for which occupancy you want ex:fuel storage tanks ,Tunnels
@erdhananjaypathe1344 жыл бұрын
@@sprinklerdesigner3436 for cable gallery
@sprinklerdesigner34364 жыл бұрын
Noted.ASAP I will release
@erdhananjaypathe1344 жыл бұрын
@@sprinklerdesigner3436 thanks will be waiting 🙏
@sasitharan47203 жыл бұрын
Could you make video for conventional system and addressable system ?
@sprinklerdesigner34363 жыл бұрын
Tq for yr comment.Sure
@pravinjohnsonj27253 жыл бұрын
What is the minimum ceiling height for providing esfr sprinkler ?
@sprinklerdesigner34363 жыл бұрын
Tq for yr question brother.NFPA 13 didn’t restrict minimum height; you can provide 3 m ceiling height also;technically nothing wrong but cost optimization wise it will increase the budget due the pump capacity.However decision of providing ESFR sprinkler subject some other factors also like commodify classification, storage arrangements etc...
@pravinjohnsonj27253 жыл бұрын
K Thank u . But this 3 m ceiling height commercial and residential. I ask to warehouse area
@pravinjohnsonj27253 жыл бұрын
Because wharehouse area ceiling height is normaly hight ( above 3 m). So how to choose wharehouse area sprinkler.
@sprinklerdesigner34363 жыл бұрын
Bro that 3 m I have mentioned indicative only (example purpose) don’t stick with the value.Finally your question is “how to choose the type of sprinkler for warehouse protection” in order to get the answer for these question you need fill some checklist it contains ; 1.commodity classification 2.storage arrangement ( rack or non rack)3.packing methods 4.ceiling height 5.storage height 6. Clearance from storage to ceiling etc.. In addition there are 3 type of sprinklers available for warehouse protection 1. CMDA (control mode design area) 2.CMSA (Control mode specific application)3.ESFR (. Early suppression fast response) .Further you have any queries don’t hesitate contact me.Tq very much for yr support.