Do You REALLY Need a Pressure Equalizer Loop? PEX TESTED

  Рет қаралды 389,589

Stud Pack

Stud Pack

Күн бұрын

Пікірлер: 1 100
@davidruss7702
@davidruss7702 2 жыл бұрын
You two are now officially scientists. The only difference between screwing around and science is writing down your results.
@JediahCummins
@JediahCummins 2 жыл бұрын
If we take writing it down as a making a video, they’ve been scientists since experimenting with how to remove a toilet flange. Love the videos Stud Pack, keep it up!
@albertthesecond210
@albertthesecond210 2 жыл бұрын
and even closer to nuke scientists -- writing it down and independent verification of the reading
@johnhaller5851
@johnhaller5851 2 жыл бұрын
Well, when my kids did science fairs, they had to run the test 3 times. That helps balance out not getting the timing right, or discovering that the results were wildly different, showing that the experiment wasn't accurately controlled. Still, the experiment was well designed for keeping control variables consistent and only changing one thing at a time. Plus, running the same experiment 3 times would make for a slow video.
@tonybowers9490
@tonybowers9490 2 жыл бұрын
Yes. It’s now a science channel. Best study our physics.
@Titantitan001
@Titantitan001 2 жыл бұрын
Or making guesses, never having a way to prove it and then write books about it.
@Derek-xr3uq
@Derek-xr3uq 2 жыл бұрын
“K.I.S.S.” Less fittings, less pipe, less time - no brainer! Guys go crazy with loops and crossovers on remodels around here but need to brush up on their Bernoulli. This is a pressurized system. Pressure builds from the end. Restrictions increase pressure. Testing or thinking of the free flow output alone doesn’t translate to the flow or balance once restriction (the sprays) are added. Great no-nonsense and simple tests!
@lblbuilders
@lblbuilders 2 жыл бұрын
absolutely awesome video. this is what separates stud pack from much of the competition. humility, the assumption that you don’t know everything , the willingness try something new and a genuine curiosity about construction science. the old TQM philosophy of constant and continual improvement lives on in stud pack.
@AdkKarl
@AdkKarl 2 жыл бұрын
Team H! Fewer fittings + Less pipe = less pressure loss. Cheaper too! Fun video, thanks for sharing.
@ronlovell5374
@ronlovell5374 2 жыл бұрын
It would have been even less fittings if he had used the dual in-let drop ears for loop
@travisk5589
@travisk5589 2 жыл бұрын
Less fittings equal less chance of leaks
@bryanhickman7663
@bryanhickman7663 2 жыл бұрын
Less line turbulence too.
@zombiexpanda
@zombiexpanda 2 жыл бұрын
@@travisk5589 Not really much of a worry when pex is involved. The pex a the fittings will become more snug over time
@travisk5589
@travisk5589 2 жыл бұрын
@@zombiexpanda get some real world experience
@leobrent7926
@leobrent7926 2 жыл бұрын
Even before the test I already knew that the H system would win. And as I said it before when I commented on your videos, you guys are not afraid of a little constructive criticism and putting other people’s theories to the test (when it makes sense) thank you for all your hard work and the time you take to read the comments. Now stop screwing around and finish that bathroom so we can see some real work on the stud pack lone star house hehe! 👍
@frankyboy4409
@frankyboy4409 2 жыл бұрын
Same, for me the simple reason is: less piping. Which also means less water in the systems, and thus faster-reacting controls.
@leobrent7926
@leobrent7926 2 жыл бұрын
@@frankyboy4409 now that you mention it... you bring up a really good point. I’ve seen a lot of new houses where they put the valves far away from the shower heads because according to them you “don’t get wet while turning them on” but the extra length of pipe means that the shower heads will keep dripping water for a longer period of time after they’ve been shut off. So my advice to prevent this issue is to use as less pipe as possible between the valves and the heads or nozzles.
@leobrent7926
@leobrent7926 2 жыл бұрын
@TJP 81 it absolutely won. Keep in mind that the name of the game was even flow and either nozzles of the same level kept delivering the same amount of water. And the difference between the top and bottom nozzles was less of that between the loop system.
@sonarun
@sonarun 2 жыл бұрын
These guys are the best!!
@MoneyManHolmes
@MoneyManHolmes 2 жыл бұрын
I believe the new plumbing code calls for the shower controls to be accessible without getting wet.
@dallasarnold8615
@dallasarnold8615 2 жыл бұрын
Another plus for the "H" pattern is easier access if there is ever a problem. Less joints less likelihood of problems also.
@andycanfixit
@andycanfixit 2 жыл бұрын
Yeah, the straight up simplicity is worth it even if the results were slightly worse, though with less fittings and pipes, there is less risk of pressure loss to begin with.
@rlb9121
@rlb9121 2 жыл бұрын
Retired plumber, started using Uponor and expander PEX since it first came out, and I'll tell you this, you are correct in that you can cut in a line to add fittings, and the water in the line won't be that much of a problem, unlike copper, BUT, BUT, BUT, if you try to expand a piece of wet Uponor pipe, and the expander ring is ALSO wet, both the ring and the pipe will slide off the expander tool at the same time. Believe me, it sucks, if you're under a house or retrofitted home, and cutting in a line, and it's wet. FYI.
@daddy1571
@daddy1571 2 жыл бұрын
When I have to do this,I take some sandcloth and rough up the pipe surface before putting the ring on. It works EVERY time with no ring slide-back.
@krispyasfk2567
@krispyasfk2567 2 жыл бұрын
Just use propress like a real man
@MrDarren5012
@MrDarren5012 2 жыл бұрын
No it won’t…the old style expansion rings yes..the new rings have stops on them
@MrDarren5012
@MrDarren5012 2 жыл бұрын
@@krispyasfk2567 progress…lol… glorified shark bite you mean?
@krispyasfk2567
@krispyasfk2567 2 жыл бұрын
@@MrDarren5012 That has to be the dumbest and most ignorant thing I've ever heard
@Vader99ify
@Vader99ify 2 жыл бұрын
I love how you show proof that we don't know what we are talking about instead of just telling us we don't know what we are talking about! Love this vid!!!
@independentinstallations8419
@independentinstallations8419 2 ай бұрын
I agree this should be mandatory practice when arguing with internet strangers in a civilized society! lol
@billcarpenterwkcplumbinghv8915
@billcarpenterwkcplumbinghv8915 2 жыл бұрын
Wonderful demonstration. Very good information for all plumbers, Masters through apprentices. Although your spray heads had adjustability, not all of them do, starting out with equal flow and pressure is always the best start. I am an inspector for a large city, also a professor of Plumbing at our local Community College. I will be using this video to help apprentices understand basics and why we do what we do. Please preach to your Utube community how important it is to get into the trades. Stay Dry
@StudPack
@StudPack 2 жыл бұрын
That’s awesome thx Bill!! And thx for teaching the trades… so important and much needed now more than ever 👊👍
@colleenscottcarmello5103
@colleenscottcarmello5103 2 жыл бұрын
Another benefit of PEX.. couldn't have done this test with copper.. =D. Would've missed out on all this fun.. this is definitely father/son quality time. Not only a great contractor teaching his son life skills, you are teaching viewers what it means to be a father, and what it looks like being a father in real life.. you are helping the world be a better place..
@syreplays5079
@syreplays5079 Жыл бұрын
Yes you could have? He used drop ear 90s with male adapters threaded into them.
@justmyopinion99
@justmyopinion99 2 жыл бұрын
As a trained engineer, I love a video like this. There is theory, and then there is practice. Sometimes, the differences created by practice totally overwhelm the theoretical. In this case, the actual pipe lengths, fitting resistance, etc. are big contributors to actual performance, while theoretical differences are overwhelmed. I would predict that the shortest length of piping and the least number of fitings would produce the highest flow and pressure and the highest volume. If the outlets are vertically separated thbn they would have to be balanced by a restriction to the lower heads. Moving the supply connection from the center to above the heads should make a difference, but testing would tell.
@jeffliverman3401
@jeffliverman3401 2 жыл бұрын
The best way albeit more expensive and time consuming would be to add a globe valve which is an metering valve to each branch and manually adjust them all to balance out pressure and volume,much like an old radiator system
@pawpaw7646
@pawpaw7646 2 жыл бұрын
In theory, there is no difference between theory and practice. In practice, there is.
@lostreb
@lostreb 2 жыл бұрын
@@pawpaw7646 ROTFLMFAO...Lots won't like it when I say this. BUT...Reality is...well..Reality!!!! Theory is...Exactly that...Theory!!!! You are wise beyond your years!!!!!! Great Comment!!!
@chrish7336
@chrish7336 2 жыл бұрын
You are correct, Theory does not equal reality. Plumbing electronics whatever it may be.. Example, (electronics) The Vacuum tube was not being designed to be used as an amplifier. Theory stated that the tubes should have done something else completely. It was only be accident that Reality "overwhelmed" Theory thus the Vacuum Tube changed electronics forever. This new theory of amplification circuitry eventually led to the design of Transistors. Theory is a great starting point and foundation, but that won't change the reality of application.
@Alphasig336
@Alphasig336 Жыл бұрын
@@jeffliverman3401 you still have lower pressure than a simple H. The more connectors and pipe cause resistance which reduces pressure. Unless your adding pressure. KISS method wins out.
@thtadthtshldntbe
@thtadthtshldntbe 2 жыл бұрын
Its been so long since college that i cant do the calcs or a schematic anymore but generally speaking, water pressure is like direct electrical current in a lot of respects. Pressure drops off over distance in relation to material reaction. For electricity thats resistance for water pressure iirc its friction. For water the material absorbs the energy in the water, this fractionally, even if minutely lowering pressure. What that means is that straight runs from source to outlet with zero joints produce the least loss in pressure. Curving the pipe where it could be straight causes a increase in pressure loss, as its essentially constant collion with the pipe wall is what changes the vector. The more extreme the curve, maxing out at 90 degrees, leads to the most loss. Additional changes like say more 90 degree turns further lowers the volume. I know plumbing is limited by existing fittings and code. Great video guys. If you know and civil or mechanical engineers they should be able to actually do math on sometging like this and produce a couple diagrams
@oldsguy354
@oldsguy354 2 жыл бұрын
Grady @Practicalengineering (on KZbin) does a lot on water systems. His focus is more on municipal sized systems (both water in and sewage out). He's pretty smart and I'm betting he has the formulas (or can write them) on the Engineering. Bonus fact is he's in Texas (San Antonio) so it wouldn't take extensive travel for a collaboration, but a zoom or email exchange would probably work. I mean if you want to know right down to the nitty gritty formulas and equations, I'm betting he's the guy. I hope he doesn't mind me saying all that.
@johnzangari3432
@johnzangari3432 3 ай бұрын
I'm sure you would have gotten the same answer by consulting hydraulics engineering book, but nobody would believe you.
@Mind_Explosion197
@Mind_Explosion197 2 жыл бұрын
I love your channel always responding to constructive criticism and not afraid to show your mistakes in the videos. Truly an inspiration.
@sherryboudreau8868
@sherryboudreau8868 2 жыл бұрын
Probably my favorite SP video. It shows your interest in your subscribers, your humility in your work, your expertise in wanting to mentor, and, well, it was just plain funny. Great dad and son collab!
@Ohio-Patriot
@Ohio-Patriot 2 жыл бұрын
The manhattan loop looked nice but I’m all about simplicity and I believe I’d go with the H pattern myself. Less things to fail in that setup. Great video guys. Love watching you guys get into your work.
@splinterinthemind5158
@splinterinthemind5158 Жыл бұрын
Loop will maintain pressure better …
@bigmike7801
@bigmike7801 11 ай бұрын
​@@splinterinthemind5158 Prove it.
@LathanM
@LathanM 2 жыл бұрын
Another great video. The pressure test and differences minimal as long as you have enough supply volume. To balance it fully you would need to ad additional restriction on the lower section to account for gravity losses. This is beyond overkill for a shower. The best solution is one that goes in fastest with the minimum number of fittings to get the job done. Stick with the H moving forward. The loop idea will works in horizontal balancing but not in vertical. You can't beat gravity.
@TdrSld
@TdrSld 2 жыл бұрын
@TJP 81 I have 65 psi on a Co-Op rural water system. MAkes for some nice hard showers and I love it
@gregoryderosa8045
@gregoryderosa8045 Жыл бұрын
R u a Plumber 🪠?!
@Asta-wl8jz
@Asta-wl8jz 2 жыл бұрын
Probably your best video yet. Not really surprised about the higher jets producing less water as the hydrostatic pressure is higher, as it takes more energy to fight gravity the higher you get. Excellent video.
@arlenem9697
@arlenem9697 2 жыл бұрын
My bathroom has no water jets, but I enjoyed watching your scientific water Pex test. It's the pressure that matters first, then the flow. Great video Stud Pack.
@tph318
@tph318 2 жыл бұрын
Great content and great tests. I have re-plumbed a few places with copper, cpvc and pex. Pex is the clear winner in my opinion.
@charliejohnston1978
@charliejohnston1978 Жыл бұрын
You are my favorite plumbing channel, you have a great sense of humor and your channel is very informative and honest texting and information too. Thanks for all your efforts to help less knowledgeable men learn plumbing.
@StudPack
@StudPack Жыл бұрын
Thanks 👍
@jeremywarren647
@jeremywarren647 2 жыл бұрын
Such a fun video, great job guys! I like the fact too that ultimately the plumbing scenario doesn't matter much since those jets can be individually tuned to the user's preference
@ericgautreaux1752
@ericgautreaux1752 2 жыл бұрын
I'm a retired self employed contractor from Crowley Louisiana and love your videos.
@daveyio87
@daveyio87 2 жыл бұрын
Great video. The science behind equal length pipes has been proven in the automotive world with performance parts, Exhaust headers use equal lenght pipes until they combine into one so each cylinder can exhale the same amount. I hope when i'm ready to do some renovations on my house i can find a contractor like you in Rochester NY. I know there are good ones out here just gotta find them! I also like the H set up as less fittings less complications = less chance for something to go wrong, also from another stand point much cheaper to make vs the loop.
@bobgodd
@bobgodd 2 жыл бұрын
Less potential points for leaks also. Less joints would easily be a winner for me.
@jameshogge
@jameshogge 2 жыл бұрын
Performance exhausts are a bit different: the issue isn't different cylinders having different back pressures. You have a single pulse of pressure each exhaust stroke and that travels down the pipe at a certain speed. Where pipes merge, you don't want pulses to arrive at the same time because then you're trying to exhaust into a high pressure region which is harder. Equal lengths mean the delay from each cylinder to the merge point cancels out. Therefore you will always have the time between cylinders exhausting at the merge point between successive high pressure waves
@jameshogge
@jameshogge 2 жыл бұрын
It gets a bit more complicated with scavenging where you actually try and get the high pressure wave from one cylinder to merge with the low pressure wave which follows the high pressure wave of a previous cylinder. However, for that you've got to tune the lengths a bit mroe carefully and it only works for specific rpm ranges
@DieGoetterdaemmerung
@DieGoetterdaemmerung 2 жыл бұрын
Same goes for heating systems, if the feeds and returns are in sum at an equal length at every radiator or buffer system then you have an equal distribution of heat. It's how biomass buffer systems are connected usually since you save a shitton of valves and fittings if you know what you are doing.
@daddy1571
@daddy1571 2 жыл бұрын
@@jameshogge True but in this case pressure will always be greater on the lower portion compared to the upper one because of head pressure being greater in the lower portion.
@kccustom1
@kccustom1 2 жыл бұрын
Not many people would take the time to do this even less videoing and sharing it! I love it, thanks for taking the time!
@milesharlan1
@milesharlan1 2 жыл бұрын
Saturday morning fun with a new video.Thank You guys. Keep up the good work!
@johnkroll1823
@johnkroll1823 2 жыл бұрын
I installed a similar system, with 6 body jets, and spent days chasing phantoms. Looped but the top 2 jets only provided a drizzle and sputtered. Found 2 problems. The first, it required water pressure to the shower valve on both hot and cold supply sides, I had not connected the dedicated hot water heater yet so it functioned at low pressure. The second required a quarter turn valve be installed in the supply lines feeding the bottom 2 to throttle the water flow a little and add resistance. Adding a booster pump soon to take pressure from 60 to 80 psi static, wish I had seen your video before doing it all. Great work guys.
@chimera5588
@chimera5588 2 жыл бұрын
I love that you guys did a test based on the comments! You're definitely my go to channel for self home improvements because of that alone! As for the H versus O testing when it comes to water pressure I think of it the same as electronics; the water is going to always take the path of least resistance. With that being said having the same distance of line on the H system, and having equal paths of travel for the water makes way more sense than having the pressure from the O system equaling out the amount of water.
@moonpiespotlight4759
@moonpiespotlight4759 2 жыл бұрын
The 90 degree bends also drop some pressure.
@Anytus2007
@Anytus2007 Жыл бұрын
I like the analogy between water and electricity; that's exactly right. I hate that common phrase "always take the path of least resistance" though! Electricity (and water) do NOT always take the path of least resistance. For both of them, if the change in potential is the same across multiple paths, then they both take ALL paths. The amount of current in each path is inversely proportional to that path's resistance. To give an example, if you have a circuit with 2k Ohms of resistance, if you wire up a new 1k Ohm resistor in parallel, the "always takes the path of least resistance" literal meaning would predict that 100% of the current would go through the 1k Ohm resistor. But that's not what you find; instead only 2/3rds of the current goes through the 1k Ohm resistor and the other 1/3rd goes through the 2k Ohm path.
@logancarter2134
@logancarter2134 2 жыл бұрын
Very interesting and informative content! Also your presentation is great, no crazy music or loud excessive talking, just straight forward and to the point. You have gained a subscriber and watcher. Y'all are welcome in Texas anytime.
@markniblack7160
@markniblack7160 2 жыл бұрын
I must say, you came up with a creative and elegant way of making the comparisons. One thing you didn’t mention is that with the expansion fittings there is less flow restriction per fitting than with the crimp on style.
@brianhughes1456
@brianhughes1456 Жыл бұрын
how about with the shark bite fitting, would those too have more restriction?
@Anytus2007
@Anytus2007 Жыл бұрын
@@brianhughes1456 With the regular sharkbite, yes. I have not used the new Sharkbite Pro I think they're called, so I don't know if those work any different. Any type of fitting where the diameter is narrower than the pipe will cause some flow restriction. With sharkbites it has to clamp onto the inside and the outside of the pipe, and that slightly smaller tube on the inside means the fitting is slightly narrower than the pipe.
@richardbateman5344
@richardbateman5344 Жыл бұрын
Loved this video. Your willingness to say I'm wrong (if you would have been wrong) is so refreshing. You can definitely tell you love your work and I for one appreciate a contractor that takes the pride in their craft that you do. Please keep up the amazing videos so us Harry Homeowners don't have to do the trial-and-error at our expense most of us can't afford to things once much less two or three times just to find it doesn't work. Love it guys....
@keithneal3253
@keithneal3253 2 жыл бұрын
The other big advantage of PEX over copper and UPVC that we learnt from the valentine freeze in TX in Feb ,20 when we had no power for 5 days and 9f, that it doesn’t burst, split or crack like the other two. Great product.
@waynerowcliffe6585
@waynerowcliffe6585 2 жыл бұрын
Our kitchen water pipes froze every winter the first four winters we lived in our house (Iowa). Finally got that sorted out, but thanks to PEX we never had to deal with burst pipes.
@163sheriff
@163sheriff 2 жыл бұрын
Hey Stud Pack, Its all about "Friction Loss" more fitting less pressure and that's coming from a retired Firefighter of 25 years. You guys are great keep doing what you do...
@frag0mat1c
@frag0mat1c 2 жыл бұрын
Nice that you took the time to find this out!
@calivalley9056
@calivalley9056 2 жыл бұрын
Great video, I went down this rabbit hole when I did a bathroom remodel. Now everyone can see the difference.
@ronlovell5374
@ronlovell5374 2 жыл бұрын
Dual in-let drop ears (drop ear tees) for loop jets equals less fittings overall! I think the key is a real loop with no 90 degree turns at all, avoiding turbulence and flow loss.
@randymack2222
@randymack2222 2 жыл бұрын
There is probably a dozen different ways to configure the loop, all could have been a different outcome. I'm impressed with the fact you went to the difficulty of testing it, you guys rock...
@williammorris3303
@williammorris3303 2 жыл бұрын
I’m impressed by all the testing , as a plumber I can appreciate the results . Because these are things we want to know
@zTribalstylerz
@zTribalstylerz 2 жыл бұрын
freaking great! what a nice opportunity to do some testing! Great job guys
@Know-Way
@Know-Way 2 жыл бұрын
PSI change for water is about 1 psi per 28 inches of rise. So the bottom ones will flow more than the top with equal pipe lengths and fittings. To equalize them the bottom pipes need to have longer pieces of PEX and OR more 90° fittings to induce drag and therefore pressure drop. This approach however is not linear and the flow rate affects the induced drag. The higher the flow rate of the shower heads the worse the imbalance will be. However these shower heads will likely either be on or off so the flow will be consistent. Feed into the top two first so they have access to the feed with the least restrictions then add a big loop of pex and or 90° fittings before connecting to the lower ones. You'd have to experiment with how much/many for find the right amount of drag for the given flow. In actual use, and with the flow controls on the shower heads, it's all needless overkill. However, if the shower heads are replaced with higher flow units, then it becomes more important. Fun video, thanks! Edited for typo.
@throttlebottle5906
@throttlebottle5906 2 жыл бұрын
2.31 foot of head = 1psi change. as long as they have enough volume to feed it, there should be virtually no difference in that closely spaced setup. now if there was multiple nozzles from floor to ceiling, then yes it would be a nasty issue.
@leonardhall7203
@leonardhall7203 2 жыл бұрын
The manufacturer of the shower heads already solved the problem with the flow valves on each shower head. Making doing anything further than the absolute simplest option is basically like reaching around your ass to scratch your elbow.
@Nug0311
@Nug0311 10 ай бұрын
Great video. As a mechanical engineer I enjoyed watching you trouble shoot this plumbing behavior using the scientific method and some excellent deductive reasoning skills. Subscribed and cheers
@raymitchell9736
@raymitchell9736 2 жыл бұрын
This is the Stud Pack version of Mythbusters! LOL Great work guys. The "H" makes a lot of sense to me as it takes fewer joints and connections and ease of installation. You don't need to make it complicated like that loop...OMG that looked crazy to me
@lostreb
@lostreb 2 жыл бұрын
Stud Pack Mythbusters...A new channel should Stud Pack ever find the desire to expand their KZbin Channels and presence!!!! Great Comment and thank you for the humor!!!
@evenberg8499
@evenberg8499 2 жыл бұрын
Paul should start growing a mustache and wear a beret. 😊
@raymitchell9736
@raymitchell9736 2 жыл бұрын
@@evenberg8499 Yes... I like where this is going... He could be a Jamie, or an Adam... or BOTH! LOL I like Adam's sayings: "Am I missing an Eyebrow?" "I reject your reality and substitute my own" all really good stuff.
@Maine307
@Maine307 2 жыл бұрын
i plumbed and wired my own house, my house, has nothing but PEx expansion Pro- Just like this PEX.. I found it the easiest and strongest.. i did this in2012-2014.. I am glad i chose the right choice.. where I live, in 2012-- Expansion Pro was not used here at all, was very hard to find parts.. I had to ship from out of state. ( mostly on line Sioux chief )The big box stores still to this day, wont carry it... it amazes me. I am glad to see, the link he included was the same kit I bought in 2012.. and the price has held.. good tools seem to last
@MuttMuttOutdoors
@MuttMuttOutdoors 2 жыл бұрын
Used PEX for replumbing the house we bought. Replaced from the meter and installed a distribution box as well. My father was helping to dig the trench and do things with me under the house running the lines and removing the old stuff. He was dumbfounded at how fast I was able to replumb the house once the main line was replaced. Still have to remodel the kitchen and bathroom but they function for now and eventually will be adding a bathroom upstairs along with a master bedroom but it's all currently one big open room. The old setup had a bunch of breaks in the PVC and CPVC lines and crud in the steel lines... Yeah it was that bad. Someone had replaced some of the steel lines from the meter with 3/4" PVC but left some of the 1/2" steel in place at some point and did some fixes here and there with a mixture of PVC and CPVC under the house. Where the 3/4" pvc came in it was reduced then fed into a 1/2" CPVC tee which fed cold to the rest of the house on one side and to the sink on the other... The water heater was plumbed backwards and was cranked to the absolute max as well.
@TD_YT066
@TD_YT066 2 жыл бұрын
I replumbed an RV with Pex-A, lots of test fitting, but when it came time to blind assemble all the joints, it was a breeze, just let the expander hold the end open for about 30 seconds to give you more time to get it into position, have to hold it for a little longer but it really make connecting to somewhere you cant see and can only reach with your shoulder up to the opening, reaching into a near inaccessible space.
@xman4328
@xman4328 2 жыл бұрын
Many MANY tears ago I was hired as a plumber for a kitchen & bath remodel company. I was 17 and I lied about my experience. I barely faked it through two weeks or so,, then I had to plumb a 2 head shower I had never even seen or heard of that before.. The 2 heads were approx 4 ft apart and I fed from one to the other instead of center feeding them.. .. I was fired the next day.. GREAT video.. The proof is always in the pudding!!!
@cbarr0288
@cbarr0288 2 жыл бұрын
I have 3 jets in a vertical line in my shower. The plumbers installed an equalization loop but it didn’t do anything. Bottom sprayer was putting out a lot of water , top was just barely spraying out. I spent an entire day taking apart sprayers and restricting the bottom with plastic washers and reassembling over and over until it was equal. In retrospect I wish they had installed a simple branch with ball valves to control the flow of each one . It would have been much simpler. The equalization loops don’t work.
@zeroheat5787
@zeroheat5787 2 жыл бұрын
@TJP 81 balancing valves and/or circuit setters. In essence, they are the same thing as a valve, but have an indicator which allows you to know how much it is open/closed and a screw to keep locked at desired opening.
@tullgutten
@tullgutten 2 жыл бұрын
The pipe size is probably much to small too feed them all at once. Should probably have it connected on the top first and then longer pipes for the lower ones. Or just change to more restrictive shower heads
@cbarr0288
@cbarr0288 2 жыл бұрын
@TJP 81 how would this differ from ball valves which I had suggested
@mikemorgan5015
@mikemorgan5015 2 жыл бұрын
Loops work in the horizontal and CAN help vertically as well. But generally loops allow for fixtures to be fed from both sides of the loop to mitigate the flow loss at the end of a branch. They won't correct for vertical head differential though. If you have a lot of plastic fittings on your feeder line, they will all add dynamic pressure and flow losses that can be significant. The brass AquaPEX fitting don't do this as their ID is the same as unexpanded pipe ID. It doesn't cost much more, due to the reduction in fittings and labor, to run each fixture back to a main manifold like a breaker box for electrical. The convenience of shutting any single fixture off from one location is a great feature, and makes future remodeling and fixture upgrades/relocations a dream.
@cbarr0288
@cbarr0288 2 жыл бұрын
@@mikemorgan5015 how would you correct for vertical generally , valves (restrictors)?
@mitchkey9747
@mitchkey9747 6 ай бұрын
Job well done!!!! I thought it was cheesy test to begin with - but you two made it very, very informative. Thanks for all your effort and hard work.
@darrinscoilsclouds1498
@darrinscoilsclouds1498 2 жыл бұрын
When cutting off the wrong fitting. Make sure not to scratch the fitting with yours knife. It will cause a leak
@TheRealBobHickman
@TheRealBobHickman 2 жыл бұрын
I love that you guys go the extra mile and aren't too proud to try out alternative approaches. This was really informative, thanks for taking the time to try everything out and share it with us.
@hydrolisk1792
@hydrolisk1792 2 жыл бұрын
"The more bends in the plumbing, the easier it is to stop up the drain." -Scotty I knew team H would win from the beginning because it makes the most sense from a hydraulic stand point. Good job gang, I like this type of video as well as the classic style.
@halunkarecord
@halunkarecord 9 ай бұрын
yo. this has nothing to do with the drain. bends will not stop up the water inlet supply.
@lynkpaul2171
@lynkpaul2171 10 ай бұрын
H won because the point of distribution is entered between top and bottom jets, also, it is important to note that the distances to each jet are equal, so there is equal pressure flow to each. However, you still have the option to use the valves on the nozzles to dial in the exact pressure flowing through all of them simultaneously. Good job and great video guys, keep it up.
@ronlovell5374
@ronlovell5374 2 жыл бұрын
Nice, love how you guys tested it. Loops are done for less fittings because there's specific in-line drop ears with two inlets you can get for it, which I believe just gives you better flow rate.(not sure about even pressure) Also size of the pipe can come into play like using 3/4 pex in entire shower, instead of 1/2 because the fittings with 1/2 inch can really choke the flow rate. Having those adjustable controls on the heads would assist with pressure issues anyway. Great job as always, I'm sure your client is gonna love their new showers regardless.
@chrisosti
@chrisosti 2 жыл бұрын
Pex A fittings are full flow and do not restrict the flow like Pex B or C. Turbulence is a different issue with 90's...
@fixerupperer
@fixerupperer 2 жыл бұрын
I think the client is their business. They are the clients.
@ronh9384
@ronh9384 2 жыл бұрын
Great video guys and as always fun to watch. Something to remember with the Uponor pex A expansion system is that the allowable distance between fittings/expansion rings is dependent on the size pex-A pipe you are using. As an example…. 1/2” Pex-A with the expansion ring has to have a minimum of 2” between fittings… if I remember correctly. And that distance goes up as you go up in Pex-A size. Another nod to the “H” pattern with less fittings.
@travisk5589
@travisk5589 2 жыл бұрын
Be careful cutting those fittings off. The slightest nick in the fitting can cause a leak. I usually cut the expansion ring off then heat the pex to slide it off the fitting.
@hanko5750
@hanko5750 2 жыл бұрын
Yup. With Uponor that is how they instruct to remove the old fitting; cut the ring and heat the PEX. But plastic isn't to be reused
@THEFlea1991
@THEFlea1991 2 жыл бұрын
Wow we got a couple of know-it-all-yet-know-nothings here lol
@xephael3485
@xephael3485 2 жыл бұрын
"slightest nick in the fitting can cause a leak" That's what your mom said the night you were conceived...
@thisisyourcaptainspeaking2259
@thisisyourcaptainspeaking2259 2 жыл бұрын
This is an important fact.
@throttlebottle5906
@throttlebottle5906 2 жыл бұрын
been there done that, third time repairing was the charm 🙄😬
@war_yakerz
@war_yakerz 2 жыл бұрын
GREAT VIDEO!!! Way to include what viewers suggest. PEX as far as i know hasn’t been around for 20/30 years but what do I know… I’m a kayak fisherman… love the fact you and your son are working together. Keep up the great work.
@briankowald6465
@briankowald6465 2 жыл бұрын
That was fun. That first loop was crazy. I thought it was silly looking. The second loop sure used a lot of fittings. I'd go with the H.
@Herby-1620
@Herby-1620 2 жыл бұрын
This video shows a through A-B testing. Trying it "both ways" and evaluating the results. VERY scientific. VERY through. More testing videos should do it this way. VERY good video, and a shining example of how a test should be done.
@choimdachoim9491
@choimdachoim9491 2 жыл бұрын
Extremely important video! If I were doing this double-shower multiple-outlets system in my own home I think I would feed it with 1" pipe, not 3/4."
@stevebabiak6997
@stevebabiak6997 2 жыл бұрын
Not sure that would buy you much if anything, since all of the residential water supply I have seen is 3/4”.
@choimdachoim9491
@choimdachoim9491 2 жыл бұрын
@@stevebabiak6997 True. When I built my home I had a well and used 1" to feed the house. My comment was based on you're potentially running both showers simultaneously and approaching maximum flow for 3/4" pipe.
@choimdachoim9491
@choimdachoim9491 2 жыл бұрын
@@stevebabiak6997 which reminds me; water-hammer wasn't a problem to address in your Auto Garage Buddy's showers?
@stevebabiak6997
@stevebabiak6997 2 жыл бұрын
@@choimdachoim9491 - I am not the one who made this video, don’t know if there are any water hammer issues.
@gombolo8
@gombolo8 2 жыл бұрын
I love your highly scientific testing methods. You're a hoot to watch and not only that, but very educational. Thank you.
@totallynottrademarked5279
@totallynottrademarked5279 2 жыл бұрын
The only problem with this test is that it is an open flow test. You have no back pressure due to the shower heads. Other than that, good work. Fluid dynamics is tricky even on the nanosecond level because you have infinite resistance when a space is occupied but since its constantly in flow you get back pressure which changes resistence at each fitting rapidly.
@InspiredScience
@InspiredScience 2 жыл бұрын
I'm very glad you did this test, to illustrate to people how you can't claim an approach is correct if you don't understand the reason it's recommended in the first place. So many people incorrectly claim that looped plumbing is the correct way to run manifolds for even distribution. Those people don't understand the physics. The misunderstanding is due to the loop approach truly having merit when there is substantial head (resistance) and/or distance in the orifices. However... When you do not need to counteract high-head/distance, you are reducing the overall flow, and the consistency, by introducing turbulence which creates head in a relatively chaotic manner. Worse yet, you can run into issues in the real-world use as a result of turning on/off with loops. Simply put, yes there is a reason for using closed-loop systems in manifolds. However, like anything else, you have to understand the pro's/con's before you can claim that it should be used elsewhere. In this case, it is not warranted and creates issues you wouldn't face with a simpler, less expensive, straight-plumb.
@mikevee611
@mikevee611 2 жыл бұрын
I think that the determining issue is that each 90° fitting has a volume/loss factor of about .9. Further, head pressure (lift) has to be considered. Another consideration is the distance (causing volume to increase) would increase the cost of hot water and response time to adjusting the temperature. The old rules seem to apply here: Fewer fitting and less distance equals better pressure.
@wricker91
@wricker91 2 жыл бұрын
If it was crimp pex the flow restriction will be greater. Expansion no different than copper. Love pex a
@ermingtonplumbing442
@ermingtonplumbing442 2 жыл бұрын
Ya dont get those flow issues with Copper.
@dillardbrown8448
@dillardbrown8448 2 жыл бұрын
Thanks for trying the different ways of doing it and showing the results. I have 9 rental houses and I do the repairs and remodeling myself on my days off from my regular job. Your videos have helped me save time on several projects. Love your videos
@ppomm
@ppomm 2 жыл бұрын
great video guys .. and fun too. ignore all the whining comments. bottom line either way will work fine .. I'll do whatever is most symmetrical and efficient with pipe and fittings in the given circumstance. smooth travels to TX!
@outoftheboxmedic1608
@outoftheboxmedic1608 2 жыл бұрын
I just bought a house and it needed a lot of work. I was looking for videos to fix a problem and found it and I was A StudPack Junkie from the first video!!! Before finding this Channel I was lost, but I am proud to stay that I’ve learned a ton from you two!!!! Guys I absolutely love your videos!!! Your both great at teaching in a way that everyone can learn from. KEEP IT UP!!! Can’t wait for the StudPack House!!! 💪🏽💪🏽💪🏽🏡
@migvinu8620
@migvinu8620 2 жыл бұрын
Loving the project Stud pack water test. We need more of this type of content when possible. Keep up good work guys From NYC.
@jamesmoeller9366
@jamesmoeller9366 2 жыл бұрын
All the right junk, in all the right places! Excellent dialing and testing! Buckets are just as good as a pressure gauge, more show and tell!
@williamdawson6351
@williamdawson6351 2 жыл бұрын
A true balance pressure loop supplies water to both halves of the to equal the pressure out you still only have a loop with a missing supply slide. The Idea is water enters at two points at the ends and the middle sees full pressure.
@Faruk651
@Faruk651 2 жыл бұрын
bs lol
@davidgiesfeldt6650
@davidgiesfeldt6650 2 жыл бұрын
Appreciate that you take the time to analyze the suggestions… net result is the logical and cost effective installation prevailed
@jameshogge
@jameshogge 2 жыл бұрын
It would be very difficult to equalise the pressure between top and bottom jets in this vertical case. If you imagine the jets as being holes in a solid tank of water, there will always be higher pressure lower down due to the weight of the water higher up. To get rid of that you would have to intentionally restrict the lower two jets so there was a pressure drop equal to the increase
@david99j
@david99j 2 жыл бұрын
You could add longer piping to the lower jets to reduce flow and equalize the output of the lower vs the upper jets.
@fixerupperer
@fixerupperer 2 жыл бұрын
I wonder if they upsized to 3/4 pex and fittings going from the valve to the threaded spray adapter for the upper jets. It still restricts at the valve.
@justsaying4195
@justsaying4195 2 жыл бұрын
I just love experiments, I'm taking notes for my project to get things just right too, and to think when I first stumbled on this channel I thought it was just going to be electrical, surprise surprise - keep us with you in your journey's and thank you.
@MIGHTYX2010
@MIGHTYX2010 2 жыл бұрын
Great video content! I was thinking that pressure regulation won't matter too much once the heads are put on because they have water restrictors in them to only allow a certain amount of gallons per minute. So long as you have enough combined pressure which is greater than the amount of heads restrictor valve kind of like the aerator then no matter what type of hookup we go with or the length of hose it's going to be very minimal difference. For instance if each head does one gallon per minute and you have four heads then you just need to be able to have a water supply of more than 4 gallons per minute of water volume and pressure. Same concept as if you run a sink right near the water supply coming into the house versus running a sink 75 ft away at the back of the house if you turn them on at the exact same time you're still only going to have one gallon per minute of water coming through them at roughly the same pressure. Some people out there verify my thoughts. Let me know?
@ADBBuild
@ADBBuild 2 жыл бұрын
I 100% agree. Pressure is created from a restriction. The incoming pressure is constant, so depending on your restrictions (shower heads), the pressure will be equal to the incoming pressure or less, always less if water is flowing. As long as there is enough flow to provide the outputs, the pressure will be equal. With no shower heads, the pressure was probably close to zero, so all you are seeing is what the max flow is.
2 жыл бұрын
@@ADBBuild Well, not exactly. If this is 1/0 system, then it might be fine as it will always feed as much as possible. If it has the water flow control and you can regulate how much you are getting from those, then different pressure loss on each nozzle will result in uneven flow and if you regulate them to be equal at this volume, it will be messed up with different volumes. That's because the main control valve is on the inlet, not on the nozzles and depending on the design you will get more or less even flow to nozzles. So generally if you have flow control, you may not have enough flow to provide the outputs as you stated and this is a valid case for some of those showers.
@GutterClown
@GutterClown 2 жыл бұрын
Really appreciate you spending an extra half-day on the jobsite, testing out a theory and sharing it with the world. As tradespeople, we do this on the odd occasion for apprentices and newbies coming up through the ranks. To do it for Joe Bloggs, random internet person - That's an effort and it's appreciated.
@stevebowser7248
@stevebowser7248 2 жыл бұрын
Great analysis! Its all in the pipe hydraulics. Every time you add a fitting, its like adding more pipe length. Pressure is lost for every foot of pipe length (headloss). So a good rule of thumb is short pipe runs and minimize fittings. Fewer fittings translates to shorter pipe. Key items into the headloss is (of course) pipe length, but reducing velocity. Velocity kills you, if you can get a slightly reduced velocity, headloss can plummet. Easy way to do that is larger pipe. That way just small bump diameter in pipe reduces velocity a great deal (the power of r squared). Your simple H was short pipe run and fewer fittings. I doubt your velocities were too high, and when you put the fittings on, that reduced velocity more which helped. Gravity is also in play - higher up is lesser pressure for sure. Short loops like the right side are nice, but for short runs, the difference are not great. Im working on an apartment site of about 10 acres with one meter. We run a big loop so it balances it all better. Loops are great when you get into fairly long runs (this one is about a 1500' loop). Great content as always, I always look forward to your graat work and I'm sure the Texas project twill be fantastic.
@jeremylunning654
@jeremylunning654 9 ай бұрын
I'm glad you broke down the tests a little deeper. It was driving me nuts how the first test was done lol
@MrBill3474
@MrBill3474 2 жыл бұрын
With just open lines for all four outlets, you will get a completely different result than if you had the restriction of the actual shower nozzles that would provide back pressure on the system. With open lines, the lower two nozzles will have more flow due to gravity, which provides back pressure on the lower two, but none on the upper open fittings.
@kenbrown2808
@kenbrown2808 2 жыл бұрын
it also occurred to me that once the water is shut off, all the water in the system will drain out of the bottom fittings. which means the bigger the loop, the more water will come out of the bottom fittings.
@CARLOSTREUIL
@CARLOSTREUIL 2 жыл бұрын
The real secret is you need to arrange the flow through each nozzle so that the pressure loss in the upstream piping is minimal compared to the flow through the holes in the spray nozzles. If you had done a time study you would have noticed that you have slightly less total water coming out of the 4 nozzles that you had on the 4 open spigots. This is the same principle in laying out a lawn sprinkler system. The water lines need to be sized so that the greatest pressure drop is across the spray nozzles. That way each nozzle sprays the same volume regardless as to where it is located in the piping system. Comments from an LSU Chemical Engineer.
@889Gaming
@889Gaming 2 жыл бұрын
I do more learning from you two than i could from any education given. Great chemistry you have, keep making these great videos.
@GailsonPvPwtf
@GailsonPvPwtf 2 жыл бұрын
How about you try having the water start above all the jets and then T off into the top jets and then right angle into the bottom jets. Like an "n". I feel gravity is affecting this more than the plumbing technique.
@justgivemethetruth
@justgivemethetruth 2 жыл бұрын
The "n" configuration is what I was thinking, the extra pipe would compensate for the gravity assist.
@kerreedrake
@kerreedrake 8 ай бұрын
I’m about to add some body sprays to my shower right now and this was an amazing video. Hats off to you guys. Super entertaining and extremely educational.
@prudencepark3731
@prudencepark3731 2 жыл бұрын
I was on team H. Good job, but nextime you test the water jets wear a big trash bag! 🤣
@franklong6269
@franklong6269 2 жыл бұрын
Great video. I would suggest anchoring your PEX lines with plastic clamps to prevent any water hammer issues. I really enjoy your videos, you do a great job on your homes and I love that you care deeply about doing a quality job. I am a licensed GC in AZ. You do amazing job with these videos.
@christrapp5591
@christrapp5591 2 жыл бұрын
When doing experiments like that, you guys should wear white lab coats 😂😂
@50srefugee
@50srefugee 2 жыл бұрын
"Not what we expected." Always a strong signal that Real Science is in play. Congrats.
@smarternu
@smarternu 2 жыл бұрын
DIRTY, GREASY, TIRED, I don't care what the design is, the fact that I am getting multiple jets in one shower is r a GREAT way to end the day.
@1afly2
@1afly2 2 жыл бұрын
There are few videos on YT that I would rate as "fantastic" this is one of them, I have wondered about this loop vs H for a VERY long time. Nice work, guys!
@JB-jk3ow
@JB-jk3ow 2 жыл бұрын
Put copper unions on all your plumbing fixtures, boom problems solved for repair and replacement. I'm a commercial plumber so any residential plumbing installs make me cringe regardless, respect your multi capabilities though and knowledge
@donna30044
@donna30044 2 жыл бұрын
As is usually the case with such things, the simpler, more elegant the system design, the more better and efficient the outcome. Excellent job, guys.
@4PFuhBenjis
@4PFuhBenjis 2 жыл бұрын
And be careful cutting off those fittings any little nick on the barbs and it will leak 100% , just cut the ring off carefully and the score the pipe a few time and you will pretty much be able to bend the pipe off the fitting . Also wanted to say I love your guy’s videos, u are a dynamic duo and so fun to watch, u guys are the definition of improvise, adapt and overcome . I hope u guys never stop uploading videos, stay healthy and have fun! (P.s. “Uponor” is actually pronounced, OOP-uh-nor rather than youp-uh-nor as u were saying, not that it matters lol), just thought I’d tell u guys.
@billevans3067
@billevans3067 2 жыл бұрын
This was great! :-) Couldn't help but grin through the whole thing. Well done, guys.
@TheZuperDave
@TheZuperDave 2 жыл бұрын
OK, so, two minutes into the video and I'm rocking out with your background track! BTDT with the remod stuff.... just love the channel. Remo-ing a big house right now. Amazing how your content fits my own work! Some day, not now, would love to exchange re: how your content has informed my own remod work.
@SkyroofNova72
@SkyroofNova72 2 жыл бұрын
I ran my last lawn irrigation install as a pressure loop because I had 8 sprinklers on one zone and it ABSOLUTELY made a massive difference for me.
@johnhaller5851
@johnhaller5851 2 жыл бұрын
What size was the pipe? I'm not an expert, but some of my zones have 1" supply while others have 3/4" supply before dropping down to the 1/2" size risers. I would expect the 3/4” supply to not perform as well in zones with heavy flows as compared to zones with misters, and the 1" is probably better for the heavy flows.
@SkyroofNova72
@SkyroofNova72 2 жыл бұрын
@@johnhaller5851 I was renovating the lawn and working with a 3/4 supply that was already run from the front to back of house with 1/2” risers. 1” would have been best but Arizona desert clay is like chipping cement so I worked with what was already there. By closing it together as a loop I had far better pressure and coverage than before between all heads. It was impressive the difference it made.
@SkyroofNova72
@SkyroofNova72 2 жыл бұрын
All I’m saying is for vertical application where you’re lifting water it may not matter, but if you’re horizontal it will equalize each head because you’re on a flat plane.
@ElQuesoGuapo
@ElQuesoGuapo 3 ай бұрын
Great video. On the Texas loop, the left hand pipes flowed less water because of Bernouli's Principle. Some water had to flow past them to reach the right hand pipes. This velocity created a pressure drop at the T fittings. The right hand pipes didn't have a significant amount of water flowing past them, so they didn't experience the same pressure drop. The problem would likely have gone away once the sprayers were fitted.
@speedskater1947
@speedskater1947 2 жыл бұрын
As a heavy equipment mechanic we work with hydraulic pressure where the medium is oil. The true axiom of pressure is that it is resistance to flow. In a shower system you want both flow and pressure and your determinant factor is the water source which is either public water or well water. Which ever source is generated they are both affected by use and in a public water sourced neighborhood the demand factor in general is after 5 PM when the majority use is at its highest. Water companies adjust this aspect by kicking up the pumping at the stations to meet the need, but if the community grows faster than the upgrades, individual performance at homes will diminish. The "pressure test" you are measuring is not truly pressure as in line pressure you are examining impact affect which is more the result of flow rate. When all your open sources are closed in a house the line pressure should be that which your source Public or Well provides. The only true way to establish effective line pressure is to have a flow meter installed inline at the source to measure flow in GPM and PSI. With no use the meter will read zero on the flow side and existing line pressure set from the source, Public or Well. As you turn on or open each outlet i.e.: kitchen, bathroom, shower, tub, toilet flush, or exterior spicket the variation readings will be indicated at the meter. A high quality flow meter besides GPM and PSI will also have a running volume tabulator and therefore can be used to check the accuracy of the water companies flow meter in the junction box. Pressures should drop slightly as flows increase, but in some instances there may be pressure regulators stepping down the water main pressure and maintaining in general 60psi, but even then as usage goes up in the neighborhood and the household maintaining adequate flow and pressure may be hampered. Having line pressure at 60 psi no matter the demand is ideal, but not always maintainable.
@bwiltse2620
@bwiltse2620 2 жыл бұрын
This video was awesome! You guys are the best for reading the comments and putting the theories to the test! This was super fun to watch and I'd love to see more like this. Keep up the great work!
@zzschulzz
@zzschulzz 2 жыл бұрын
It just makes sense that any time you add more of anything - plumbing, electrical, HVAC - you lose volume. Vortexes and friction play a big part in this. On the other hand, thanks for testing this because I won't take that kind of time to do it and it's nice to see the experiment take place.
@MadridMadrid007
@MadridMadrid007 Жыл бұрын
I am about to remodel my shower and needed this info. Great job. The only thing I will be changing is I will not have a shower head installed instead it wall be a rock water fall. I will have 6 jets and on opposite side of each other. 3 on one side with the diverter valve and 3 on the opposite side. I will have fun figuring this one out. Thanks for the info.
@rickdawson4507
@rickdawson4507 2 жыл бұрын
The H Side has less fittings meaning more volume because not lost to too many fittings. I would never plumb a shower valve like the loop side because it is a waste of pipe and fittings. I have been a Plumbing contractor for 46 years and have used Pex since the day it came out. It is way better than copper but I do stub out with Type L copper for angle stops and water heater and for Main water line into the building and irrigation and sometimes manifolds if we decide to make them out of copper like we used to back in the day but now we just use Pex manifolds or make our own.
@JK-fi3zl
@JK-fi3zl Жыл бұрын
LOL. Dad!, you look much more hydrated and thus look healthier at the end of the video. Pleasure watching both of you. Great team!!!
@hu5116
@hu5116 Жыл бұрын
The H is balanced because at each T you get a balanced split. As long as the lengths, diameters and materials are the same, there is no way the H should be unbalanced. HOWEVER, note that the bottom openings are a little lower than the top. They will have a little more gravity pressure, and will handle flow a little more than the top ones (emphasis on little, but over time will add a bit more water which is what you saw). Great vid!
@sandcrabronco
@sandcrabronco 2 жыл бұрын
Not more pressure more velocity, can't change the pressure without consuming energy. Love your videos guys! really liked this one.
How to Size Your Water Lines (PEX & Copper)
17:33
Williams Plumbing & Heating
Рет қаралды 244 М.
How to Install a Shower Valve with PEX A and SharkBite Plumbing - BEGINNERS Guide
20:44
БАБУШКА ШАРИТ #shorts
0:16
Паша Осадчий
Рет қаралды 4,1 МЛН
I'VE MADE A CUTE FLYING LOLLIPOP FOR MY KID #SHORTS
0:48
A Plus School
Рет қаралды 20 МЛН
Who is More Stupid? #tiktok #sigmagirl #funny
0:27
CRAZY GREAPA
Рет қаралды 10 МЛН
10 Reasons Why You'd FAIL a Plumbing Inspection! | GOT2LEARN
7:36
Plumbers Hate Me For Showing You This!
23:28
Fix This Build That
Рет қаралды 621 М.
Zurn PEX-B Expansion vs. Uponor PEX-A Expansion 2020
15:33
Integrity Repipe inc
Рет қаралды 202 М.
PEX-A vs PEX-B - What's the Difference? Which Should You Use?
9:23
Roger Wakefield Plumbing Education
Рет қаралды 760 М.
The Tile Floor SECRET NO ONE Tells You!
45:36
Stud Pack
Рет қаралды 585 М.
PEX Manifold System - Pros and Cons + Tour
12:01
Matt Risinger
Рет қаралды 1,3 МЛН
BUILDING a CURBLESS SHOWER (Recess in Floor Joists)
31:04
Stud Pack
Рет қаралды 1,9 МЛН
4 Plumbing Tricks I Haven't Seen Before!!!
9:19
Matt Risinger
Рет қаралды 1,8 МЛН
Which Is Better Solder or Braze? | Pressure Test
14:35
Roger Wakefield Plumbing Education
Рет қаралды 168 М.
БАБУШКА ШАРИТ #shorts
0:16
Паша Осадчий
Рет қаралды 4,1 МЛН