IS THIS THE WORST THREE PHASE WIRING YOU'VE EVER SEEN - Does it need a rewire?

  Рет қаралды 62,014

eFIXX

eFIXX

Күн бұрын

Пікірлер: 264
@Jay-fp8iy
@Jay-fp8iy 3 жыл бұрын
This is extremely helpful. I'm an apprentice electrician and this is giving me a fantastic real-world example of a visual inspection. Even though your regulations are a little different from ours, the approach and thought processes are invaluable. Thank you very much for your videos. Greetings from a fellow Anglo across the seas in Australia. Cheers
@efixx
@efixx 3 жыл бұрын
Glad to hear we’ve helped - more on site videos coming soon!
@paultipton743
@paultipton743 3 жыл бұрын
Rewire with maybe a Scheider 3 phase consumer unit like the one in your previous videos, Metal trunking around the outside of the workshop and metal sockets and light switches off it in galv conduit 3 Compartent trunking in office areas,maybe floor sockets depending on room size and use, i know there are so many ways and depends on the use of the building. Smoke detectors,call points. Emergency lighting An Ev charger ready for charging the latest company van in the future whilst doing the office paperwork.
@scabthecat
@scabthecat 3 жыл бұрын
Burgundy toilet. I'd put that as a C3.
@efixx
@efixx 3 жыл бұрын
Fantastic 👊
@efixx
@efixx 3 жыл бұрын
Gary's got his name on it to upgrade his current chocolate brown suite.
@sparkz9803
@sparkz9803 3 жыл бұрын
Who? I mean who? Has a burgundy toilet? That is third world stuff.
@farmersteve129
@farmersteve129 3 жыл бұрын
Could be worse - it could have been Avocado... or even Salmon!
@James-dv1df
@James-dv1df 3 жыл бұрын
@@farmersteve129 That would then be a C1
@matthewsellers82
@matthewsellers82 2 жыл бұрын
Absolutely after 25 years due a full makeover but you really need to go out to the second and third world to have an appreciation for dangerous wiring as opposed to just old and ratty. On one job in S. America, it was the apprentice's job to start the table saw, which ran all day, by twisting two live wires together!
@davidclark3603
@davidclark3603 3 жыл бұрын
I'm afraid I've seen far, far worse than this old 15th edition installation. You didn't have to fit an RCD in those days. It's the tinkering and meddling that helps to make it a mess. And no, you have to use brass or copper for that earth continuity at the intake. Also, the intended future use. Is there any rotating machinery? If so, the lighting has to be flicker free! The future intended use is crucial to the selection and erection of equipment. What a great video that! So real, as it is? Thanks again guys!
@Orgakoyd
@Orgakoyd Жыл бұрын
I’m wondering how would you make the lights flicker free?
@MrHack4never
@MrHack4never 3 жыл бұрын
I would have checked if the plug in the DB was live, because too many people fixing a board for their own needs just work after "no one else will touch it" and "I'll take it down when I move"
@stephendawes8462
@stephendawes8462 3 жыл бұрын
After carrying out a EICR on a commercial property a few years ago, one item I flagged was reduced size neutral conductor in the submain SWA supplies dotted around the premises. Once back in the office I blew the dust off the old BS7671 and set about finding the right regulation. What I actually found was that providing the over current protective device is rated for the load taken it is a pass. In this case all but a few machines actually needed a neutral connection so the load on the neutral was minimal compared with the line conductor in the same SWA.
@efixx
@efixx 3 жыл бұрын
Thanks 🙏- we will investigate further on this.
@markholmes4143
@markholmes4143 3 жыл бұрын
Metal enclosure used as earth conductor Reg 543.2.6.
@vikingofengland
@vikingofengland 3 жыл бұрын
As a DIY'er, this looks good to me.
@efixx
@efixx 3 жыл бұрын
🤣🤣🤣
@ssdpresident7505
@ssdpresident7505 3 жыл бұрын
Me too
@Jay0903
@Jay0903 2 жыл бұрын
Lol
@alunstone
@alunstone 3 жыл бұрын
Do you think if you turn that upsidedown socket the right way up and tighten that burnt neutral connection,that installation might get a satisfactory EICR?😀
@LindaTheLearner
@LindaTheLearner 3 жыл бұрын
Your explanation of the causes/reasons for all the faults you identified, is hugely useful to apprentices like myself. Ta 👍
@paulprescott7913
@paulprescott7913 3 жыл бұрын
Looks like the landlord has not been too concerned about what his tenants do or dont do. It must have cold that day lads, are those Makita heated jackets ?
@efixx
@efixx 3 жыл бұрын
We love the heated jackets 🧥 !
@olatilewashodeinde9095
@olatilewashodeinde9095 3 жыл бұрын
I can watch this video Ten times and still find something new to learn. Thank you guys
@efixx
@efixx 3 жыл бұрын
We’ll be pleased if you do watch it 10 times! - look forward to seeing your comments as this project progresses!
@TheSadcyclist
@TheSadcyclist 3 жыл бұрын
Great to see 2 young chaps getting started as electricians, a few years ago went to look at a new industrial unit for a workshop for us, asked the landlord what we got he said 4 walls a roof and floor , no electrics they all get ripped out after every re let, in the workshops spaces, to ensure the electric is safe for all. Strangely the whole business centre burnt to the ground a year later. Lots of companies lost everything, hope the electrics that where installed where safe. Who Knows.
@TheSadcyclist
@TheSadcyclist 3 жыл бұрын
Oh and it would have been new to us but the building was a converted warehouse dating from the 1860,s.
@Whipster-Old
@Whipster-Old 3 жыл бұрын
Every time I see a unit like this I think to myself, "I could put an X barrel brewery in there". I think I'd get lightly toasted in this one!
@efixx
@efixx 3 жыл бұрын
Ideal for a brewery! -plenty of power
@chrisrussell5682
@chrisrussell5682 3 жыл бұрын
Urm I’d look to rewire with the use of of 75x75 steel trucking to the left hand side of cupboard new Hager three phase db. Tray up from there up to basket then onto light fittings, high level trunking steel pipe drops to outlets ect...
@efixx
@efixx 3 жыл бұрын
Stay tuned !
@chrisrussell5682
@chrisrussell5682 3 жыл бұрын
@@efixx oh and steel Copley to lol 😂
@stevecraft00
@stevecraft00 3 жыл бұрын
Rewire in galv trunking at 8ft around the unit, and galv conduit drops and risers to the sockets and lights.
@petermichaelgreen
@petermichaelgreen 3 жыл бұрын
It's clearly suffered from a fair bit of dubious work and a fair bit of wear and tear. On the other hand i'm not seeing things like rubber cable or green goo. The question is once you strip out the damaged stuff and the bodges, is there enough of an installation left to be worth saving? and is the installation what the new occupants of the property want/need?
@efixx
@efixx 3 жыл бұрын
Looks like it’s time to start again with this installation stay tuned.
@carlbigeasy
@carlbigeasy 3 жыл бұрын
I've got that plug on my 20 year old jigsaw which is currently held together with tape... I've been meaning to swap it since 2009 😇
@tobysherring1369
@tobysherring1369 3 жыл бұрын
Lovely label but why did they use the / symbol in the middle of out/side and flood/light?
@efixx
@efixx 3 жыл бұрын
We pondered this for a while perhaps they don’t know how to use the label/printer.
@alanwalton5735
@alanwalton5735 Жыл бұрын
5 mins in and everyone can see cause for rewire. Thank you for carrying on to highlight further nastys.
@ironknobsteelworks4063
@ironknobsteelworks4063 3 жыл бұрын
Electricians love Picking apart substandard work.
@sergiofernandez3725
@sergiofernandez3725 3 жыл бұрын
If the correct terminology is CPC why do lots of places sell Twin & Earth?
@filipe.skunk8
@filipe.skunk8 3 жыл бұрын
Who told you CPC is the correct terminology? 😂
@Nigel1969
@Nigel1969 3 жыл бұрын
ahhh the single phase cu is a road map for UK motorways :)
@dae8864
@dae8864 3 жыл бұрын
Have you checked if there is a RCD?
@efixx
@efixx 3 жыл бұрын
The search continues 🤣
@petertallowin6406
@petertallowin6406 3 жыл бұрын
I would love to see you guys on that re-wire. :) You work so well together. Excellent video.
@cprfenom
@cprfenom 3 жыл бұрын
Its worth noting that if the sockets were installed in 1992 then it may have been designed under the 15th edition and not required? Does 133.1.1 not cover SY as it has a IEC standard? Overall I agree that it needs a rewire based on the issues at the board alone.
@anthonyschofield7807
@anthonyschofield7807 3 жыл бұрын
Nope I saw one in an electroplating works that was far worse,the guy from HSE took one look and pulled the main fuses
@efixx
@efixx 3 жыл бұрын
Great comment 👍
@totherarf
@totherarf 3 жыл бұрын
I would be amazed if an HSE guy was authorized to remove main fuses! ...... but I think he would have had the phone number of those who are! ;0)
@anthonyschofield7807
@anthonyschofield7807 3 жыл бұрын
@@totherarf This guy was a factory inspector,he put elbow length rubber gloves on,turned the main fuseswitch off
@anthonyschofield7807
@anthonyschofield7807 3 жыл бұрын
@@totherarf and then pulled the fuses,he knew what he was doing
@totherarf
@totherarf 3 жыл бұрын
@@anthonyschofield7807 So he operated a switch? ... Diferent countries different rules! In the UK the customers do not own the cutout and it is illegal for anyone not authorized to operate it!
@seandempsey9396
@seandempsey9396 3 жыл бұрын
MICKY MOUSE had been at it again 😂. Wow what a crazy mess of an installation. I would just rip it all out and start again from scratch. Great video guys very interesting as always Thank you.
@efixx
@efixx 3 жыл бұрын
Thanks 🦾👍
@sparkz9803
@sparkz9803 3 жыл бұрын
Good reply mate.
@thomasbonse
@thomasbonse 3 жыл бұрын
You'd spend more time trying to determine what is salvageable than it appears it would take to just start fresh.
@andysims4906
@andysims4906 3 жыл бұрын
The most common things I see on 3 phase installations is people still using the black in multi core cables as the neutral. A couple times I have seen main tails brown , brown and blue used as the 3 phases and a blue with black tape used as the neutral.. It was complete madness ever changing our old colour system
@alanspooner4659
@alanspooner4659 2 жыл бұрын
I pondered this years ago, Black for newtral, Red for danger, Green for earth. Then i met a bloke who was refused an electricions apprenticeship on the grounds he was RED GREEN colour blind! There are about 10% of the MALE population with this condition, how dangerous is this!!!
@SavedByFaithInJesus
@SavedByFaithInJesus 3 жыл бұрын
Greetings from across the pond in the USA. I love your reactions to what you find inside the boxes... It's like I'm watching me and my coworkers with British accents... "Wood screws." "Two screws". cheers mates.
@Reaktanzkreis
@Reaktanzkreis 3 жыл бұрын
Bugger! What a mess! You should convince the Landlord to do your job. A suitable 3ph Consumer unit and a meter box with with integrated incomer switch, equipotential bonding rail and proper earth rod. A complete new wiring and lighting with energy saving L.E.D. fixtures . And of course to the latest standards.
@enriquedmu1
@enriquedmu1 3 жыл бұрын
Maroon toilet should be given to the parachute regiment. Love anything maroon (or burgundy, close enough)
@efixx
@efixx 3 жыл бұрын
It’s yours we’ll have it ready for you to pick up when you take on the electricians challenge. www.efixx.co.uk/electricians-challenge
@09weenic
@09weenic 3 жыл бұрын
5:00 - I remember fitting that type of Next Test labels at Forestry Commision properties in 1995 😃
@garethblake3941
@garethblake3941 3 жыл бұрын
Hi, excellent video yet again. I worked for the NHS in a fairly large hospital in a maintenance capacity for many years and insert 13amp socket outlets were always an issue like you observed in your video. Seen similar installations not good so looks like a total rewire is in order, keep up the good work and stay safe.
@JBinthesticks
@JBinthesticks 3 жыл бұрын
We have a 100 Amp 3 Phase supply to our home, rest assured it is competently fitted. This is scary!
@billdoodson4232
@billdoodson4232 3 жыл бұрын
Yes we have as well. When we moved the electricity meter from the cellar to the side of the new garage, I asked Yorkshire Electricity, as was, how much a 3 phase supply would be instead of the single phase. Same price £70.00, no brainer really and 28 years on I probably need to have a look at an upgrade to the main Square D 3 phase board. We have had two single phase consumer units in that time fed from the 3 phase. All the machinery in the garage is 3 phase. Rather fancy the new Schnieder Acti9 Isobar P.
@JBinthesticks
@JBinthesticks 3 жыл бұрын
@@billdoodson4232 we are on 2 KQ boards and 2 Easy9 consumer units, it's a complex system. Nothing compared to the system we took out, it's an ex RAF control tower!😀 No radar, radios or airfield lighting to run now fortunately.
@TheChipmunk2008
@TheChipmunk2008 3 жыл бұрын
I don't see using the steelwork of the box as CPC as a real issue provided the connections are tight and the CSA is adequate (approx 7x the required size of copper). The rest of it makes that a bit of a moot point though! It's a shame the UK regs don't have phrasing like the US NEC does for 'workmanlike installation' or similar wording. Something else I see that others may not pick up on, the BT distribution point wiring being right next to the SY feeding that 3ph socket. (separation of services) Also SY: no BS number, by using it you're taking responsibility for it being suitable. I don't like it outside of industrial control.
@Orgakoyd
@Orgakoyd Жыл бұрын
Would you recommend regular 5 core flex on 3 phase sockets/plugs?
@TheChipmunk2008
@TheChipmunk2008 Жыл бұрын
@@Orgakoyd Depends what you mean by regular.... H07 RN-F should be fine for most use, SY has its place too despite not having a BS number....
@ElliottVeares
@ElliottVeares 3 жыл бұрын
What is the main issue with using SY cables on final circuits providing they are terminated correctly and meet BS7671 standards?, Twin and earth which of course is permitted would provide no more protection than a SY cable does?
@efixx
@efixx 3 жыл бұрын
SY is one of those grey areas because of the standards it’s manufactured too.
@bramcoteelectrical1088
@bramcoteelectrical1088 3 жыл бұрын
biggest issue is there tested to TUV standards with dubious ratings 😆 🤣 Bs standards for a reason 😴 🙄 would be a deviation on certifcate... ideally only using s/y or y/y for control cables
@MadMetalShop
@MadMetalShop 3 жыл бұрын
Post more electrical horrors! I like to see what jacked up stuff people do 😂.
@efixx
@efixx 3 жыл бұрын
On it !
@EXFElectrician
@EXFElectrician 3 жыл бұрын
Great video, show that the visual inspection is just as important if not more so .
@tww5719
@tww5719 3 жыл бұрын
Think who ever had the unit before new a mate down the pub,waste of time doing a test ,turn it off and put a danger label on it
@efixx
@efixx 3 жыл бұрын
Agh yes the pub electrician ⚡️
@artisanelectrics
@artisanelectrics 3 жыл бұрын
Glad to see Gaz brought his Tesla Model X!
@efixx
@efixx 3 жыл бұрын
That’s his “mid week motor”
@artisanelectrics
@artisanelectrics 3 жыл бұрын
@@efixx 😂👍
@Alan.Moffat
@Alan.Moffat 3 жыл бұрын
Does it matter what phase live you use when creating a single phase outlet from a 3 phase incoming?
@alinili5569
@alinili5569 3 жыл бұрын
I do for insurance company and do some time for fire brigade and 8-out of ten. It’s loose neutral And never seen any overload conductors But what you see it’s. Very good and safe compared to what we see On daily and when Most of landlord and owner don’t care they say it’s been working all these time. And it’s ok. Money it’s tight Until something goes wrong Be surprised what photos we have. Shocking
@hein_mcleod
@hein_mcleod 3 жыл бұрын
Just started with my journey to become a electrician and this is very interesting to watch. Thank you for sharing this!
@hayleyanne3516
@hayleyanne3516 3 жыл бұрын
Same I'm on.my way work know go help with a 16mm 5core swa omg my poor nails
@Elberto71
@Elberto71 4 ай бұрын
Talking about task lighting, my employer has recently fitted PIR sensing led lights, they are set to turn off after 10 seconds if movement is not detected. Not ideal when I work a 170 ton press 😏
@nosferatu8293
@nosferatu8293 3 жыл бұрын
Excellent video and it's really highlighted what to look out for when thinking about renting a small unit. Thanks.
@bernardgarrett3897
@bernardgarrett3897 3 жыл бұрын
Can you two please confirm that you didn't do the initial installation?
@claas6504
@claas6504 3 жыл бұрын
I'd install luxna led batten fittings, with gewiess industrial sockets, Hager DB and Hager M/C sockets and switches. That's what I like! 👍
@bramcoteelectrical1088
@bramcoteelectrical1088 3 жыл бұрын
hager all the way ....or acti-9
@keirstitt8277
@keirstitt8277 2 жыл бұрын
"Out/Side Flood/Light" is that for out or side? and does it light or does it start a sump pump for flooding?
@HA05GER
@HA05GER 2 жыл бұрын
My mates unit the meter tails are loose can just pull them out. Has a pound meter makes it easy to by pass but can't believe it was left like that.
@9plusinstalaciones
@9plusinstalaciones 3 жыл бұрын
Looks Really Nice.
@efixx
@efixx 3 жыл бұрын
when the sun shines no one will notice !
@9plusinstalaciones
@9plusinstalaciones 3 жыл бұрын
@@efixx 🤣🤣🤣
@MadMetalShop
@MadMetalShop 3 жыл бұрын
In the states you could most certainly fail a inspection for non workmanship appearance. It's a grey area usually left to the discretion of the inspector. Our NEC states all work must be finished in a neat workmanship manner.
@efixx
@efixx 3 жыл бұрын
Sounds like a great term to add to our Regulations!
@MadMetalShop
@MadMetalShop 3 жыл бұрын
@@efixx don't get me wrong as long as everything else meets code here its pretty hard to fail an inspection based on workmanship appearance. You you basically have to totally not care and try to make it messy enough to fail. Most honest professional electricians here do take pride. Messiness is usually the result of a general contractor or builder. Im neither just a homeowner who does his own work and lives to learn.
@clydeceniza2521
@clydeceniza2521 3 жыл бұрын
@@efixx It sounds fancy and technical at the same time
@holmesjunction
@holmesjunction 3 жыл бұрын
Two comments - Landlords legal responsibility to ensure supply is fit for use before reletting unit (or was it a 'deal')? Cables strapped to telephone cable providing 'correct' seperation (ok, only for a short distance,...... but)?
@grumpygit447
@grumpygit447 Жыл бұрын
Have found in the past many factories use there so called maintenance man to fit electrics for them as it saves in paying for an electrician and test sheets just as many householders buy from diy stores and try doing there own electrics
@robertwilliamson3934
@robertwilliamson3934 3 жыл бұрын
Is your safe isolation switch it off and that will do !
@efixx
@efixx 3 жыл бұрын
Close the door and walk away.
@thomasbonse
@thomasbonse 3 жыл бұрын
@@efixx Why walk? This looks more worthy of a brisk jog, or sprint. 😉
@timhoward7037
@timhoward7037 3 жыл бұрын
Good job - a few bonding questions come up in my mind - incoming services, structural steel, steel trunking, and maybe supplementary for that steel sink as no RCDs. Clearly a rewire.
@westinthewest
@westinthewest 3 жыл бұрын
The electrical industry in the UK needs a re-wire.
@09weenic
@09weenic 3 жыл бұрын
Explain please 🤔
@westinthewest
@westinthewest 3 жыл бұрын
@@09weenic This standard of wiring is typical in the UK. We have organisations like the NICEIC who issue qualifications such as 3-day '18th Edition Full Course' with 'no formal entry requirements'. Successful candidates litter the country with unterminated CPCs and half-completed certificates. Have a look on David Savery's channel to see what happens when you report dangerous work to one of the governing bodies. He was not impressed. I think the industry needs to take responsibility for what we've seen in this video.
@BigG3686
@BigG3686 3 жыл бұрын
Was a blacksmith the previous owner
@efixx
@efixx 3 жыл бұрын
Something related to horses sums this job up
@richardtaylor4240
@richardtaylor4240 3 жыл бұрын
On the metalclad socket, would it not be better if the CPC were wire directly to the terminal on the socket outlet?
@whitebeltlyfbjj3393
@whitebeltlyfbjj3393 2 жыл бұрын
🤣🤣love watching these vids....always helpfull...upcoming electrician here
@againstalloddstherussiansg3206
@againstalloddstherussiansg3206 3 жыл бұрын
Storage of "ANT killer" (and the like) in the electrical panel is unacceptable.
@efixx
@efixx 3 жыл бұрын
🤣
@againstalloddstherussiansg3206
@againstalloddstherussiansg3206 3 жыл бұрын
@@efixx Sorry for my English
@bramcoteelectrical1088
@bramcoteelectrical1088 3 жыл бұрын
ant regulations 123.790.01 "no compent ant can go near a shitty fitted db without permission from the ant powder distribution board operator"
@andrewyeo2818
@andrewyeo2818 3 жыл бұрын
Plug on the twin and earth . Oh no you have just knocked off the power to the server room 😁
@Millionaires.Empire
@Millionaires.Empire 3 жыл бұрын
i don't know about the UK but in The Netherlands you can earth or ground metal boxes just fine
@arcadia1701e
@arcadia1701e 3 жыл бұрын
Get a nice Schneider D IKQ board in there, or an isobar / p. SY replace with armored or tuf sheath, But yes the entire thing needs taken down to the tails and re done. Its not saveable.
@pauljohnson4590
@pauljohnson4590 Жыл бұрын
was there ever an update on the re-wire?
@jkelectrical
@jkelectrical 3 жыл бұрын
In Australia, all cables (single or double insulated) should be installed in conduit or similar to a height of 1800mm if exposed to consumers.
@alunroberts1439
@alunroberts1439 3 жыл бұрын
That all looks good some jobs I have seen are much worse
@timhoward7037
@timhoward7037 3 жыл бұрын
Possible issue with proximity of the telephone DP wiring (band II) and the circuits around it. Reg 528.1 ?
@waithereivegonetogethelp3240
@waithereivegonetogethelp3240 Жыл бұрын
If you're going to be technical, no one should be using be using SY flex anyway, as it has no BS number and is therefore not covered by the regs. I've seen it used a lot on AC systems, quite often outside, however its also not UV rated and goes white and brittle when exposed to sunlight for a few years. I don't know why anyone uses it, anyway, as a result of it not being covered by the regs there's no requirement to earth the wire reinforcing, so technically its not code-able. however there's plenty of C2s in this and a myriad of C3s!
@bikecrash611
@bikecrash611 3 жыл бұрын
Another great video guys! Plenty of hidden gems ⚡
@unboxme4803
@unboxme4803 3 жыл бұрын
You guys are hilarious 😂
@paultipton743
@paultipton743 3 жыл бұрын
I'm wondering if the original test was at the suplly before the consumer unit and other installation was installed. Did see a Hager 3 phase switch feeding another 3 phase switch in the same enclosure?
@johnwaby4321
@johnwaby4321 3 жыл бұрын
Great love it 😂😂. Now you know what we have to contend with 😂👍👍👍👍
@choatdean636
@choatdean636 3 жыл бұрын
No mention of emergency lighting ?
@haldo691
@haldo691 3 жыл бұрын
Not uncommon to see a small neutral to a meter and the main neutral connected straight to the cutout
@efixx
@efixx 3 жыл бұрын
Well spotted thanks 🙏
@OkenWS
@OkenWS 3 жыл бұрын
Seen it a few times when I was in the meter business and one of the problems is a sub 16mm unbushed neutral conductor leaves the terminal exposed underneath - straight off the tools for that.
@robertbreen7227
@robertbreen7227 3 жыл бұрын
I notice you commented about not earthing the braiding on the SY cable. The braiding is there for screening more than earthing no? I’ve certainly never earthed it, nor have I ever seen it being earthed in any application.
@robertbreen7227
@robertbreen7227 3 жыл бұрын
Although, I’ve also never used it in a final circuit as it’s non-standard and doesn’t comply if memory serves me correctly.
@shavermcspud
@shavermcspud 2 жыл бұрын
@@robertbreen7227 SY absolutely has to be Earthed at the braiding point of termination/glanding , although classed as a "control cable" its designed for usage in fixed applications up to 500V, if a live conductor was to be pierced to the braiding and no bonding was present, the whole outer sheathed braiding would be come live, its no different to SWA.
@robertbreen7227
@robertbreen7227 2 жыл бұрын
@@shavermcspud It’s completely different to SWA - unless you can find a regulation that says it’s usable for LV applications as I’ve never been able to find a table for it.
@garrybt1
@garrybt1 3 жыл бұрын
Seen a lot worse than that, try coming down to London 😱
@claas6504
@claas6504 3 жыл бұрын
Remember "Does it Blend?" Introducing "Does it need a Rewire?"
@advertslaxxor
@advertslaxxor 3 жыл бұрын
With the loose conductor in that socket, I think "Will it Burn?" is more appropriate :D
@bernardgarrett3897
@bernardgarrett3897 3 жыл бұрын
Congratulations - What a fascinating video. Thank you
@paultipton743
@paultipton743 3 жыл бұрын
Just about filled a code sheet with the supply consumer units alone! With the Sy flex I have never used it myself and I don't know if its suitable for outdoor use but I have seen similar cable with the same outer insulation on a communal lighting installation which came from a building then through ducting under a private road to street lights in a carpark the other side where I was asked to refix on the wall where the building was as the cable cleats had come away and i found the outer sheath was crumbling off from exposure to the sun and weather just leaving the steel wires
@TheFool2cool
@TheFool2cool 3 жыл бұрын
Yeah I find SY cable outside is unsuitable most of the time, not sure how those HVAC boys get away with it so often
@davidfaraday3085
@davidfaraday3085 3 жыл бұрын
A bit off-topic but I wonder what you think of a recent use of CY cable in an installation I know of. The cable carries 230V mains fused at 6A, a 24V AC alarm relay circuit, a 0 - 10V DC control signal and two circuits for NTC thermistor temperature sensors, all in a single 12-core 0.75 mm CY cable. Is that acceptable? Personally I'd have segregated-out the mains and low voltage circuits into separate cables.
@efixx
@efixx 3 жыл бұрын
Was the application part of a process line or machinery?
@davidfaraday3085
@davidfaraday3085 3 жыл бұрын
@@efixx Its part of an HVAC system. The cable connects the system control box to one of the duct-mounted heaters. Three-phase power for the heater elements is supplied by an SWA cable direct from the DB, but mains power for the power-control electronics and contactor comes via the CY cable from the controller. This is the way the contractor installed it, but having mains and control signals in the same cable seems to me to be in breach of the segregation of LV and ELV requirements of BS7671.
@bramcoteelectrical1088
@bramcoteelectrical1088 3 жыл бұрын
ohhhh there's a very well known chicken place that I did qn eicr on the 200amp main from the 200amp switched isolator to the 72way db was in.... S/Y have a picture if you want bodge of the week lol
@enriquedmu1
@enriquedmu1 3 жыл бұрын
You nice and toasty, modeling those makita jackets. AH HHAARR!
@efixx
@efixx 3 жыл бұрын
Never leave home without them! - Gary is on the shortlist for the next Grattan catalogue.
@efixx
@efixx 3 жыл бұрын
New collection “Grandad at Grattan”
@enriquedmu1
@enriquedmu1 3 жыл бұрын
@@efixx and i think he would do a fantastic job! That smile will break a few hearts!
@Ste2023
@Ste2023 Жыл бұрын
Love it eefix More of these visual on the spot .. Inspection For us beginners 👌💪
@darkdepth1991
@darkdepth1991 3 жыл бұрын
Only one thing to do, pull the main fuses and start again XD, Is this going to be the Efixx industrial unit 2021 ?
@timhoward7037
@timhoward7037 3 жыл бұрын
Are they single insulated tails going between cut-out and meter?
@ChristmasCrustacean1
@ChristmasCrustacean1 2 жыл бұрын
"I don't think we've found anything salvagable" a couple of backboxes maybe
@markrainford1219
@markrainford1219 3 жыл бұрын
So, if your CU lid has got a stripped screw hole do you advocate leaving the hole empty, replacing the entire CU, or putting in a woodscrew?
@efixx
@efixx 3 жыл бұрын
If you look at some of our other videos we found another plastic CU with two wood screws - just seems to be a trend.
@sparkz9803
@sparkz9803 3 жыл бұрын
Unfortunately I have seen worse.
@efixx
@efixx 3 жыл бұрын
Wow - hope you managed to turn the situation around!
@sparkz9803
@sparkz9803 3 жыл бұрын
What I did do is tell the CEO that he should employ professionally trained personnel if he expects to get an NICEIC accreditation. Then advised that he invests in a calibrated crimping system rather than his staff hammering non insulated terminals onto cores against concrete. As they say in the scriptures, some fell on stoney ground. I only lasted up to payday, then exited stage left.
@kevinpickett7249
@kevinpickett7249 3 жыл бұрын
Lol first thing lads was NO PROVING DEAD ( I know we only do it on inspection day though 😏) I have seen plenty worse
@philipshanahan4228
@philipshanahan4228 3 жыл бұрын
I presume that's outdoor rated t & E on the bulkhead.
@efixx
@efixx 3 жыл бұрын
by the the lichen spread along the full length it will be!
@mp-xt2rg
@mp-xt2rg 3 жыл бұрын
Its interesting to see how things are done across the pond. I'm surprised to see such small capacity in an industrial setting. Most houses around here are 200amp service.
@efixx
@efixx 3 жыл бұрын
Power wise it should be similar as our voltage is 230vac single phase 400vac across phases.
@craigbutler6243
@craigbutler6243 2 жыл бұрын
USA volts is 120, higher current. UK volts is 230, lower current
@mp-xt2rg
@mp-xt2rg 2 жыл бұрын
@@craigbutler6243 kind of? USA is 120v and 240v all houses are 240v from the pole outside. Most houses here are 200amp at 240v or 400amp at 120. All the high current appliances run on 240 though, ac, oven, stove, exc
@craigbutler6243
@craigbutler6243 2 жыл бұрын
@@mp-xt2rg unusual, but why not.
@mp-xt2rg
@mp-xt2rg 2 жыл бұрын
@@craigbutler6243 what's unusual?
@5nowChain5
@5nowChain5 2 жыл бұрын
That looks fine, when compared to East European (former Soviet Block countries / still outside EU) wiring. A Rats nest of mixed up coloured mains cables that would give you nightmares.
@ABRUSAHAELEKTRIK
@ABRUSAHAELEKTRIK 3 жыл бұрын
Nice sharing.
@darrenfreeman6205
@darrenfreeman6205 2 жыл бұрын
Great video 👍
@efixx
@efixx 2 жыл бұрын
Thanks
@anthonybragg
@anthonybragg 3 жыл бұрын
The original installation looks around the 15th and is worn, tired aged, etc. It has had poorly installed additions and alterations to suit occupiers over the years. I think that there could have been an original 3 phase D.B. with the single-phase circuits eg lights and power. Protective devices for this board are no longer available eg 3 phase MCB for the 3 phase socket so this lash-up was done as the cheapest option.
@lesmoor001
@lesmoor001 3 жыл бұрын
how often should it be tested ?
@90dfender
@90dfender 3 жыл бұрын
Oh yes the old double screw flex arresting take the shortest route cable clip no glander ip rating type attack. Sweet who says a mate they know does not no what there doing and all for 3 pints.
@carlbigeasy
@carlbigeasy 3 жыл бұрын
You don't need RCD protection on an industrial socket outlet providing it meets criteria
@efixx
@efixx 3 жыл бұрын
Its difficult to avoid RCDs on new installations -
@efixx
@efixx 3 жыл бұрын
www.efixx.co.uk/Know%20How/requirements-for-industrial-socket-outlets
@Nigel1969
@Nigel1969 3 жыл бұрын
wow a new type of cpc junction box LMAO
@bramcoteelectrical1088
@bramcoteelectrical1088 3 жыл бұрын
early wago box...
WORST DIY ELECTRICS I'VE EVER SEEN! 🤯
22:52
Artisan Electrics
Рет қаралды 666 М.
АЗАРТНИК 4 |СЕЗОН 1 Серия
40:47
Inter Production
Рет қаралды 1,2 МЛН
The CUTEST flower girl on YouTube (2019-2024)
00:10
Hungry FAM
Рет қаралды 39 МЛН
Секрет фокусника! #shorts
00:15
Роман Magic
Рет қаралды 63 МЛН
A look inside a British home electrical panel.
18:07
bigclivedotcom
Рет қаралды 600 М.
LEWDEN CONSUMER UNIT with DOUBLE POLE RCBOs
13:42
eFIXX
Рет қаралды 40 М.
Smart Meter Disaster!!
16:33
Rygol Electrical and Renewables Bristol
Рет қаралды 344 М.
10 Common Mistakes DIYers Make In Circuit Breaker Boxes
13:55
LRN2DIY
Рет қаралды 2,4 МЛН
Would you use a WAGO 221 CEILING ROSE?
10:26
eFIXX
Рет қаралды 68 М.
U.K. Electrics SUCK! This is what we should be doing…🇫🇷
19:17
Artisan Electrics
Рет қаралды 206 М.
Electrical Wiring in Spain is SO Different
13:49
eFIXX
Рет қаралды 218 М.
АЗАРТНИК 4 |СЕЗОН 1 Серия
40:47
Inter Production
Рет қаралды 1,2 МЛН