YOU ARE DOING A GOOD JOB , MOST OF THE PERSON DOES NOT TOUCH IT
@electricalinindustry5 ай бұрын
Thanks keep watching ❤️
@adilakbar3053 Жыл бұрын
Thanks for sharing informative material Sir
@electricalinindustry Жыл бұрын
Thanks and welcome
@anonymus738711 сағат бұрын
This is the formula for cable sizing...not for sizing of earthing conductor. Please review.
@mdafsar5058 Жыл бұрын
The above formula you have mentioned It is IS standard or British Standard
@electricalinindustry Жыл бұрын
IS
@mdafsar5058 Жыл бұрын
Thank you for reply, could you please provide earthing conductor formula according IEC or British Standard
@kakongkea77843 ай бұрын
Dear Sir Please kindly check about the method value calculation conductor sizing I'm following the method calculation below: - (Isc=25kA, K=205 for Cooper Conductor, t=0.5Sec) * We can use formula ((S=Isc*√t)/K) Therefore, S= ((25*10^3*√0.5)/205) =86.23mm² (We can use select follow in the table we have conductor sizing 95 mm²) Many thanks so much!
@electricalinindustry2 ай бұрын
Thanks for watching dear, for calculation kindly check the example again in video for small correction.
@osst126 ай бұрын
For home lightning arrestor, what should be the copper wire of down conductor?
@electricalinindustry5 ай бұрын
Dear it depends upon many factors.
@SURAJPATIL-vg7mc4 ай бұрын
Bhai I value load current lete hai
@electricalinindustry4 ай бұрын
No, short circuit current
@mohitmeena12334 ай бұрын
Bhai aap pakistan Sai ho kya
@electricalinindustry4 ай бұрын
How may I help you
@Akshaypawar-un9wl4 ай бұрын
Is there any standard you are using?
@electricalinindustry4 ай бұрын
This formula is based on IEC 60364 Standard
@panchalprashant8786 Жыл бұрын
Sort circuit cureent kese disid kre?
@electricalinindustry11 ай бұрын
Short circuit given hota h
@md.anisurrahman87085 ай бұрын
What is the reference of this formula?
@electricalinindustry5 ай бұрын
This formula is based on the IEC 60364 standard.
@transparentinfraandenergys55685 ай бұрын
LET US KNOW CABLE CONDUCTOR FOR LED LIGHTS INSTALLATIONS
@electricalinindustry5 ай бұрын
For LED lights installations, the earthing conductor size depends on the total current and fault current requirements. Here are some general guidelines: 1. For LED installations up to 10A: - 1.5mm² (14 AWG) earthing conductor is usually sufficient 2. For LED installations between 10A-20A: - 2.5mm² (12 AWG) earthing conductor is recommended 3. For LED installations above 20A: - 4mm² (10 AWG) or larger earthing conductor may be required However, it's essential to consider the following factors: - Total LED current - Fault current (if applicable) - Distance between LED drivers and earthing point - Soil resistivity (if earthing electrodes are used) - Local electrical codes and regulations
@transparentinfraandenergys55685 ай бұрын
DO COMPLETE CALCULATION WITH PICTURE
@electricalinindustry5 ай бұрын
Sure
@TasleemKhan-sp5xb5 ай бұрын
😢😮😮😮
@electricalinindustry4 ай бұрын
?
@transparentinfraandenergys55685 ай бұрын
COMPLETE THE VIDEO
@mdsadikhusain700710 ай бұрын
Sir If Someone ask me why time short Circuit 0.5 sec why not 0.10 sec what should be response?
@charylucky99819 ай бұрын
All the materials designed for more than 0.5sec solar ,as a thumb rule to avoid the damage we have to maintain 0.5sec
@electricalinindustry5 ай бұрын
The time value "t" represents the duration of the fault current in seconds. This is the time it takes for the protective device (e.g., fuse, circuit breaker) to clear the fault and interrupt the current. Typical values for "t" are: - 0.5 seconds (500 ms) for fast-acting protective devices - 1 second (1000 ms) for standard protective devices
@AjayKumar-ct6ok6 ай бұрын
❤
@electricalinindustry5 ай бұрын
❤️
@transparentinfraandenergys55687 ай бұрын
Unable to understand as nothing is clear about cable ie copper or ALLUMINIUM armoured
@electricalinindustry5 ай бұрын
Both can be use but the size calculation will be different as described in video kindly watch again ❤️
@manishkumargautam16544 ай бұрын
Very boring topic
@electricalinindustry4 ай бұрын
That's why I explained this in very simple mannar.