Electrical Engineering: Ch 13: 3 Phase Circuit (23 of 53) Balanced Y-Delta Circuit: Ex 2

  Рет қаралды 59,718

Michel van Biezen

Michel van Biezen

Күн бұрын

Пікірлер: 34
@yolokazizungu9074
@yolokazizungu9074 Жыл бұрын
the correct answers for the line currents are as follows: Ia = 8.66 with a phase angle of -100 degrees Amperes ib = 8.66 with a phase angle of -220 degrees Amperes ic = 8.66 with a phase angle of -340 degrees Amperes
@markfar4837
@markfar4837 Жыл бұрын
right
@sanusanujan6920
@sanusanujan6920 7 ай бұрын
@@markfar4837 then why did he do like this? plz. make sure when you answering!!! @Michel van Biezen
@trolee9987
@trolee9987 4 ай бұрын
yup that's correct since line current lags phase current by 30 degrees.
@Ser3naaaa
@Ser3naaaa 5 жыл бұрын
Doesn't the line current lag the phase current by 30 degrees? Should you be subtracting 30 degrees from -70 so its -100?
@romeissa5232
@romeissa5232 5 жыл бұрын
U are right !!!
@burakkarakus7681
@burakkarakus7681 5 жыл бұрын
Yes it sould be. Just in the previous video he did it with the minus sign. Also I checked the textbook.
@islamzerrougui7718
@islamzerrougui7718 5 жыл бұрын
i have the same remark here
@backtonature1923
@backtonature1923 5 жыл бұрын
so , what is the correct answer?
@user-dz7ix5go9d
@user-dz7ix5go9d 4 жыл бұрын
++
@wscrivner
@wscrivner 3 жыл бұрын
Prof Van Biesen is making sure everyone is paying attention. 😉
@kannanr9016
@kannanr9016 5 жыл бұрын
Line current is lags phase current by -30° but you wrote +30° sir.....
@MichelvanBiezen
@MichelvanBiezen 5 жыл бұрын
You are correct it should be - 30 degrees
@kannanr9016
@kannanr9016 5 жыл бұрын
@@MichelvanBiezen thanks for your quick reply sir. ..
@sbonelobonengcongo2262
@sbonelobonengcongo2262 5 жыл бұрын
@@kannanr9016 yoo thanks guys i was bit confused now but im glad that you notes an mistake thank to you sir as well you my hero i think i got this now because im even able to see an mistake
@kannanr9016
@kannanr9016 5 жыл бұрын
@@sbonelobonengcongo2262 thank you brother. ....
@droferconcepcion2588
@droferconcepcion2588 4 жыл бұрын
i am enlighthen now. thx for your hard work. hoping more videos to come from you
@ceyk2023
@ceyk2023 2 жыл бұрын
In the next video, you substract 30 degrees from the phase current to find the line current. So I am confused why here +30 and in the next same Y-Delta connection -30 degrees
@davenandrew7292
@davenandrew7292 Жыл бұрын
Sir line current lags phase current by 30 degrees. Why adding 30 degrees? Please clarify on that. Thanks.
@MichelvanBiezen
@MichelvanBiezen Жыл бұрын
I believe that was a mistake. Look at the other comment below. Others have found it as well.
@Dima-sx7hb
@Dima-sx7hb 6 күн бұрын
What is Ian current?
@sohailjanjua123
@sohailjanjua123 3 жыл бұрын
Hi Michel , Line current is lags phase current by -30 degrees and you wrote + 30 degrees why? Please explain me . Thanks
@SAJ-wk6hz
@SAJ-wk6hz 3 жыл бұрын
you are correct, it should be lagging (he should have minused 30 not add)
@thefutureengineer6975
@thefutureengineer6975 2 жыл бұрын
The line current lags the phase current by 30 degrees
人是不能做到吗?#火影忍者 #家人  #佐助
00:20
火影忍者一家
Рет қаралды 20 МЛН
黑天使被操控了#short #angel #clown
00:40
Super Beauty team
Рет қаралды 61 МЛН
Wye-Delta Transformation Example
15:18
plusD
Рет қаралды 32 М.
Why there is no Neutral in Transmission Lines?  Explained | TheElectricalGuy
8:46
Gaurav J - TheElectricalGuy
Рет қаралды 277 М.
Imaginary numbers aren't imaginary
13:55
Ali the Dazzling
Рет қаралды 225 М.
50 - Balanced Star Delta 3 - Phase Circuit
27:37
SkanCity Academy
Рет қаралды 9 М.
Delta and Wye - Volts, Amps, & VA
13:21
Dave Gordon
Рет қаралды 563 М.