Directional Earthfault Operating Region | Working of Directional Earth fault

  Рет қаралды 21,221

Barani Tech

Barani Tech

Күн бұрын

Пікірлер: 58
@TheMandardange2011
@TheMandardange2011 2 күн бұрын
Sirji thank you for your valuable information
@sureshpadhy2243
@sureshpadhy2243 3 жыл бұрын
Excellent explanation... But I have some doubts... Please clarify 1.You have presented three videos about directional relay. Where to use self polarised, cross polarised and residual voltage method. All are showing different tripping region. 2. In self polarised method you have rotated clockwise to draw MTL. In cross polarisation method you have rotated the phasor clockwise to draw MTL. In residual method again you have rotated the phasor clockwise to draw MTL. 3. In relays only RCA and PU values settings implemented. So how to find out tripping regions for relay testing. Please explain.. Thank you
@baranitech1026
@baranitech1026 3 жыл бұрын
1. for earthfault the direction earthfault is different then overcurrent. 2.same in earthfault the residual voltage direction change so it different form overcurrent 3.in numerical relay has both self and cross polarised method some relay we have to choose. if not they will have only one polarised method. this can be seen in manual of the relay.
@baranitech1026
@baranitech1026 3 жыл бұрын
for direction earthfaul i will check once again
@karamhusenkhan2201
@karamhusenkhan2201 3 жыл бұрын
Very nice explanation.. Thanks you so much for such a nice tutorial which I was looking for....
@baranitech1026
@baranitech1026 3 жыл бұрын
You are most welcome
@HaNPT-HTD
@HaNPT-HTD 2 жыл бұрын
at 4:30s in your video, as previous calculation V0 is 60 degrees and I0 is 180 degrees for fault of L2-ground but your diagram is they are 60 degrees same? Can you explain for me, thanks.
@rekhasatheeshkumar6767
@rekhasatheeshkumar6767 3 жыл бұрын
Sir,Thanks a lot for clear explanation one doubt I have as per explanation R-phase to E/F in forward case V reference you took opposite to Vr same way reverse explanation 180 opposite you took that is in phase with Vr up to that it was clear . But in Y to E/F and B to E/F direction is mentioned in the drawing reverse but the fault is not in phase direction with corresponding phases so that as per my understanding it’s forward direction diagram if I wrong please explain sir.
@baranitech1026
@baranitech1026 3 жыл бұрын
yes your correct. i have made for forward only for Y and B .
@zeeshankhaliq2593
@zeeshankhaliq2593 Жыл бұрын
Nice & clear explanation, however, I have doubts in the Io calculations as below: when I1 = 2.8 L 0 degree I2 = 1 L 240 degree I3 = 1 L120 degree Io should be = 0.60 L 0 degree whereas you calculated 0.6 L180 degree also there is difference when I calculate Io for faults on I2 and I3 Please explain your calculation? Thanks
@baranitech1026
@baranitech1026 Жыл бұрын
I WILL MAKE CLEAR VIDEO AGAIN
@karsjoan
@karsjoan 2 жыл бұрын
For Earth fault always RCA should be in Negative. But you mentioned +40. What is the reason?
@baranitech1026
@baranitech1026 2 жыл бұрын
its depends on power in and out .
@Mumbaindianzzzzz
@Mumbaindianzzzzz 3 жыл бұрын
For r phase you considered vref at 0 & 180 degree..... For y and b phase what are the angle for v ref to be considered
@baranitech1026
@baranitech1026 3 жыл бұрын
for y is 110 to 290 and for b its 170 to 350 . this i have show at the end of the video
@Mumbaindianzzzzz
@Mumbaindianzzzzz 3 жыл бұрын
@@baranitech1026 how?
@baranitech1026
@baranitech1026 3 жыл бұрын
@@Mumbaindianzzzzz Please see at the end of the video i have shown
@SantoshKumar-nk5ve
@SantoshKumar-nk5ve 3 жыл бұрын
Sir, if RCA angle is -45 degree then MTA should be anticlock wise direction from Vref or same clockwise??
@baranitech1026
@baranitech1026 3 жыл бұрын
yes it should be in anticlock wise direction
@flyhighwithyourdreams.2132
@flyhighwithyourdreams.2132 Жыл бұрын
@@baranitech1026 @SantoshKumar-nk5ve sir this angle (RCA) depends upon Network earthing like compensated, isolated & Solidly earthing. Here Isolated depends upon capacitance charging current when fault accrued (that is taken RCA - 90 deg lag). Compensated depends upon Capacitance & Inductance (that is RCA - 0 deg). Solidly earthing inbetween 0-90 deg). I hope this is correct & if wrong kindly clear me.
@kaisalvi7850
@kaisalvi7850 2 жыл бұрын
Please share Hindi language too but your explanation very good best wishes
@baranitech1026
@baranitech1026 2 жыл бұрын
i will try in future
@companyalleyan649
@companyalleyan649 Жыл бұрын
thank you very for these details
@baranitech1026
@baranitech1026 Жыл бұрын
welcome lot
@sagormohammad349
@sagormohammad349 2 жыл бұрын
RCA = 40 degree. Why we not draw in anti clock wise direction As a reference of Vref
@baranitech1026
@baranitech1026 2 жыл бұрын
it will change region
@By-ss4ss
@By-ss4ss 2 жыл бұрын
thank you very much
@baranitech1026
@baranitech1026 2 жыл бұрын
You are welcome
@madhuvimal88
@madhuvimal88 2 жыл бұрын
Brother... RCA angle settings how to deside.. Wether its 45 60 40...dgree, its related with earthing system... Ungrounded grounded or resistance earthing how we choose exactly... Particular angle.. Kindly make clarify... Rest of this doubts... I got some idea's from... Above videos thanks
@baranitech1026
@baranitech1026 2 жыл бұрын
i don't know how to set RCA angle its design related. if i came to know i will share bro.
@madhuvimal88
@madhuvimal88 2 жыл бұрын
@@baranitech1026 sure.. Thanks... Barani brother... Your doing such amazing work... I learnt lot of concept from you.. Thanks.
@ISLAMASIF56
@ISLAMASIF56 2 жыл бұрын
Sir please explain the relay neutral coil polarity change effect on the zone. Even phase coil polarity change effect details.
@baranitech1026
@baranitech1026 2 жыл бұрын
i will try to make
@abudhakir9403
@abudhakir9403 3 жыл бұрын
Thank you
@baranitech1026
@baranitech1026 3 жыл бұрын
You're welcome
@saju121
@saju121 8 ай бұрын
Can you make one video for cos theetta polarisation method
@baranitech1026
@baranitech1026 6 ай бұрын
i will try thank you
@gunpowder98
@gunpowder98 Жыл бұрын
How did you get the RCA angle?
@baranitech1026
@baranitech1026 Жыл бұрын
for calculation i have take random value
@HR-rp8pc
@HR-rp8pc 3 жыл бұрын
Thanks sir
@baranitech1026
@baranitech1026 3 жыл бұрын
Welcome
@venkateshkumar4827
@venkateshkumar4827 2 жыл бұрын
Io, Vo calculation for all cases, not getting correct
@baranitech1026
@baranitech1026 2 жыл бұрын
i will check
@velusamypothiraj2300
@velusamypothiraj2300 Жыл бұрын
Case 2 calculation explain with calculator, and earth fault for rphase operating region is confusion
@baranitech1026
@baranitech1026 Жыл бұрын
earth fault i will try to make one more video
@madhivanan8115
@madhivanan8115 3 жыл бұрын
Bro generator protection relay full testing video poduga
@baranitech1026
@baranitech1026 3 жыл бұрын
Will do soon bro
3 жыл бұрын
mta 40 or -40 ?
@baranitech1026
@baranitech1026 3 жыл бұрын
40
@刘建伟-u3v
@刘建伟-u3v 2 жыл бұрын
During test the DEFLLPDEF 67n on the ABB REF615 relay, I make the same setting as u motioned on the video ,but it is not tripping in the operation region .I am confused ,can You show the full settings for the earth fault, thank you
@刘建伟-u3v
@刘建伟-u3v 2 жыл бұрын
Mentioned
@baranitech1026
@baranitech1026 2 жыл бұрын
i will make for ABB relay testing for directional earthfault
@companyalleyan649
@companyalleyan649 Жыл бұрын
if you still need support for REF615 I am ready
@Y0Giiii
@Y0Giiii 11 ай бұрын
Bro directional earth fault tamil solluga bro
@baranitech1026
@baranitech1026 10 ай бұрын
kzbin.info/www/bejne/hmXTmmlqjJuid8k
@Y0Giiii
@Y0Giiii 10 ай бұрын
@@baranitech1026நன்றி சகோ
Restricted Earth Fault Protection Basic information
3:14
Barani Tech
Рет қаралды 6 М.
Это было очень близко...
00:10
Аришнев
Рет қаралды 6 МЛН
Who’s the Real Dad Doll Squid? Can You Guess in 60 Seconds? | Roblox 3D
00:34
Help Me Celebrate! 😍🙏
00:35
Alan Chikin Chow
Рет қаралды 90 МЛН
Sigma baby, you've conquered soap! 😲😮‍💨 LeoNata family #shorts
00:37
Directional and Non Directional Earth Fault Relay
13:23
RELAY PROTECTION ELECTRICAL
Рет қаралды 8 М.
IDMT Over Current/ Earth Fault Relay Operating Time Calculation App
18:41
Directional Earth Fault Relay for Transmission Line
10:39
RELAY PROTECTION ELECTRICAL
Рет қаралды 8 М.
Directional Over current relay|Protection of parallel lines|Directional over current protection
8:24
ELECTRICAL TECHNOLOGY and INDUSTRIAL PRACTICE
Рет қаралды 55 М.
Directional Relay Setting|How direction is detected|PART-3|BASIC OF DIRECTIONAL RELAY SETTING
7:16
ELECTRICAL TECHNOLOGY and INDUSTRIAL PRACTICE
Рет қаралды 18 М.
DIRECTIONAL OVER CURRENT RELAY WORKING PRINCIPLE|DIRECTIONAL RELAY SETTING|PROTECTION
13:46
ELECTRICAL TECHNOLOGY and INDUSTRIAL PRACTICE
Рет қаралды 48 М.
Это было очень близко...
00:10
Аришнев
Рет қаралды 6 МЛН