The compressor we repaired We check the warranty conditions We check the working conditions of the compressor Suction pressure - Discharge pressure The amount of superheat is 20 degrees The amount of subcool is 4 degrees Suction increased 56 Suction Discharge 254 Meanwhile Look at superheat Superheat is coming down Subcool On the other hand, it has a discharge pressure goes up Superhit is coming Down Suction pressure 68-276 Superheat is coming down and recovering . 282 283 We want to see something together Our pressure went up to the nearest 290 The condenser fan turned on You can see that the discharge pressure is going down This side of Superhit is going up With the lowering of the discharge pressure The superheat is rising The suction pressure reached 38 In our old chillers, we have a problem when the fan settings when the weather is relatively cool, the suffering of pressure changes is very high, unfortunately, this problem exists here You can see the fluctuation of suction pressure What happens like this oil escape? The oil escape from the compressor and the oil foams when the oil escapes the oil inside the evaporator coil It accumulates, the efficiency of the evaporator also decreases, on the other hand, the suction pressure drops more. The problem next that the compressor is not well lubricating.