Restricted Earth Fault Protection working | REF relay working principle | REF relay working Part-1

  Рет қаралды 44,671

Barani Tech

Barani Tech

3 жыл бұрын

Restricted Earth Fault Protection working
the working of REF high impedance protection
Definition for REF
Restricted earth fault protection is a sensitive way to protect a zone between two measuring points against earth faults.
zone present in REF protection
i) inzone
ii)outzone
#REF #REFworking

Пікірлер: 76
@ranjansahu2362
@ranjansahu2362 3 жыл бұрын
Much needed sir... Great explanation.. thank you sir
@baranitech1026
@baranitech1026 3 жыл бұрын
Always welcome
@thulasiram5156
@thulasiram5156 3 жыл бұрын
Very well explanation thanks Anna.
@mohammadpathan4668
@mohammadpathan4668 3 жыл бұрын
Well explained !
@himanshu2232
@himanshu2232 3 жыл бұрын
Thanks sir such a good vedio
@ImranKhan-ht1wp
@ImranKhan-ht1wp 3 жыл бұрын
Super job ana
@sanjayakumarpatel775
@sanjayakumarpatel775 3 жыл бұрын
Nice video sir.very informative and clear video.
@baranitech1026
@baranitech1026 3 жыл бұрын
Thanks and welcome
@softurial8123
@softurial8123 3 жыл бұрын
Please make video on SKE11 synch check relay, slip frequency test. Keep it up...
@daleshwarpatel4789
@daleshwarpatel4789 3 жыл бұрын
Thank you sir
@nikashbabu1860
@nikashbabu1860 3 жыл бұрын
Good
@surendrakverma555
@surendrakverma555 2 жыл бұрын
Very good. Thanks 🙏🙏🙏🙏🙏
@baranitech1026
@baranitech1026 2 жыл бұрын
you are welcome
@samySan-yj8hp
@samySan-yj8hp 2 ай бұрын
ஹாய் ப்ரோ சூப்பர்
@baranitech1026
@baranitech1026 Ай бұрын
most welcome
@mohamedtaleb6113
@mohamedtaleb6113 3 жыл бұрын
Many thanks.
@baranitech1026
@baranitech1026 3 жыл бұрын
You are welcome!
@badshahibrahim8475
@badshahibrahim8475 2 жыл бұрын
Thank for it 👍🏻👍🏻👍🏻👍🏻
@baranitech1026
@baranitech1026 2 жыл бұрын
You're welcome 😊
@insinsat3723
@insinsat3723 2 жыл бұрын
I am shorting r phase with respective to earth for ref stability in primary method and how much current will flow in primary and secondary of transformer is there any calculation for that
@baranitech1026
@baranitech1026 Жыл бұрын
please follow transformer stability primary injection
@mohamedtaleb6113
@mohamedtaleb6113 3 жыл бұрын
I am waiting your next videos'
@baranitech1026
@baranitech1026 3 жыл бұрын
soon i am going to upload
@ganeshachally4881
@ganeshachally4881 3 жыл бұрын
Sir is that REF protection and sensitive earth fault one and the same or what please
@baranitech1026
@baranitech1026 3 жыл бұрын
both are different
@Munaam1989
@Munaam1989 2 жыл бұрын
ABB relays: REM= Relay for Electrical Machine (Motor or Generator) RET= Relay for Electrical Transformer REF=Relay for Electrical Feeder RED=Relay for Electrical Differential REL=Relay for Line (Distance Protection) Rex= basic protection NOC/NEF
@baranitech1026
@baranitech1026 2 жыл бұрын
REM is mainly used for motor and REG is mainly used for generator
@ritesh8353
@ritesh8353 2 жыл бұрын
Pls understand for PT selection for double bus bar single breaker
@baranitech1026
@baranitech1026 2 жыл бұрын
Earth fault will not created
@sanjayakumarpatel775
@sanjayakumarpatel775 3 жыл бұрын
Sir please prepare a video regarding differential protection
@sanjayakumarpatel775
@sanjayakumarpatel775 3 жыл бұрын
Also about the motor protection testing on Micom P242
@baranitech1026
@baranitech1026 3 жыл бұрын
kzbin.info/www/bejne/rqqQdqmmhNmsoNE
@sanjayakumarpatel775
@sanjayakumarpatel775 3 жыл бұрын
@@baranitech1026 thank you sir
@muhamedmuneer4540
@muhamedmuneer4540 3 жыл бұрын
6:24 what is reason for B phase Ct providing high impedence to flow of nutrel ct fault current?already B phase load current 1A flowing through B phase.then at the time of fault current cant to flow through B phase ct?kindly explain sir
@baranitech1026
@baranitech1026 3 жыл бұрын
it is the node of all three phase R, Y and B . not only for B phase CT
@baranitech1026
@baranitech1026 3 жыл бұрын
no current out form Core balance CT so neutral CT current not able to enter
@DesiMusafir1
@DesiMusafir1 3 жыл бұрын
Please do a video on NGR@Barani Tech
@baranitech1026
@baranitech1026 3 жыл бұрын
yes
@DesiMusafir1
@DesiMusafir1 3 жыл бұрын
Please do a video on NGR
@baranitech1026
@baranitech1026 3 жыл бұрын
Surely I make video on NGR
@ganeshnale6153
@ganeshnale6153 Жыл бұрын
in second case R phase current will be zero?
@baranitech1026
@baranitech1026 Жыл бұрын
IF ITS FULLY SHORT THEN IT WILL BE ZERO, IF ITS HAVE RESITIVE LEAKAGE CURRENT THEN IT WILL TAKE LOAD CURRENT ALSO.
@tahajerroundi4606
@tahajerroundi4606 Жыл бұрын
hello please what software tool do you use for drawing these schemes
@baranitech1026
@baranitech1026 Жыл бұрын
only ppt
@srva3907
@srva3907 10 ай бұрын
Case1 current flow of neutral current is showing incorrect in flowing red dot animation.
@baranitech1026
@baranitech1026 9 ай бұрын
according to P1 and P2 the current flow on CT secondary. Thank you.
@sharehbutt7947
@sharehbutt7947 2 жыл бұрын
Can you do a case study: when one phase is fully loaded, other two half loaded, EF in one winding & same current passes through N CT as in fully loaded phase but half of this passes through other two phases?? Thanks in advance
@baranitech1026
@baranitech1026 2 жыл бұрын
yes i will make later for you
@sibingeorge685
@sibingeorge685 6 ай бұрын
What is core balance ct
@baranitech1026
@baranitech1026 4 ай бұрын
sum of all phase
@hussainamjad9443
@hussainamjad9443 2 жыл бұрын
Good info : question - what will happen to REF if CT of faulty phase becomes saturated during through fault condition ?
@baranitech1026
@baranitech1026 2 жыл бұрын
before it get saturation relay has to give trip .
@manojtkd01
@manojtkd01 Жыл бұрын
In saturated condition neutral secondary current shall flow through phase CT due to minimum impedence ...
@rajeshkumarjack6056
@rajeshkumarjack6056 2 жыл бұрын
hi , how to calculate in current for ex: I1+I2+I3=0 (1.5+1+1= 0.5) explain plz
@baranitech1026
@baranitech1026 2 жыл бұрын
i1
@rasersk1691
@rasersk1691 2 жыл бұрын
Convert from polar to rectangular form, that way it'll be easier to understand.
@victormahadev7158
@victormahadev7158 Жыл бұрын
@@baranitech1026 brother please explain below thing If we take angle for (1.5+1+1=0 .5) 1.5 sin 0° + 1 sin 240° + 1 sin 120°= 0 .5 sin 0° = 1.5 (0) + 1 sin (-3/2) + 1 sin (3/2) = 0.5(0) Then value wil come 0 - 0.866 + 0.866 = 0 Total value is 0 Please clarify my doubts sir
@victormahadev7158
@victormahadev7158 Жыл бұрын
Case 2 : As per your video ,Neutral Ct secondary current will choose low resistance path & it will make the relay trip . Same scenerio if we consider for case 1 How the neutral secondary current will flow in core balanced side since its a high impedence path . Please clarify sir..
@baranitech1026
@baranitech1026 Жыл бұрын
if flow of the current in same direction then it will have low resistance path.
@vijaysenthilkumar2761
@vijaysenthilkumar2761 Жыл бұрын
In first case the fault current is able to travel the high impedance path whereas in second case it chooses low impedance path? Can you please explain the difference... Meaning the first case has 1 amp total fault current which chooses high impedance path whereas 0.5 amps chooses low impedance path... Pleassexplain
@baranitech1026
@baranitech1026 Жыл бұрын
if the flow in same direction it can able to flow easily
@akhilsm6840
@akhilsm6840 2 жыл бұрын
What happens if no fault happened and load is unbalanced , will the relay trip
@baranitech1026
@baranitech1026 2 жыл бұрын
no it will not trip unbalance current and NCT current get balanced
@akhilsm6840
@akhilsm6840 2 жыл бұрын
But unbalance current will not pass through transformer neutral CT right?
@akhilsm6840
@akhilsm6840 2 жыл бұрын
Only fault current can pass through the neutral point CT
@baranitech1026
@baranitech1026 2 жыл бұрын
@@akhilsm6840 without help of neutral line the star connection cann't able to take unbalance current
@akhilsm6840
@akhilsm6840 2 жыл бұрын
U meant to say then total 5 CT will be required for 3 phase 4 wire system am I right sir
@archive9994
@archive9994 3 жыл бұрын
Hindi
@mdshahidali80
@mdshahidali80 2 жыл бұрын
Pop up notes on display is obstructed the image of diagram. Due to which , I am not able to understand properly. So I request you sir to please avoid displaying the notes on display .
@baranitech1026
@baranitech1026 2 жыл бұрын
okay i will avoid
@muthuraman6093
@muthuraman6093 Жыл бұрын
Don't hide all by subtitles
@baranitech1026
@baranitech1026 Жыл бұрын
i try to reduce subtitle sizes small
Difference between High Impedance REF Protection and Low Impedance REF Protection Relay
9:31
Nastya and SeanDoesMagic
00:16
Nastya
Рет қаралды 44 МЛН
Mama vs Son vs Daddy 😭🤣
00:13
DADDYSON SHOW
Рет қаралды 51 МЛН
Получилось у Миланы?😂
00:13
ХАБИБ
Рет қаралды 6 МЛН
Mom's Unique Approach to Teaching Kids Hygiene #shorts
00:16
Fabiosa Stories
Рет қаралды 39 МЛН
Restricted Earth Fault Protection|REF relay working principle
11:56
ELECTRICAL TECHNOLOGY and INDUSTRIAL PRACTICE
Рет қаралды 140 М.
Directional Over current relay|Protection of parallel lines|Directional over current protection
8:24
ELECTRICAL TECHNOLOGY and INDUSTRIAL PRACTICE
Рет қаралды 54 М.
Differential, REF and SEF protection of transformer.
12:05
Gyaan ELECTRICAL
Рет қаралды 45 М.
LOW IMPEDANCE RESTRICTED EARTH FAULT(REF) PROTECTION
11:10
RELAY PROTECTION ELECTRICAL
Рет қаралды 5 М.
REF STABILITY TEST & Value of Stabilizing Resistor (Transformer Testing)
8:21
RELAY PROTECTION ELECTRICAL
Рет қаралды 14 М.
Restricted Earth Fault Protection | Restricted Earth Fault Relay | Hindi
13:46
Electrical With Abhishek Joshi
Рет қаралды 108 М.
Transformer stability test
14:06
Barani Tech
Рет қаралды 36 М.
Nastya and SeanDoesMagic
00:16
Nastya
Рет қаралды 44 МЛН