Electrical Engineering: Ch 13: 3 Phase Circuit (46 of 53) Unbalanced Y-Load: Example

  Рет қаралды 83,923

Michel van Biezen

Michel van Biezen

Күн бұрын

Пікірлер: 71
@Jnglfvr
@Jnglfvr 4 жыл бұрын
As others have commented the wrong voltage was used to calculate the line currents. We're given that the line voltages are a balanced 120 V configuration. In a Y connected load the phase currents are the same as the line currents. Problem here is that the phase currents were calculated using line voltage instead of phase voltage. So the phase (and thus line) current should be equal to phase voltage/impedance. But the phase voltage in this case is the line voltage divided by sqrt(3) with phase shifted by - 30 degrees. That would make all the currents calculated above too large by a factor sqrt(3) with phase angle augmented by 30 degrees. So the correct line currents are Ia = 3.46< -30 Ib = 7.35< -182 and Ic = 5.48
@gilbertvanheerswynghels5246
@gilbertvanheerswynghels5246 3 жыл бұрын
In a star connection the line voltage are measured between the lines (220 V). phase voltage are measured between line and neutral (120 V). This calcultion is correct
@Jnglfvr
@Jnglfvr 3 жыл бұрын
@@gilbertvanheerswynghels5246 Except that Va, Vb and Vc above are LINE voltages not PHASE voltages. It says, right at the top of the blackboard "LINE VOLTAGES." You must convert these line voltages to phase voltages in order to calculate phase currents! This calculation is NOT correct.
@StannyMrKee
@StannyMrKee Жыл бұрын
​@gilbertvanheerswynghels5246 you're also confused
@majoy3653
@majoy3653 Жыл бұрын
Yeahh that should be 120/sqrt of 3
@lrobertiii
@lrobertiii 5 жыл бұрын
Hello Michel, I wanted to personally thank you for your videos. It's because of them, I was able to pass my mathematics and sciences courses, particularly Calculus Physics, and Astronomy, and get accepted into my dream college - the University of Michigan - one of the top science and engineering schools in America! I know you must get a lot of thanks but you really deserve it. Thank you so much.
@MichelvanBiezen
@MichelvanBiezen 5 жыл бұрын
That is great news! We wish you all the best in Michigan. Thanks for sharing.
@xxxx-fw2kk
@xxxx-fw2kk 4 жыл бұрын
Why is there a " -" sign in the final equation for I(n). According to the diagram, I(n) should be the sum of I(a), I(b) and I(c) by KCL i.e. In=out?
@bradenwallace6107
@bradenwallace6107 3 жыл бұрын
Sir, this video is amazing. You present the information extremely clear and show all your work. I've been scouring the internet for hours trying to figure out how to do a problem like this since my professor could not explain any of the process and then I came across this video. Thank you!
@MichelvanBiezen
@MichelvanBiezen 3 жыл бұрын
Thank you. I am glad you found us.
@ninojohnjayme679
@ninojohnjayme679 4 жыл бұрын
correct me if I am wrong; aren't you supposed to use the Phase voltage in calculating the phase current?
@sirtodip5272
@sirtodip5272 4 жыл бұрын
yeah i have this question too like if given voltage is vline, how to find vphase since we cant use relationship of surd3 angle 30 between vline and vphase? do we have to change to delta connection?
@juswesaligan
@juswesaligan 4 жыл бұрын
@@sirtodip5272 we can still use the relationship of squareroot of 3 here since we are dealing with the supply side which balanced.
@billpulvera8817
@billpulvera8817 3 жыл бұрын
@ 0:07 the currents that he's calculating are line currents
@Emaad_Ahmad
@Emaad_Ahmad 5 жыл бұрын
Thank you very much sir. You explained the concepts in an efficient manner just before my exams. Hopefully you'll help with more videos. I'm pursuing B.E Electrical and Electronics Enginnering. You earned a subscriber! Cheers!
@MichelvanBiezen
@MichelvanBiezen 5 жыл бұрын
Good luck on your exams!
@MdUzzolHossain-e7d
@MdUzzolHossain-e7d Жыл бұрын
Very very important video for every electrical engineer. Thank you so much sir.
@MichelvanBiezen
@MichelvanBiezen Жыл бұрын
We appreciate your feedback. Thank you. 🙂
@chooper3048
@chooper3048 3 жыл бұрын
so the phase current whether its negative or positive will be base on the phase value of voltage . . thank you . . just an observation from Ic
@keithto5990
@keithto5990 Ай бұрын
If the final neutral current is postive, it is means that the In current direction is flowing into the circuir?
@omarsh77
@omarsh77 5 жыл бұрын
If both source and load are solidly grounded and if we assume a negligible resistance in the neutral wire, shouldn't the supply neutral and the load neutral be at the same potential i.e. neutral current = 0 A?
@SteveW6SJK
@SteveW6SJK 2 жыл бұрын
How about an example of an unbalanced delta connected load(s) on this wye system?
@MichelvanBiezen
@MichelvanBiezen 2 жыл бұрын
We are still working on completing the other playlist.
@JaykeSapalaran-iq3qs
@JaykeSapalaran-iq3qs Жыл бұрын
How did you get the 9.48 angle32.0 12.65 and -18.43??? How to press in calculator???
@MichelvanBiezen
@MichelvanBiezen Жыл бұрын
The inverse tangent of (=4/12) = -18.43 degrees (Make sure your calculator is in degree mode and not in radian mode. )
@JaykeSapalaran-iq3qs
@JaykeSapalaran-iq3qs Жыл бұрын
Thank you for teaching me ♥️🇵🇭👍
@sagyshehata3616
@sagyshehata3616 5 жыл бұрын
Great videos thank you so much for your effort
@rchokelal
@rchokelal 3 жыл бұрын
Great Review. Took me back to 1993/4. Needed to be remined of the math....;)
@remembering2739
@remembering2739 3 жыл бұрын
it would be phase voltage. not line voltege
@MichelvanBiezen
@MichelvanBiezen 3 жыл бұрын
In a three phase system the line voltage (also known as the line-to-line voltage) is the votage between 2 phases (between 2 lines). The phase voltage is the difference between the phase and neutral.
@AudioJunkie79
@AudioJunkie79 5 жыл бұрын
Great video how would you find the current in each phase when there is no neutral?
@MichelvanBiezen
@MichelvanBiezen 5 жыл бұрын
If there is no neutral, than the KCL at the junction becomes Ia + Ib + Ic = 0 (with the given current directions)
@ArpanDutta-xv2dv
@ArpanDutta-xv2dv 4 жыл бұрын
can you please write the main question!!
@heyman8820
@heyman8820 4 жыл бұрын
How would you do it if a neutral line impedance was given?
@faizmalik9210
@faizmalik9210 3 жыл бұрын
You can use Millman's Theorem.
@razuahamed6418
@razuahamed6418 3 жыл бұрын
Sir my question please answer me quickly,,,,,, if newtral point junction then karsaf law junction point, Ir+Ib+Ic=In but you write Ir+Ib+Ic+In=0 me don't understand.so please explain my question
@MuhammadAbbas-pq3gw
@MuhammadAbbas-pq3gw 4 жыл бұрын
hit a like for sir's efforts
@EngineersCalculatorTechnique
@EngineersCalculatorTechnique Жыл бұрын
The solution is correct the problem is wrong. The problem must be. a unbalanced 4 wire y connected load is supplied by a balanced 3 phase source 120v per phase.
@Odyseee
@Odyseee 6 ай бұрын
0:07 使用線電壓計算線電流
@stanleycates1972
@stanleycates1972 4 жыл бұрын
A field engineer would measure the currents in each hot leg and the neutral. Then shift loads around to gain optimal balance.
@michaelguo6349
@michaelguo6349 5 жыл бұрын
Jesus, this is so nice. Thanks a lot!!!
@surendrakverma555
@surendrakverma555 2 жыл бұрын
Very good. Thanks 🙏🙏🙏🙏
@MichelvanBiezen
@MichelvanBiezen 2 жыл бұрын
Most welcome
@kannanr9016
@kannanr9016 5 жыл бұрын
Awesome sir ....thank you so much sir. ...
@tharakapanabokke4512
@tharakapanabokke4512 Жыл бұрын
Thank you!
@MichelvanBiezen
@MichelvanBiezen Жыл бұрын
You're welcome!
@supaluv3851
@supaluv3851 5 жыл бұрын
Nice video
@abhaynandanchaturbedi6798
@abhaynandanchaturbedi6798 2 жыл бұрын
superb...
@MichelvanBiezen
@MichelvanBiezen 2 жыл бұрын
Thank you! Cheers!
@knowledgeispower8561
@knowledgeispower8561 4 жыл бұрын
Thank you sir very much I'm gonna subscribe now
@MichelvanBiezen
@MichelvanBiezen 4 жыл бұрын
Thanks for the sub!
@knowledgeispower8561
@knowledgeispower8561 4 жыл бұрын
No problem sir
@Rashed_007
@Rashed_007 Жыл бұрын
thanks....
@MichelvanBiezen
@MichelvanBiezen Жыл бұрын
You're welcome!
@DulceSeeker
@DulceSeeker 2 жыл бұрын
splendid
@MichelvanBiezen
@MichelvanBiezen 2 жыл бұрын
Glad you find our videos helpful. 🙂
@kuzgunkuzgun7141
@kuzgunkuzgun7141 3 жыл бұрын
Great
@vimukthimadhusanka4806
@vimukthimadhusanka4806 4 жыл бұрын
Thank you sir
@MichelvanBiezen
@MichelvanBiezen 4 жыл бұрын
Welcome
@error17.o22
@error17.o22 5 жыл бұрын
I think the method u did is wrong sir
@aimgodyt7801
@aimgodyt7801 5 жыл бұрын
yes this is wrong
@danakaterinegomez7480
@danakaterinegomez7480 4 жыл бұрын
@@aimgodyt7801 what would be the correct solution?
@danakaterinegomez7480
@danakaterinegomez7480 4 жыл бұрын
what would be the correct solution?
@pratikrahate6227
@pratikrahate6227 4 жыл бұрын
Yes it is wrong
@danakaterinegomez7480
@danakaterinegomez7480 4 жыл бұрын
@@pratikrahate6227 What would the correct solution?
人是不能做到吗?#火影忍者 #家人  #佐助
00:20
火影忍者一家
Рет қаралды 20 МЛН
Quando eu quero Sushi (sem desperdiçar) 🍣
00:26
Los Wagners
Рет қаралды 15 МЛН
Unbalanced Power in a 3-Phase Wye Circuit
5:45
Zack Hartle
Рет қаралды 12 М.
Three Phase: How to Calculate Neutral Current in an Imbalanced Load
34:06
Joe Robinson Training
Рет қаралды 90 М.
3 Phase Balanced vs 3 Phase unbalanced system / load | Explained | TheElectricalGuy
7:08
Gaurav J - TheElectricalGuy
Рет қаралды 282 М.
3 Phase Wye Tutorial (Electrical Power PE Exam Review)
13:47
Pete Vree
Рет қаралды 204 М.
Delta and Wye - Volts, Amps, & VA
13:21
Dave Gordon
Рет қаралды 564 М.
Three phase unbalanced 4wire star connected load
14:22
Soumya Simon
Рет қаралды 1,2 М.
Lecture 1: Introduction to Power Electronics
43:22
MIT OpenCourseWare
Рет қаралды 957 М.