Dishwasher and Disposal on same circuit? NEC 210.23 says...probably.

  Рет қаралды 68,703

Ryan Jackson

Ryan Jackson

Күн бұрын

Пікірлер: 203
@zabizeyaee8002
@zabizeyaee8002 2 жыл бұрын
Ryan, I can't believe you are not getting more views. Your explanation is one of the best that I have seen.
@victorpoliashov2467
@victorpoliashov2467 2 жыл бұрын
I agree. The content on here is mind blowing
@pjmcinnis1188
@pjmcinnis1188 2 жыл бұрын
I agree he is the best on KZbin
@wim0104
@wim0104 2 жыл бұрын
He's written books too! They are used and sold by the IEC (comprehensive guide to the NEC)
@patrickg7569
@patrickg7569 2 жыл бұрын
If only KZbin recognized quality of information given by an educated person. He definitely knows his stuff 👍🏻
@JFlywheel
@JFlywheel 2 жыл бұрын
Yep, Just subscribed!
@buckhunter4413
@buckhunter4413 2 жыл бұрын
Ryan Jackson, I do want you to know every video you put out is Valuable. We can all learn code by studying but you add some extra support and info. Much Appreciated and God Bless!
@electricianron_New_Jersey
@electricianron_New_Jersey 2 жыл бұрын
I know I’m not the only one driving home and listening in the work truck. Good video Ryan.
@JesusCruz-wt2zp
@JesusCruz-wt2zp 2 жыл бұрын
Hello .. just want to say thank you, passed my test today.. and your videos helpped me a lot.. dont stop DOING THIS videos . thanks
@bobb.6393
@bobb.6393 6 ай бұрын
What test
@TexasEngineer
@TexasEngineer 4 ай бұрын
Thanks for the three hour rule explanation for continuous operation. I upgraded my built in non-plugged electric furnace air handler to a 5 ton from a 3.5 ton and it had a 100 amp breaker. We put a current meter on it and it read 82 amps on high. It is a 2 speed, 42/82 amps. The 2 amps is for the blower motor. We were uncertain about the definition of continuous load until I watched your video. The heater will never be on high for three straight hours.
@Roommate625
@Roommate625 2 жыл бұрын
Ryan, your videos are always well thought out and informative. Thank you for sharing your knowledge!
@FinchNygard-ff2yc
@FinchNygard-ff2yc Жыл бұрын
Great video, I just went through the stuff when a customer asked to add a disposal to their island sink. They had a dedicated disposal at their main kitchen sink. I couldn't find a reason why you would need to pull a new circuit when the original could handle both loads
@everythinghomerepair1747
@everythinghomerepair1747 2 жыл бұрын
This was such a clear explanation to a problem that people have a lot of disagreements over. Thanks.
@Jonacarpenter
@Jonacarpenter 4 ай бұрын
This was by far one of the best 'code reviews' and descriptions, that isn't just a 'yes / no' but a good reading of it and a 'human' explanation that you can follow with out questioning you Ryan, it allows the viewer to say "Ahhhh I got you, and I understand" rather then the yes/no stuff. Thanks, now with a few screen shots I can tell other friends info..... we were chatting about it the other day because of a situation exactly the dishwasher and garbage disposer (👍) is each on their own 20 amp circuit, and they aren't even on the same tandem breaker. 😳 They are on 2 completely different tandem breakers 6A and 8A and the B's on each are 'spares'..... WTH????? So thanks for this and I shall be looking at more from you.👍
@MasterTheNEC
@MasterTheNEC 2 жыл бұрын
Well Done as Usual. The key is the branch circuit ONLY supplies the Dishwasher and Disposal and nothing else, such as lighting or plug and cord connected utilization equipment. Once it does then 210.23(A) through (D) kicks in...Well Explained as Usual Ryan.
@dmh8329
@dmh8329 2 жыл бұрын
Ryan should come on the podcast Paul.🧐
@MasterTheNEC
@MasterTheNEC 2 жыл бұрын
I would LOVE to have Ryan on an episode of Coffee Hour. He brings amazing insights, and knowledge to our electrical industry. Huge supporter of Ryan and what he does. Sadly It's been hard to do any videos or podcasts lately as the Academy has me swamped but I think Ryan and myself will hook up eventually.
@RyanJacksonElectrical
@RyanJacksonElectrical 2 жыл бұрын
@@MasterTheNEC Just let me know Paul, I'll be there!
@MasterTheNEC
@MasterTheNEC 2 жыл бұрын
You got it Fella....Keep Being Excellent!
@marcosmota1094
@marcosmota1094 2 жыл бұрын
KZbin and you are mind readers...I'm examining our circuits after a breaker box rebuild and this is just what I needed to hear. Complete algorithm suggested.
@ericsullivan9725
@ericsullivan9725 2 жыл бұрын
This has been a long question ive been asking myself. Glad to have such clear clarification
@edwardmccormick7852
@edwardmccormick7852 9 ай бұрын
In my opinion, think it’s a good practice to always run a Multi wire or two separate circuits for the DW & Disposal, especially in new construction and major remodeling. This video really provides the rationale, both the DW and disposal are fixed, but are also replaced / upgraded over the years. Two circuits will protect the option to upgrade, without having to rewire @ some point in the future. However, for homes with one circuit this video makes it perfectly clear what you can do.
@Krunch2020
@Krunch2020 8 ай бұрын
Modern appliances use less energy. No need for two circuits.
@davidgiron9671
@davidgiron9671 Ай бұрын
Very good breakdown of this area of the code!
@floyd7396
@floyd7396 Жыл бұрын
You’re awesome Ryan. Thanks for taking the time💯
@alhawkins3376
@alhawkins3376 Жыл бұрын
Like the way you explain, got most of the basic rules yet still thoughly confused, I subscribed for more.
@luckyhiker3434
@luckyhiker3434 2 жыл бұрын
Ryan, so very excellent! All was relevant but I especially loved the pups at the end.
@brentgill6981
@brentgill6981 10 ай бұрын
Excellent content! It was Mike Holt suggesting the three way switch. 😀I’m studying for my Washington masters exam and was going thru my Mike Holt dvds on this section yesterday.
@RyanJacksonElectrical
@RyanJacksonElectrical 10 ай бұрын
Yeah, it's easy to screw this section up.
@court2379
@court2379 2 жыл бұрын
They should allow over breaker rated current for disposers so long as a momentary switch is used (you cannot leave the switch on and walk away). The device is not run long enough to heat the wires up even if running at the same time as the dishwasher.
@KenD868
@KenD868 2 жыл бұрын
I just found Ryan's KZbin channel. I really liked listening to.him with Mike Holt now I get to watch his channel. Happy I found it.
@RyanJacksonElectrical
@RyanJacksonElectrical 2 жыл бұрын
Thanks Ken!
@davep8366
@davep8366 8 ай бұрын
Best breakdown / explination I have seen!!!!
@slavickovalenko6702
@slavickovalenko6702 9 ай бұрын
I’m confused on how in the world electrician supposed to know what home owner will plug in particular outlet.?
@Lordjerm78
@Lordjerm78 2 жыл бұрын
Thank you for this. It actually helps a ton to know the changes a little sooner.
@felixsandoval486
@felixsandoval486 2 жыл бұрын
Clear and easy. Thanks a lot Mr. R. Jackson. Useful and helpful. Even Ajax said, it is awesome.
@ajcarrico1
@ajcarrico1 3 ай бұрын
You are an excellent teacher.
@steven7650
@steven7650 Жыл бұрын
can you yes; should you no. Having a heavy motor load right next too and on the same circuit as senstive electronics in modern dish washers helps account for their increased failure rates. I separated mine by just running 14/2/2 to that location.
@The360Electrician
@The360Electrician 2 жыл бұрын
Ryan, hope all is well. Thank you for the content as usual
@thebluecommet
@thebluecommet 2 жыл бұрын
Thank you, these videos help me out so much.
@jimdension8074
@jimdension8074 2 ай бұрын
Excellent presentation
@urbanturbine
@urbanturbine 6 ай бұрын
You discussed UL rating for household appliances. How about commercial equipment? We are seeing a lot of equipment imported from overseas that are obviously not listed. For example, refrigeration equipment for walk in coolers etc. We always get asked if they need to be UL rated. As far as i checked, i do not see NEC requiring UL listing on those kind of equipment. What would your thoughts be on that? Sometimes these equipment will even require European voltages like 380 or 400 volts 3phase or 220-240v single phase line to neutral power. They will offer to sell a transformer to come along with it. It'd be great to see a video about tips and tricks for compliance. Your content and explanations are fantastic. Thank you.
@--JohnDoe
@--JohnDoe 2 жыл бұрын
@14:14. So we can decide if we, or any future owner will or will not utilize it for 3+ hrs? I always though if it's possible to run 3+ hrs it's continuous. Thank you for all the videos.
@vlad1889
@vlad1889 2 жыл бұрын
Idk, can you imagine doing a house calculation load with that mentality? I doubt anyone will run a dishwasher even more than 1-2 hours ever, in residential applications of course.
@garbo8962
@garbo8962 2 жыл бұрын
My wife only knows one cycle on our fancy dishwasher. Hygienic with heat to dry dishes. Yep the longest and most expensive cycle. The motor probably never runs more then 10 to 12 minutes before going to a rinse cycle then heater that probably does not draw 10 amps so in my eyes you could connect the two appliances that never run motor never runs over 10 to 15 minutes. I have rewired kitchens during remodels and always but the dishwasher, garbage disposal and refrigerator on their own circuit breaker. Used to love when people spent tens of thousands of dollars to gut & update a kitchen from the 1930 or 40's and people refused to spend money to replace a 60 amp service & fuse box. Told them to please get somebody else to cut corners. Had some of these people that called me back to say they could not run dishwashet, garbage dispisal, hot comb in bathroom. Told them they had to hire somebody to split up circuits and by the way now that walls are closed in going to cost a lot more.
@rupe53
@rupe53 2 жыл бұрын
@@vlad1889 ... even a dishwasher will shut off at the end of a cycle, so there's a break in service. IOW, the 5 minutes to empty it is less than 3 hours.
@ericdevries3007
@ericdevries3007 10 ай бұрын
Does NEC require that dishwasher and disposal circuits be sized for what future owners could reasonably install, or may the circuit be sized (smaller) for what will be installed initially? For example, a future owner COULD reasonably install a 15A dishwasher and a 1.25hp (12.3A) disposal. These are the largest sizes that are currently on the market. The dishwasher could be run virtually continuously for a party so needs its own 20A circuit. The disposal at 12.3A needs it’s own 15A circuit.
@jrpritchard1622
@jrpritchard1622 2 жыл бұрын
hey Ryan thanks for the awesome information very helpful on understanding codes ill be the first to say i have done the hp rating incorrect thanks for clearing that up
@estevaness
@estevaness 2 жыл бұрын
Nice 👍 my question would it have to be AFCI / GFCI protected? We have different views of this in my region… I personally would think GFCI would not have to since the outlet is not readily accessible? But would be required to be AFCI protected per Article 210.12 (A).
@felixbruno8806
@felixbruno8806 2 жыл бұрын
GFCI required also 210.8 D.... 422.5 A 7
@estevaness
@estevaness 2 жыл бұрын
@@felixbruno8806 Thanks
@J-Jim
@J-Jim 2 жыл бұрын
Felix has pointed out the GFCI codes for the DW. The disposal would need to GFCI’d under 210.8.A.7 since the receptacle location falls with the sink distance rules. They both must be AFCI protected because the outlet (in this case receptacle outlet) is in a kitchen, 210.12.A. Building Code does let you put the DW receptacle behind the DW. Since the receptacle will be under the sink, it is still readily accessible as long as you don’t need a tool to open the under sink doors.
@ronbonick4265
@ronbonick4265 Жыл бұрын
Great when you give examples
@chrismorz8541
@chrismorz8541 2 жыл бұрын
Hi Ryan great video as always, Table 210.21(B)(2) says for cord and plug 20A circuit max load is 16A, if the dishwasher and disposal are both cord and plug would this be true? Thanks again great work!!
@RyanJacksonElectrical
@RyanJacksonElectrical 2 жыл бұрын
Yes, but remember that a duplex is two receptacles. Each half of the duplex may support 16A, and the total must not exceed 20A.
@johnkling3537
@johnkling3537 2 жыл бұрын
Wow. Thank you for the training. Well explained
@franksoler598
@franksoler598 2 жыл бұрын
Ryan thanks for share your time and knowledges with us. Now referring to the disposer name plate in this case what would be the hp rating 3/4hp or 1hp?.
@thisgame1499
@thisgame1499 Жыл бұрын
I watched another code channel video on this topic, where the instructor said that some modern dishwashers could be considered a continuous load. I assume continuous load rules still apply to this scenario (2 fixed in place)
@russellperhamii2220
@russellperhamii2220 2 жыл бұрын
Ryan; love the content! Especially the XFMR vid.
@jeremymiley6453
@jeremymiley6453 2 жыл бұрын
Thanks for the info. I do have a kind of related question because it is an appliance question. Would a refrigerator be considered a "fastened in place" appliance? It is not easily moved and most have an ice maker which is connected to water.
@RyanJacksonElectrical
@RyanJacksonElectrical 2 жыл бұрын
Not in my opinion.
@jonpastore7728
@jonpastore7728 Жыл бұрын
Awesome way to explain the code! Thank you
@ericgold3840
@ericgold3840 Жыл бұрын
Wonderful content and presentation. THANK YOU
@hangngoaigiare
@hangngoaigiare 2 жыл бұрын
Great presentation love it
@garbo8962
@garbo8962 2 жыл бұрын
I would place a saw drawing 14 amps on #12 copper to a 20 amp breaker because it would be just my luck to get a call back that the high in rush motor current would trip a 15 amp breaker maybe once a year. We were taught the 125% rule that all motors even the ones that only run a few minutes a day should be on wires & a circuit at least 125% larger then nameplate amps. Some times like with air compressors had to supply a breaker or time delay fuse 150% higher then nameplate amps. Good to see another well produced vid from you. Also do not believe that the code rule for kitchen counter top receptacles having at least two 20 amp dedicated circuits. Now with protruding islands off a counter top think it should be at least 3 twenty amp circuits. Saw houses where they have a 4 slice toaster, 30 cup coffee pot, blender, counter top toaster oven etc.
@rupe53
@rupe53 2 жыл бұрын
in most areas they call for another circuit on an island.
@J-Jim
@J-Jim 2 жыл бұрын
Two small appliance branch circuits are just a minimum. It’s up to us to point this out and educate as early as possible in the building process, hopefully while still in the planning stage.
@jasonparkinson7621
@jasonparkinson7621 2 жыл бұрын
Great and informative as always. Thanks.
@victorpoliashov2467
@victorpoliashov2467 2 жыл бұрын
WOW! Blown away by your explanation. You know as a apprentice 15 years ago I remember dis this with my JW, but it was sweeped under. I recently I was in this very position of suppling a DW and disposal from a single circuit, I was uncertain of 100% code compliance but you cleared that up! Just curious what about a disposal and the light over the sink scenario? I remember that being called by inspectors multiple times in my career. Would love to hear your thoughts
@rupe53
@rupe53 2 жыл бұрын
that's a tough call, but I would think that light might be a "fixed" application so just figure for the max load.
@icevariable9600
@icevariable9600 2 жыл бұрын
Remember, he said, "210.23(A)(2) Equipment fastened in place (50%). The load must not exceed 50% of the circuit rating if lighting, portable equipment, or both are supplied on the same circuit." So a 10A disposal should be able to work on a 20A breaker with lights, presuming the lights aren't greater than 10A load. But I could be wrong. I'd go read 210.23 and see what it says.
@rupe53
@rupe53 2 жыл бұрын
@@icevariable9600 ... point taken, but the max load on a 20 amp breaker is 16 amps, although there is some allowance for start surge on a disposal. I take that to read 50% is the allowed max for those fixed appliances. There's still 6 amps left for a light fixture.... although your local inspector may frown on it. Perhaps there's an exception if the light WITH the other things is still under 50%?
@KrazyKajun602
@KrazyKajun602 Жыл бұрын
on the flip side, where does it say on a applicance label that it requires a AFCI or GFCI but yet the NEC requires GFCI receptacles in a kitchen. Didn't see anything on the labels that it required a gfci.
@fredbrown7954
@fredbrown7954 2 жыл бұрын
Thanks for the Code explanation. You did a good job 👏
@educationpower1823
@educationpower1823 2 жыл бұрын
Great job Ryan. Appreciate it.
@gmr228
@gmr228 2 жыл бұрын
Could you plesse explain the 80% rule for cord connected appliance why the device rating must be less than the circuit breaker?
@bobniles1928
@bobniles1928 Жыл бұрын
When wiring for a DW and disposal, you do not know the appliance ratings that will be installed.
@dandisen2643
@dandisen2643 Жыл бұрын
Ryan, in your example in time stamp 13:32 with a 5 A sander (fixed) and 10 A dust collector (portable), could you have used a 15 A circuit?
@flatbeavergarage7692
@flatbeavergarage7692 Жыл бұрын
in the 40 years of doing electrical work I have always ran a separate 20 amp ckt for the dishwasher and disposal using a 20 amp recpt. under the sink with the top half switched for the disp. to plug into and the bottom half non switched for the dishwasher to plug into and installed rated pigtails on each appliance......And the only place I use 15 amp ckts and 14 wire is some lighting and gas fired furnaces....most every thing else 20 amp 12 wire......keep it simple
@RyanJacksonElectrical
@RyanJacksonElectrical Жыл бұрын
Sounds like you've wasted a lot of money in your forty years.
@nhzxboi
@nhzxboi 2 жыл бұрын
Give us more. Keep it coming.
@Sparky-ww5re
@Sparky-ww5re 2 жыл бұрын
Hey Ryan, just to clear things up. If cord and plug connected equipment is limited to 80% of the circuit rating, then why do manufacturers make 1875 watt hair dryers, and deep fat dryers, toaster ovens and steam irons rated at 1800 watts, with a 15 amp plug? It would seem like they would be required to come with a nema 1-20P or 5-20P to comply with the NEC code for the 80% rule.
@christopherlawler3033
@christopherlawler3033 2 жыл бұрын
Both a dishwasher & garbage disposer on the same branch circuit ? ? ? I don't see any problems with this, so long as the nameplate ratings of both appliances do not exceed the rating of the branch circuit and so long as the branch circuit is dedicated to those two appliances (with nothing else added to it.) In practice, I also use a single 20-ampere branch circuit to supply electrical current to a common household refrigerator and a typical household microwave oven (up to a 1.2kW rating), since both appliances are not continuously operated (the refrigerator cycles on & off, and the microwave oven, for obvious reasons - is not in operation for more than several minutes at a time.) My interpretations of the CODE when it comes to two dedicated circuits in a domestic kitchen environment is defined as two dedicated appliance circuits supplying counter-top receptacles that are intended for the use by portable, cord and plug connected small appliances i.e. toaster, coffee machine, food processor, meat slicer, rice cooker, etc. larger appliances such as the microwave oven or a convective air-fryer (with a nameplate rating of 12.50 amperes @ 120V.A.C. or 1.5kW of electrical energy consumption or power draw should be placed on a different circuit dedicated to that appliance as would be the case above (with the household refrigerator only drawing 3 amperes (0.360kW) or less when it is cycled on.) Commercial/industrial refrigeration units may very well draw even more electrical energy (in excess of 10 amperes (1.2kW) in some circumstances) and would otherwise be handled as the same as a microwave oven, being that it would also require a dedicated electrical circuit in order to operate reliably and without overloading the associated branch circuit supplying it and causing the circuit protection to trip offline, causing the refrigeration unit to cease operation and the contents requiring refrigeration to expire. I honestly do not see why NEC Article 210.23 is really all that difficult to understand? Basic math skills are definitely required in order to sum up the total circuit demands needed to understand when loading up branch circuits used for supplying specific appliances or applications, such as that of what would be found in a domestic/residential kitchen or commercial food preparation environment, workshop, or any other environment where there is a higher than normal electrical demand. I almost always keep lighting equipment, light fixtures or luminaires & associated utilization equipment (ceiling fan(s)) on a separate or dedicated electrical circuit, apart from circuits supplying kitchen appliances & electrical receptacles or other convenience receptacles so as to prevent the affected area from being left in the dark, should an electrical overload or other electrical fault occur on one of those appliance circuits.
@hansmortensen5668
@hansmortensen5668 2 сағат бұрын
Thanks man this helped a lot!
@court2379
@court2379 2 жыл бұрын
1 hp is only 6.1 A at 100% efficiency and 120V. Those name plates look quite accurate actually. 9.5A for . 75hp means it is a pretty inefficient motor, but likely puts out it's full rating. The main place I have seen the lies is on vacuums. I believe they are taking the stall torque and multiplying it by the maximum speed to get those those numbers, but the two don't occur at the same time so they are lies.
@unlimitedbandwidth
@unlimitedbandwidth 2 жыл бұрын
There's no such thing as a 100% efficient motor so doing a conversion of HP to watts and calculating amps from that doesn't really help since a motor is not a resistive load. Also, I'm not sure where you're FLA numbers are coming from but they're incorrect for 120Vac motors. 3/4HP is listed as 13.8A @ 120Vac per NEC table.
@OctavioDiaz-z4l
@OctavioDiaz-z4l 14 күн бұрын
Ryan Thank you
@dexteralivio9417
@dexteralivio9417 2 жыл бұрын
I just subscribed to your channel, this is excellent content.
@joer9276
@joer9276 Жыл бұрын
6 amps for a DW is pretty low, typical amperage is 12 ish.
@petercook3143
@petercook3143 6 ай бұрын
No problem, those are very small motors. Also should be 20 amp circuit according to everything else in a kitchen.
@RyanJacksonElectrical
@RyanJacksonElectrical 6 ай бұрын
It doesn't have to be a 20A circuit.
@Samnang1965
@Samnang1965 Жыл бұрын
Hi I believe the appliance label wrong on Disposal & dishwasher the same circuit? Even y using cable awg it will smoke.label should be printed 1,500w
@Samnang1965
@Samnang1965 Жыл бұрын
I mean Cable
@isaachinojosa9863
@isaachinojosa9863 2 жыл бұрын
Just here to leave this comment, thanks for the great info.
@GeneralRock114
@GeneralRock114 Жыл бұрын
Can a GFCI breaker flip due to excess heat caused by our excess outside temperatures making the circuit box hotter than normal ???
@AustinAdams
@AustinAdams 7 ай бұрын
Is a freestanding range considered “fixed”? Also your typical washer and dryer units?
@RyanJacksonElectrical
@RyanJacksonElectrical 7 ай бұрын
Appliances can be fixed, portable, or stationary. I would call those stationary.
@quintinwiley2089
@quintinwiley2089 2 жыл бұрын
I may have missed it in all the other comments... What about three fixed appliances on the same circuit in the kitchen. I've got the dishwasher, diospser, and the instant hot water tap all in the same region. What would be my parameters there?
@randallcalhoun6604
@randallcalhoun6604 Жыл бұрын
How do you differentiate fixed vs plug and cord connected? Ie is a drill press cord and plug then changes to fixed if bolted down?
@JFlywheel
@JFlywheel 2 жыл бұрын
Ok found out contractors ran 2 yellow romex to the dishwasher outlet and the tab is broken to make it two circuits (there is no line to a switch). Both romex just run to the attic and attach to the same 14-2 romex that is a 15 amp circuit. Is this some kind of trick to help pass an inspection? My dishwasher is LG and rated for 15 amps and my garbage disposal has a sticker on it that says it is 9.5 amps. Trying to get them to fix it...
@chrisf3875
@chrisf3875 Жыл бұрын
What about table210.21(b)(2) Total cord and plug connected load. No more than 16 amps on a 20 amp circuit. Looks like you're over by 1/10 of an amp. If you're dishwasher & garbage disposal are cord and plugged type. Just curious that you didn't discuss the total cord and plug connected load table 210.21(b)(2)
@RyanJacksonElectrical
@RyanJacksonElectrical Жыл бұрын
Because a duplex receptacle is two receptacles.
@chrisf3875
@chrisf3875 Жыл бұрын
Oh...so each receptacle on the duplex can supply up to 16amps if on 20 circuit....(but you can't load the branch circuit up to 32 amps)... It is not stating the total being plugged into both. Is what the table means. What I think is getting me confused is how the tables description, uses the terminology" total cord and plug connected load in excess" should it not drop the word "total" and just state "cord and plug connected load in excess" The word total makes me want to add up all my cord and plugs connected loads. Thanks I really do appreciate your work.
@Darenator1
@Darenator1 2 жыл бұрын
I see dishwasher and disposal on 20A circuit all the time. However they are cord and plug. So does that mean limited to 16amps total?
@JohnThomas-lq5qp
@JohnThomas-lq5qp 6 ай бұрын
Have to poke fun at hard working brillant Ryan but here goes. Heard of people coming out of the closet but never somebody coming out of a dishwasher. I always installed a dishwasher on thier own circuit breaker but now with combination AFCI/GFCI single pole circuit breakers costing close to $50 each would reconsider adding the garbage disposal to a single circuit. ( 12 guage copper NM on a 20 amp AFCI breaker. Dishwasher load calulation can be misleading. The motors in all the new dishwashers use less power then the heating element and believe the calculation should only use the 125% multiplyer for only the motor then add the ampere for the heating element. Heating element is purely 100% resitance load with 100% power factor and no locked rotor intush current like a motor.
@spdglez6663
@spdglez6663 Жыл бұрын
No offence. Your Dogs are the best. You are good too.
@Gazebomanfla
@Gazebomanfla 2 жыл бұрын
Hello Ryan 5 amp sander and 10 amp dust collector Requires 15 amp circuit?
@jolyonwelsh9834
@jolyonwelsh9834 2 жыл бұрын
Heavy duty lamp holders= mogul base sockets.
@markchidester6239
@markchidester6239 9 ай бұрын
Ok, so if i have a dishwasher and desposer combo that draws more than 20a, can i split a duplex receptacle into two circuits?
@JeffBanfield-t6v
@JeffBanfield-t6v Жыл бұрын
How do you get around Table 210.21(B)2? Maximum cord and plug connected load on a 20 amp receptacle and a 20a circuit is 16 amps? Maximum on a 15 amp receptacle is 12 amps.
@RyanJacksonElectrical
@RyanJacksonElectrical Жыл бұрын
A duplex is two receptacles. The total load on the duplex is limited to the rating of the device. Each of the receptacles can take up to 80% of that rating.
@JeffBanfield-t6v
@JeffBanfield-t6v Жыл бұрын
@@RyanJacksonElectrical 210.21(B)2) refers to more than one receptacle. Read it
@RyanJacksonElectrical
@RyanJacksonElectrical Жыл бұрын
@@JeffBanfield-t6v I am aware of that. I have read it once or twice. What do you beleive the Code violation is?
@JeffBanfield-t6v
@JeffBanfield-t6v 7 ай бұрын
@@RyanJacksonElectrical I paused the video at 7:50 mark. It reads disposal is 6.6A and dishwasher is 9.5A = 16.1A 'Both may be supplied by a 20A circuit that doesn't contain any other loads'. Assuming you have cords on them, that is a violation of Table 210.21(B)2 that states the maximum cord and plug connected load is 16 amps for a 20 amp rated outlet on a 20A circuit.
@RyanJacksonElectrical
@RyanJacksonElectrical 7 ай бұрын
@user-ll1vj7qo1m No it isn't. A duplex is two receptacles, not one
@jimmiegill3981
@jimmiegill3981 2 жыл бұрын
I remember a video you did about bundle wires I had an inspector question 3 wires through a tgi with no foam could you link me to that video
@skunkbri
@skunkbri 2 жыл бұрын
Dishwasher has to be on a GFCI 422 and they both have to be arc fault 210.12
@Jeff-xy7fv
@Jeff-xy7fv 2 жыл бұрын
It's best practice to just wire the disposal and dishwasher to a separate circuit for each. This ensures that all appliances will be in compliance.
@DonkeyLipsDA3rd
@DonkeyLipsDA3rd Жыл бұрын
Depends on the situation. If I am doing remodel work on a kitchen that’s on a slab. I will definitely put that on one circuit if the wire is in good shape.
@mailchrisbailey
@mailchrisbailey Жыл бұрын
why is that? he just demonstrated that it's code compliant and perfectly safe. most of the time you don't run both together. you use the disposer first and then start the dishes
@westernbear2265
@westernbear2265 4 ай бұрын
All these “Well, better just run another line” or “better safe than sorry.”If a client is being charged an extra $1000+ dollars to run a new line because the electrician can’t be bothered to apply their own expertise, maybe quit being electricians. The whole point of a profession is to provide competency to someone who trusts you to be a subject matter expert.
@MrClaudio
@MrClaudio 2 жыл бұрын
How would anybody know that a circuit is shared with lights? Should it be labeled with the 50% as max rating?
@talbertadams6586
@talbertadams6586 2 жыл бұрын
If you trip the breaker for the dishwasher and disposal and the lights will not come on, you possibly have your answer.
@MrClaudio
@MrClaudio 2 жыл бұрын
@@talbertadams6586 I was referring to minute 11 in the video. If in the future the machine is replaced, no one knows the parameters. Also, if the luminaries take, let's say, 15 amps, does the nec allow to add an outlet to the circuit?
@rupe53
@rupe53 2 жыл бұрын
@@MrClaudio ... you are cutting it too close because even a 20 amp circuit is only rated for 16 amps continuous.
@MrClaudio
@MrClaudio 2 жыл бұрын
@@rupe53 that's not the point.... But I still have an amp to spare.
@rupe53
@rupe53 2 жыл бұрын
@@MrClaudio ... gotta read between the line again. If you mean old fashion Edison base bulbs, then all bets are off because people can stick any bulb in a socket and overload things. If you have newer fixtures with a specific socket type that can't accept a different bulb, then the math is different on the lighting load. What I am driving at is 15 amps worth of light is 1800 watts. (continuous load) If the CFLs are 20 watts each then that's 90 fixtures. If they are LED then probably twice that. I doubt your local inspector will allow that many fixtures on a circuit, no matter what the code says. BTW, if these are industrial type lights and permanently secured / hardwired, then you probably should be looking at the 50% rule for load.
@JFlywheel
@JFlywheel 2 жыл бұрын
Contractors put both my garbage disposal and dishwasher on the same 15 amp circuit. Remodel is not finished. Does this need to be corrected? Garbage disposal is 8amps and I can't find the info on the dishwasher we are adding (did not have one before).
@RyanJacksonElectrical
@RyanJacksonElectrical 2 жыл бұрын
I'm sure it's fine, assuming that those are the only two things on the circuit.
@JFlywheel
@JFlywheel 2 жыл бұрын
@@RyanJacksonElectrical oops i was thinking 20 but it's a 15 amp. Going to change my question above to be 15 amps instead of 20. Thanks! I think you did say 20 would be ok in your video. Just opened that box for the dishwasher and it says it should be on a dedicated circuit (15 amp minimum) but I can't find the power numbers. Didn't have a dishwasher before so they were supposed to provision power for it.
@rmhanseniii
@rmhanseniii 2 жыл бұрын
I agree with the code explanation however quality dishwashers nowadays will draw 11 Amps
@garbo8962
@garbo8962 2 жыл бұрын
I have been in the same house and on the 4 th or 5th dishwasher. First was a portable on wheels that we had the two years in an apartment then cut out a cabinet and made it a built in. Newest dishwasher & even my direct drive heavy duty large capacity v washer machine have motors halve throw size of older ones and draw at least 35% less current. Guess that's due to being energy star rated. Have Manuel started on my gas dryer & washing machine. Had to down size ampere rating at least 4 amps lower on the latest washing machine. Glad I had the Manuel starter on those washing machine. Twice starter tripped out due to me not removing handful of #10 solid wire from my pocket causing water pump to jam up.
@megabytephreak
@megabytephreak 2 жыл бұрын
16:48 210.23(C) Does this imply that a 40 or 50 amp circuit in a dwelling unit cannot supply anything other than cooking equipment? E.g. EV Charger, Welder, Large AC, Electric Furnace etc.
@rupe53
@rupe53 2 жыл бұрын
you need to read between the line here as most things at 40 amps and higher might not have a neutral so are wired different.
@J-Jim
@J-Jim 2 жыл бұрын
For these other appliances / equipment, you would be running an individual branch circuit and 210.22 would apply, and not any of the multi-outlet rules of 210.23.
@rupe53
@rupe53 2 жыл бұрын
@@J-Jim ... good point. I can't think of any applications where a 30 - 60 amp outlet would not be a dedicated run to a single outlet. Anything over 60 amps will be a sub panel and broken out from there.
@WardCo
@WardCo 2 жыл бұрын
Also, a lot of that equipment is not "in" the dwelling unit.
@rupe53
@rupe53 2 жыл бұрын
@@WardCo ... but the circuits all start at the main panel FOR the dwelling so it's implied.
@JuanRamos-sh9we
@JuanRamos-sh9we 2 жыл бұрын
Great explanation thanks
@Patrocco
@Patrocco 2 жыл бұрын
I just watch it 2 times. 🙏🏼😍😍
@brockpace8996
@brockpace8996 2 жыл бұрын
So I’m looking to purchase the Nfpa 70e but I don’t know what I should get , the standard 70e or the handbook which one has more detailed information and what is the difference thank you .
@RyanJacksonElectrical
@RyanJacksonElectrical 2 жыл бұрын
If you're new to the subject, I recommend the handbook. The handbook contains commentary that you'll find useful.
@brockpace8996
@brockpace8996 2 жыл бұрын
@@RyanJacksonElectrical well I am a safety coordinator by trade and just wanna keep up to date with the codes and protocols and things like that .
@PLEBEJones
@PLEBEJones 2 жыл бұрын
Lol how'd you get in to that cabinet Article 100
@luis2186
@luis2186 Жыл бұрын
Which is better to run 12/3 or 12/2?
@mauriciomalisani2506
@mauriciomalisani2506 2 жыл бұрын
Omg now I'm more confused, why if I have disposal and dishwasher in the same circuit the inspectors don't passed my inspection
@erikolsen3611
@erikolsen3611 2 жыл бұрын
Ryan are you still associated with mike holt? i know that 3 way switch thing you mentioned came from him in one of his videos.
@philgonzales5310
@philgonzales5310 2 жыл бұрын
Good job
@chrisbodiford6368
@chrisbodiford6368 Жыл бұрын
ok a disposer it is!
@icevariable9600
@icevariable9600 2 жыл бұрын
You said that the dishwasher and disposal were "fixed in place". Then at 10:10 you said they were "fastened in place" and that "you're going to need tools to get those out. At 10:44 you said both your dishwasher and disposal are "fixed equipment, 210.23(A)(2) does not apply". So, you're using the terms interchangeably. However, the definition of "Fastened in Place" is found at NEC 625.2: "Mounting means of equipment in which the fastening means are specifically designed to permit periodic removal, without the use of a tool, for relocation, interchangeability, maintenance, or repair." Note that it says "without the use of a tool" and "periodic removal" which, disposals and dishwashers are not periodically removed. Can you clarify this? Also, id "cord-and-plug" pretty much equivalent to "not fastened in place"?
@RyanJacksonElectrical
@RyanJacksonElectrical 2 жыл бұрын
Article 625 definitions apply only to Article 625 (EV power transfer).
@icevariable9600
@icevariable9600 2 жыл бұрын
@@RyanJacksonElectrical Ok, thanks for clarifying that. But can you still clarify the difference between cord-and-plug, Fixed in place and fastened in place? Maybe some examples of each, since they're not in Article 100.
@franksoler598
@franksoler598 2 жыл бұрын
Or do you know why there’s two hp rating on the disposer name plate? Thanks in advance.
@johnhaller5851
@johnhaller5851 2 жыл бұрын
It was 120/240, the second number was for 240. I had to think about it when I first saw that too.
@franksoler598
@franksoler598 2 жыл бұрын
@@johnhaller5851 thanks👍
@tobieebonics4193
@tobieebonics4193 2 жыл бұрын
Good video
@MrOpinionCantSignIn
@MrOpinionCantSignIn Жыл бұрын
While not relative to subject , andvyou are correct , manufacturers lie ...( 5HP shopvacs are my favorite).... please do your math on how much Amperage a 1HP motor draws .... 1 HP is 748 watts .... last I checked that's 6 Amp, not 15 Amp .... startup is in most cases is not considered a factor as it is momentary .... Disposals draw a bit higher due to possibly immediately starting under load (was surprised that your 3/4 specified 9.5A - clearly starting)
@RyanJacksonElectrical
@RyanJacksonElectrical Жыл бұрын
In the US, horsepower of a motor is a measurement of OUTPUT power, which means nothing unless we know the efficiency of the motor. That is why we NEVER use it in the NEC and why we use Tables 430.248 through 252.
@davem5392
@davem5392 2 жыл бұрын
How could you accomplish this with the needs for AFCI and GFCI protection
@joeltoomey1987
@joeltoomey1987 2 жыл бұрын
Dual Function breaker.
@michaeldemetro5009
@michaeldemetro5009 2 жыл бұрын
Great thumbnail
@MrResale
@MrResale Ай бұрын
you da man
Kitchen islands and peninsulas in the 2023 National Electrical Code
17:14
When are grounding/bonding bushings required in the NEC?
40:36
Ryan Jackson
Рет қаралды 2,7 М.
Colorful Pasta Painting for Fun Times! 🍝 🎨
00:29
La La Learn
Рет қаралды 308 МЛН
Это было очень близко...
00:10
Аришнев
Рет қаралды 7 МЛН
Seja Gentil com os Pequenos Animais 😿
00:20
Los Wagners
Рет қаралды 89 МЛН
Dishwasher and Disposal on Same Circuit? NEC 50% rule?
10:29
Electrical Code Coach
Рет қаралды 10 М.
NEC requirements for box support (314.23)
16:45
Ryan Jackson
Рет қаралды 19 М.
Feeder taps and the 2020 National Electrical Code
28:25
Ryan Jackson
Рет қаралды 65 М.
10 Common Mistakes DIYers Make In Circuit Breaker Boxes
13:55
LRN2DIY
Рет қаралды 2,6 МЛН
Where and Why Do We Need AFCI Protection?
12:45
Electrician U
Рет қаралды 167 М.
Kitchen Counter Electrical - Code Minimum
6:30
Electric Pro Academy
Рет қаралды 38 М.
2023 NEC changes: GFCI protection (210.8)
32:47
Ryan Jackson
Рет қаралды 106 М.
Metal Vs Plastic Electrical Boxes | Avoid This Common DIY Mistake
13:21
Everyday Home Repairs
Рет қаралды 797 М.
How To Wire A Kitchen - Rough In Electrical Circuit Wiring Guide
14:39
The Excellent Laborer
Рет қаралды 324 М.