Easy Guide to Cable Sizing and Cable Calculations

  Рет қаралды 108,721

Sparky Help

Sparky Help

Күн бұрын

How to size electrical cables for various electrical loads using the electrical wiring regulations 18th edition. This step by step guide will guide you through the process for all events enabling you to carry out basic electrical cable sizing for all your needs, such as new shower circuits or just up and coming exam revision for all level 3 students.
Addendum: 2.3^-3 should read 2.3x10^-3 (2.3mV).

Пікірлер: 120
@ahmadirshaid896
@ahmadirshaid896 2 жыл бұрын
from Jordan , i am truly thankful for you to sharing this valuable guides with us and looking forward to seeing more about circuit breakers and fuses selection too according to bs 7671
@sparkyhelp3997
@sparkyhelp3997 2 жыл бұрын
My pleasure!
@mohamedbaghdadi778
@mohamedbaghdadi778 9 ай бұрын
I get this lesson last week, and I didn't understand anything until I saw this wonderful video. Everything became clear and easy. Many thanks.
@sparkyhelp3997
@sparkyhelp3997 9 ай бұрын
Wonderful, Glad it was useful. Please Share with your colleagues. Please Like, Share & Subscribe. Many thanks.
@lukemerriman5574
@lukemerriman5574 Жыл бұрын
This video is the best. It explained it so well & a lot better than my tutors at college.
@sparkyhelp3997
@sparkyhelp3997 Жыл бұрын
Thank you very much, I'm glad you found it useful - I only hope my students look at it and find it helpful! Please, Like, Share & Subscribe
@Hamispeople
@Hamispeople 2 жыл бұрын
Excellent explanation! Really helped me in my Masters electrical design module
@sparkyhelp3997
@sparkyhelp3997 2 жыл бұрын
Excellent - well done
@smilburt
@smilburt Жыл бұрын
Earned my subscription, very clear example, I will defiantly pass this on to the apprentices as i think this would help them a lot.
@sparkyhelp3997
@sparkyhelp3997 Жыл бұрын
Many thanks, others in the pipe line - they are made for the apprentices I teach, if only they would look at them... Enjoy.
@nickmatthews4935
@nickmatthews4935 2 жыл бұрын
great vid! example at the end was a huge help.
@sparkyhelp3997
@sparkyhelp3997 2 жыл бұрын
Glad it helped! Please like and share...
@Oufg103f
@Oufg103f 3 жыл бұрын
I'm doing c&g 2396 in may, so any videos regarding this would be super cool. Great video 👍
@sparkyhelp3997
@sparkyhelp3997 3 жыл бұрын
Good luck!
@solutionbybrain9978
@solutionbybrain9978 2 жыл бұрын
how this smart man couldn't have more subscribers. sadly i hope to have more subscribe thank you for sharing an amazing video
@sparkyhelp3997
@sparkyhelp3997 2 жыл бұрын
I appreciate that!
@michaelcostello6991
@michaelcostello6991 3 жыл бұрын
You explained cable grouping excellently. In effect this is worse than thermal insulation put over cables as each cable can be at 70 degrees so when grouped they are heating each other potentially if they are at full load.
@sparkyhelp3997
@sparkyhelp3997 3 жыл бұрын
Thank you - please read the notes below the table for grouping in BS7671 for other variations on its application.
@simonpoole1492
@simonpoole1492 Жыл бұрын
How then are multiple (more than 16) circuits sized to fit in a single trunking?
@khalidrash5814
@khalidrash5814 Жыл бұрын
Hello I am a follower of your lessons and a big fan of them. I hope that you will show videos explaining the method of calculating the power factor, as well as the correct way to calculate the main breaker, and whether it should be larger than the service provider’s breaker, equal to it, or less in size than it. sincerely Khalid
@sparkyhelp3997
@sparkyhelp3997 Жыл бұрын
HI Thank you, Power Factor is on my to do list - keep watching. Many thanks. Please Like, Share & Subscribe.
@khaledrabea5050
@khaledrabea5050 2 жыл бұрын
Thanks for your great help.. much appreciated.
@sparkyhelp3997
@sparkyhelp3997 2 жыл бұрын
Glad to help
@alancooper7018
@alancooper7018 2 жыл бұрын
Very well explained!
@sparkyhelp3997
@sparkyhelp3997 2 жыл бұрын
Glad it was helpful!
@komyozaw2878
@komyozaw2878 3 жыл бұрын
Thanks for your sharing . Could you help me to advice that when we calculated the Design Current Ib , the power factor is required to include or can omit as this power factor make the result of the Design Current into 1.25 Time when the power factor is included in Design Current Calculation Step .
@sparkyhelp3997
@sparkyhelp3997 3 жыл бұрын
If there is a power factor it must be included in the calculation as the design current will be higher, and therefore the cable will have to carry the extra current. Hope this helps.
@marknewcombe7510
@marknewcombe7510 2 жыл бұрын
This is a very well put video ( and great channel that I have just come across ). I am now designing electrical circuits as part of my job and something I never thought about, until now is - when we design, as you in this video with the step by step guide, how can we be sure that our ZS when verifying after installation will be acceptable? Thanks - great wok. 😊
@sparkyhelp3997
@sparkyhelp3997 2 жыл бұрын
Best of luck! Please Like Share & Subscribe.
@Hamispeople
@Hamispeople 2 жыл бұрын
After calculating the cable size and when attempting to calculate the short circuit current am I correct in saying you need to calculate the resistance and reactance of the cable which is separate from the values in the voltage drop calculations? Do you know where to find the tables for resistance and reactance values? The do not appear to be in BS7671
@sparkyhelp3997
@sparkyhelp3997 2 жыл бұрын
For the vast majority of circuits reactance of the cable will be ignored as it is such a small value it would be insignificant. If you are talking long distribution or transmission cables then the information from BS7671 would not cover this. BS7671 covers low voltage installations. I would suggest seeking information from the cable manufacturer (this is where I go to find the resistance of cables or armouring of cables - BS7671 does not provide resistance of conductors, the On-Site-Guide does but only up to 50mm^2) . I hope this goes some way to answering your question, but the answer is not that straight forward as we could write an entire paper on this subject.
@raquelsapalaran2907
@raquelsapalaran2907 Жыл бұрын
great video tutorial, thank you for sharing your knowledge💌
@sparkyhelp3997
@sparkyhelp3997 Жыл бұрын
You are so welcome, Please Like, Share & Subscribe.
@jayescalante-kz6rw
@jayescalante-kz6rw Жыл бұрын
Just perfect.. Very informative ❤
@sparkyhelp3997
@sparkyhelp3997 Жыл бұрын
Many Thanks, Glad you found it useful. Please Like, Share & Subscribe.
@angelofranklin1
@angelofranklin1 2 жыл бұрын
Thanks for th video, can you confirm that in cases where there is no possibility of overload in respect to usage you would use "Ib" (design current) rather than "In" (.size of protection) when calculating for "It". (tabulated current) e.g Ib/Cg x Ca x Ci etc
@sparkyhelp3997
@sparkyhelp3997 2 жыл бұрын
This is true BS7671 Appendix 4 equation 3,4 & 5 could be used as you have put above. Hope that helps.
@jvd6282
@jvd6282 Жыл бұрын
Hi, thanks very much for your video. My question is, would the calculated Ib be divided by 3 if the circuit were to be a 3 phase supply?
@sparkyhelp3997
@sparkyhelp3997 Жыл бұрын
No use the three phase formula at the start to calculate. Please Like Share & Subscribe.
@NaciMahmut-rf5xf
@NaciMahmut-rf5xf 10 ай бұрын
You need to elaborate on your use of Ib & In in your voltage drop & It calculations. Both can be used depending on the nature of your circuit. If the circuit can be overloaded, you would use the In value. If for a fixed load, you would use Ib.
@sparkyhelp3997
@sparkyhelp3997 10 ай бұрын
This is True, but in this video it has not been covered. One for another video maybe. If I keep adding new ideas the videos are too long, so I have to stop somewhere. But thank you.
@roryn3rdc
@roryn3rdc 2 жыл бұрын
When calculating Ib do I include diversity? Or the value before I do diversity calculation
@sparkyhelp3997
@sparkyhelp3997 2 жыл бұрын
I would tend to apply diversity after the design of the circuit.
@Eren-vz5vb
@Eren-vz5vb Жыл бұрын
Hello are we talking about a a copper or aliminum cable here? Could you tell how does cable size change according to type
@sparkyhelp3997
@sparkyhelp3997 Жыл бұрын
Hi the Cable is copper, calculations can be carried out for Aluminium, but the current carrying capacity of aluminium is lower than copper. Please Like, Share & Subscribe.
@markbramwell2284
@markbramwell2284 2 жыл бұрын
Hi great videos Can I just confirm, when calculating vd , the original Ib of 36.52v is used and not the new It of 60.79v . Is this correct 👍
@sparkyhelp3997
@sparkyhelp3997 2 жыл бұрын
Yes that is correct, it is Ib that is actually flowing through the cable to cause the volt drop.
@davidkamore
@davidkamore 2 жыл бұрын
Thankyou very much sir! I really appreciate.
@sparkyhelp3997
@sparkyhelp3997 2 жыл бұрын
Most welcome! Please like and share. Many thanks.
@joao-ironracers6969
@joao-ironracers6969 2 жыл бұрын
I can use these techniques to calculate the cable of an automotive wiring harness.
@sparkyhelp3997
@sparkyhelp3997 2 жыл бұрын
That is good question, the same principles apply, you would just need to find the actual current carry capacity of the type of cables used from the manufacturer. Hope that helps.
@aidanmochan306
@aidanmochan306 2 жыл бұрын
Hi Sparky, doing an electrical installation design for a health centre at the moment and I'm curious in regards to design current. What would I use for the design current for sockets where I'm not really expecting much permanently connected equipment? such as a changing room/circulation areas. The protective device would still have to be 32A or 20A for radials to comply with appendix H surely? even though the load will never reach anywhere near this? The client(lecturer) hasn't really provided any guidance on what electrical devices are intended for use. I mean I can spec for a typical industrial hoover being plugged in & a few mobile chargers but current is something negligible like 7A for example but Appendix H states it would have to be on a 20 or 32A breaker for radials? Maybe I'm missing something or maybe 20A or 32A radials with negligible load is fine? Hope to hear back from you soon, submission is in 2 weeks lol.
@sparkyhelp3997
@sparkyhelp3997 2 жыл бұрын
Hi Part H of OSG explains that diversity has already been taken into account from historical usage. keep the floor area as per 100m^2 for 32A (A1) RFC providing you do not know the load and the load is not reasonably expected to rise above 32A at any one time. So what I would do is measure the floor area of the design and provide enough A1, A2 or A3 circuits as per the floor area. Areas to give special consideration would be rooms such as kitchens, utility rooms or any with room with a lot of appliances which could be on at the same time. Remember diversity is not an exact science (just read the first couple of paragraphs from OSG maximum demand and diversity). Good luck - Please like, share and subscribe. Many thanks.
@aidanmochan306
@aidanmochan306 2 жыл бұрын
@@sparkyhelp3997 Thanks alot mate, after a bit more digging around I seen I should be Using my cpd rating as design current Ib=In I'm only using radials, no rings. I ended up with something like 31 seperate socket circuits (4 Storey building with 8 on bottom 3 floors and 7 on the 4th) with almost all except for 2 or 3 being A2s 75m squared radials on 32A cpds and the other 2 or 3 Being A3s 50m squared on 20A cpds, haven't fully specced into the cabling yet as it must've took me about 3/4 hours of looking back and forth between the model and drawing my circuits on CAD. I also have to wait for my team members to feed back to me info regarding the lighting and LV stuff such as CCTV and security systems and fire alarms. That way I can get my groupings. I only noticed today when reading appendix A that A1 is for your initial circuits and A2 is diversity to be applied after all circuits have been spec'd to get your main incoming fuse size. I swear I done my college HND coursework from 3 years ago wrong because I'm sure I was applying A2 diversity to my lighting d'oh. I've recently gotten a job as an electrical engineering consultant so it's key I keep refreshing my knowledge and keeping up to date. Thanks again for your help mate!
@simonpoole1492
@simonpoole1492 Жыл бұрын
​@@sparkyhelp3997 How then are multiple (more than 16) circuits sized to fit in a single trunking?
@lemech
@lemech 3 жыл бұрын
Thanks for sharing. In real life, I wonder if electricians do actually do all these calculations, especially for Ca, Cg and voltage drop. Normally, rules of thumb are applied, so for example 20A mcb equals 2.5mm2 cable, regardless of Ca, Cg and voltage drop. Just like to hear what real life electricians do or do not do in practice.
@sparkyhelp3997
@sparkyhelp3997 3 жыл бұрын
A good designer / electrician will take the method of installation and type of cable into consideration. Obviously we can all choose not to take these into consideration, but we are hoping things do not go wrong (and they may not, most of the time) - remember BS7671 can be used in a court of law to provide evidence. The OSG has tables to take some of the design out of installations - you just need to stay in those parameters.
@Vivekvvooz
@Vivekvvooz 2 жыл бұрын
Can you explain why you didn't consider power factor 17:55? For single phase it is V*I*COSPHI rigth ?.....how much load can single phase carry? For beyond 8kw it should be 3phase right ? @sparkyhelp
@sparkyhelp3997
@sparkyhelp3997 2 жыл бұрын
Power Factor only applies if the load is inductive or Capacitive. If power factor is not given (maybe for example an electric heater) it is more than likely a resistive load and therefore power factor is 1.
@x.pv2452
@x.pv2452 2 жыл бұрын
You explain much better then my college teacher that he is supose to be an Engineer, thanks a lot for making this explanation!! If i could I would marry you but unfortunately I'm straight 😄
@sparkyhelp3997
@sparkyhelp3997 2 жыл бұрын
I'm glad it helped. Good luck!
@dimitrisblane6368
@dimitrisblane6368 7 ай бұрын
How about multicore cables like SOCAPEX? 6 circuits on 1 multicore cable. Does that mean that a 2.5mm SOCA cable is downrated from 16A to 9A per circuit just by being bunched up??
@sparkyhelp3997
@sparkyhelp3997 7 ай бұрын
Hi good question, that would be a little more detailed to answer as you would need to read the regulations further. you would also need to know the % load of each circuit as it may be neglected in in certain circumstances. Have fun determining the rating - happy designing. Please Like, Share & Subscribe.
@dimitrisblane6368
@dimitrisblane6368 7 ай бұрын
@@sparkyhelp3997 ah ok. So it depends on the load for each circuit? I'll do some more research. Love the channel it has helped me a lot since I discovered it! Cheers
@Andy-71
@Andy-71 2 жыл бұрын
sorry to sound dumb here but if I have 10 single phase circuits each 7.2kw and I wanted to find the design current for a sub main to feed a board and the supply is 3 phase how do I work that out as obviously I don't just add all 10 circuits up (72kw) as you would if the supply was single phase.
@sparkyhelp3997
@sparkyhelp3997 2 жыл бұрын
Good Question. Assuming it will be split over the three phases, you could divide by three, (this is crude - approx. 100A per phase), or design which phase you want them to be on to be more accurate. If you want to design the sub-main, you may with your more in-depth knowledge what these circuits are, you may want to apply diversity. Really hope that helps.
@Andy-71
@Andy-71 2 жыл бұрын
@@sparkyhelp3997 they are for EV single phase 7.2kw car chargers so can't use diversity. I looked at it as I have 10 circuits each 7.2kw on a 3 phase DB so that's 4 + 3 + 3 so did 4 x 7.2kw = 28.8kw power factor of 0.95 which gave me a design current of 132A.
@sparkyhelp3997
@sparkyhelp3997 2 жыл бұрын
The dilemma of the modern age (EV chargers), it will just need a large supply and a dis-board rated to cope.
@Andy-71
@Andy-71 2 жыл бұрын
In the end I took the total power of 9 of the single phase circuits as these will be balanced over 3 phases, 3 - brown, 3 - black, 3 grey then used a pF correction of 0.95. So 400v x 0.95 = 380v. 7200 x 9 = 64800w / 380v / Sq route 3 = 98.5A. Then the final circuit 230v x 0.95=218.5v. 7200/218.5v = 32.9A + 98.5A So lb = 131.4A
@sparkyhelp3997
@sparkyhelp3997 2 жыл бұрын
I agree with the answer (easier to write down than type in - dont you think) - Good luck
@adamAziz683
@adamAziz683 Жыл бұрын
Thank you for your explanation, could you please tell me how I can download appendix tables of BS 7671
@sparkyhelp3997
@sparkyhelp3997 Жыл бұрын
I'm afraid I don't think you can legally, they are from BS7671. Please Like Share & Subscribe.
@adamAziz683
@adamAziz683 Жыл бұрын
@@sparkyhelp3997 Thank you for your response, so how I can get it legally please ?
@sparkyhelp3997
@sparkyhelp3997 Жыл бұрын
@@adamAziz683 IET web site (Wiring Regulations BS7671 - 2022 {Brown Cover})
@vinnybyrne09
@vinnybyrne09 2 жыл бұрын
Thanks mate :)
@sparkyhelp3997
@sparkyhelp3997 2 жыл бұрын
Happy to help, please like, subscribe a share.
@Mostafa38809
@Mostafa38809 2 жыл бұрын
Thank you very much, although some tables are not complete and also in 12:01 the text ended with " size is " and the rest of words are not there. would you please help us with your reference to let us get the complete knowlege and also help those who are making a research on that topic to get soft copy of the document.
@sparkyhelp3997
@sparkyhelp3997 2 жыл бұрын
Hi the reference material used is the 'IET Wiring Regulation 2018', but a new one is out now dated 2022 Amendment 2. Hope it helps please Like, Share & Subscribe.
@Mostafa38809
@Mostafa38809 2 жыл бұрын
@@sparkyhelp3997 Thank you very much
@dabay200
@dabay200 Жыл бұрын
Great explanation but a slight correction on the way you represent numbers in standard form in your calculations e.g. 2.8mV should be represented as (2.8 * 10^-3)V instead of (2.8^-3)V which is actually 4.6mV
@sparkyhelp3997
@sparkyhelp3997 Жыл бұрын
Yes I know but a pain to go back and add an addendum now. Well done for spotting it though. My copy has already been corrected. Please Like, Share & Subscribe.
@thisarasudarshana5648
@thisarasudarshana5648 Жыл бұрын
Thanku very much
@sparkyhelp3997
@sparkyhelp3997 Жыл бұрын
Most welcome, Please Like Share & Subscribe
@valegio_ch
@valegio_ch 2 жыл бұрын
How do we get the 11.5 Volt drop?
@sparkyhelp3997
@sparkyhelp3997 2 жыл бұрын
It is from the wiring regulations IET 18th Edition (used in the uk), 3% or 5% of the nominal voltage for particular circuits. Hope that answers your question.
@valegio_ch
@valegio_ch 2 жыл бұрын
@@sparkyhelp3997 yes, it does completely answer my question. Thank you!
@berkotropia
@berkotropia 10 ай бұрын
😮What about the 40A circuit breaker after having 60.79A? Do we still keep the In=40A?
@sparkyhelp3997
@sparkyhelp3997 10 ай бұрын
Hi, 60.79A is the It rating for the cable not the circuit breaker. The Load has remained unchanged, therefore the Circuit Breaker is still acceptable. Please Like, Share & Subscribe.
@berkotropia
@berkotropia 10 ай бұрын
Many thanks for your explanation!
@jsphcle
@jsphcle 2 жыл бұрын
good explanation sir
@sparkyhelp3997
@sparkyhelp3997 2 жыл бұрын
thank you, please like, share and subscribe.
@arun4846
@arun4846 2 жыл бұрын
Thanks ❤️👍
@sparkyhelp3997
@sparkyhelp3997 2 жыл бұрын
No problem 👍 Please Like Share & Subscribe.
@sankarbasava7439
@sankarbasava7439 2 жыл бұрын
without using tabular form, how to calculate mV ?
@sparkyhelp3997
@sparkyhelp3997 2 жыл бұрын
Hi you need to know the resistance of the cable conductor over a given length and apply ohm's law. Hope that helps, please like share and subscribe to enable me to continue doing this. Many thanks.
@user-yh7bk7dx7c
@user-yh7bk7dx7c Жыл бұрын
Is ambient temperature still at 70 degrees in thermal insulation ? Also 40 divided by 0.94 x 0.7 = 29.78 or am I wrong ? 🤔
@sparkyhelp3997
@sparkyhelp3997 Жыл бұрын
Hi the conductor temperature is 70 degrees, the ambient temperature is the surrounding air temperature. Put the 0.94x0.7 in brackets 40/(0.94x0.7)= Hope this helps. Please like Share & Subscribe - Good luck
@user-yh7bk7dx7c
@user-yh7bk7dx7c Жыл бұрын
@@sparkyhelp3997 sorry I ment is ambient temperature 30 degrees if wrapped in thermal insulation or would it be greater Na still not getting the calcs but il try work it out lol
@sparkyhelp3997
@sparkyhelp3997 Жыл бұрын
@@user-yh7bk7dx7c Ambient Temperature is what ever the designer deems it to be (or the question setter!) Keep going...
@beardedsparks2825
@beardedsparks2825 3 жыл бұрын
Any reason why you didn't include thermal constraints?
@sparkyhelp3997
@sparkyhelp3997 3 жыл бұрын
Topic to come soon - watch this space
@beardedsparks2825
@beardedsparks2825 3 жыл бұрын
@@sparkyhelp3997 That wasn't a dig by the way, I was merely curious.
@ReviewsBuster57
@ReviewsBuster57 Жыл бұрын
Hello and good day to you! I have been looking on all the internet, KZbin, and I just happen to come a cross your video, my question (if you can able to help me in this little matter!!) I just bought a Fish Finder, and I just want to splice the cable to make it longer, the cable's of the unit they are very thin, could i able to spliced it with a bigger gauge,??? so I can able to reach the 12v Battery. thank you for your expertise, and for your little help on this!! Sincerely the Dummy.
@sparkyhelp3997
@sparkyhelp3997 Жыл бұрын
In order to do this you will have to know the current passing through the cable (it will be small). You could just put a larger cable on (it should not cause a problem - just may look unsightly) and try it. A bit of trial and error, just means your warranty will be invalid. Good luck, hope this has helped in some way.
@Oufg103f
@Oufg103f 3 жыл бұрын
👍👍👍
@sparkyhelp3997
@sparkyhelp3997 3 жыл бұрын
Any thing in particular you think would be helpful?
@Oufg103f
@Oufg103f 3 жыл бұрын
@@sparkyhelp3997 that's the problem, reading examiners past reports earthing, bonding, explaining diversity all seem a problem. 👍👍👍
@stoloveje6144
@stoloveje6144 2 жыл бұрын
I'm going to take a wild guess here, is this from the NEC or the CEC 2018 BOOK?
@sparkyhelp3997
@sparkyhelp3997 2 жыл бұрын
It comes from the 'IET wiring regulation 2018', but a new one is out now dated 2022 Amendment 2. Hope it helps please Like, Share & Subscribe.
@andrewkaindu7281
@andrewkaindu7281 2 жыл бұрын
How can I get that book 📖 excellent work there
@sparkyhelp3997
@sparkyhelp3997 2 жыл бұрын
Many thanks, the book is by the IET, it is the 18th edition Electrical Wiring Regulations (New one out soon) available from Amazon etc
@tiezhongchi
@tiezhongchi 2 жыл бұрын
like and share
@sparkyhelp3997
@sparkyhelp3997 2 жыл бұрын
Thankyou
@arun4846
@arun4846 2 жыл бұрын
🎉
@sparkyhelp3997
@sparkyhelp3997 2 жыл бұрын
Thank you.
@azizurrahman6663
@azizurrahman6663 3 жыл бұрын
thank you for your video it it very good but calculation voltage drop formula minus -3 not gave correct answer please clearly gave formula thank you
@sparkyhelp3997
@sparkyhelp3997 3 жыл бұрын
Hi, my apologies it is raised to the power of x10^-3 or (milli). hope that helps
@azizurrahman6663
@azizurrahman6663 3 жыл бұрын
@@sparkyhelp3997 yes thank you very much now it work many many thank do more Video for calculation please thank you
Everybody Should Know this...  How to Size Earthing & Bonding
25:59
Finger Heart - Fancy Refill (Inside Out Animation)
00:30
FASH
Рет қаралды 28 МЛН
Playing hide and seek with my dog 🐶
00:25
Zach King
Рет қаралды 35 МЛН
Red❤️+Green💚=
00:38
ISSEI / いっせい
Рет қаралды 86 МЛН
BREAKER AND CABLE SIZES FOR ELECTRICAL CIRCUITS.
11:39
LEARN ELECTRICS
Рет қаралды 170 М.
Cable calculation. Calculating the live cable size from BS 7671
18:29
Electrical Student
Рет қаралды 10 М.
Cable Selection Method | Cable size calculation
13:08
Rashid iqubal
Рет қаралды 3 М.
Everything you need to know to solve Voltage Drop Calculations!!
14:57
Craig Michaud- Electrical Instructor
Рет қаралды 218 М.
How to Calculate the cable size and protective device rating
48:16
Basic Cable calcs - A SparkyNinja Webinar
1:18:03
SparkyNinja
Рет қаралды 34 М.
Kumanda İle Bilgisayarı Yönetmek #shorts
0:29
Osman Kabadayı
Рет қаралды 2,3 МЛН
КРУТОЙ ТЕЛЕФОН
0:16
KINO KAIF
Рет қаралды 6 МЛН
Лучший браузер!
0:27
Honey Montana
Рет қаралды 933 М.