Electrical equipment must be installed in a professional and skillful manner.

  Рет қаралды 14,487

MikeHoltNEC

MikeHoltNEC

Күн бұрын

Пікірлер: 67
@adfadgaqgv
@adfadgaqgv 6 күн бұрын
Im going with everyone else so far. The Romex is UF and legal.
@MikeHoltNEC
@MikeHoltNEC 5 күн бұрын
After the video was posted, it was brought to my attention that the cable is actually UF which is listed to be suitable in a wet location [340.10(3)], so, this installation is correct.
@YaksAttack
@YaksAttack 6 күн бұрын
That romex may be UF. I have seen some newer UF on the market that doesnt look like the old stuff im used to. It strips a lot easier. Maybe, i dont know, its hard to tell from the video. Missing KO seal and no bushing on the raceway are definitely the biggest issues here i think
@MikeHoltNEC
@MikeHoltNEC 5 күн бұрын
After the video was posted, it was brought to my attention that the cable is actually UF which is listed to be suitable in a wet location [340.10(3)], so, this installation is correct.
@christopherworks400
@christopherworks400 6 күн бұрын
In some areas romex is allowed in PVC with special circumstances.
@MikeHoltNEC
@MikeHoltNEC 5 күн бұрын
Sorry but this comment serves no value. What areas? What special circumstatnces? Understand?
@adfadgaqgv
@adfadgaqgv 5 күн бұрын
@@christopherworks400 it can be used in PVC as long as as the conditions for Romex are met. It can't be used in PVC in wet locations like UF can.
@charliespruyt5815
@charliespruyt5815 6 күн бұрын
I believe that’s uf not rx. Thank you mike and god bless
@MikeHoltNEC
@MikeHoltNEC 5 күн бұрын
After the video was posted, it was brought to my attention that the cable is actually UF which is listed to be suitable in a wet location [340.10(3)], so, this installation is correct.
@chadrionda4114
@chadrionda4114 4 күн бұрын
👍👍 thanks Mike🧐
@tonyrossi3151
@tonyrossi3151 5 күн бұрын
Isn’t the bushing based on #4 and larger. This looks smaller than that?
@MikeHoltNEC
@MikeHoltNEC 5 күн бұрын
Correct, see 300.4(G).
@stevehansen6550
@stevehansen6550 Күн бұрын
What you think is Romex is UF and it is rated for wet lication
@MikeHoltNEC
@MikeHoltNEC Күн бұрын
After the video was posted, it was brought to my attention that the cable is actually UF which is listed to be suitable in a wet location [340.10(3)], so, this installation is correct.
@chrispate2788
@chrispate2788 6 күн бұрын
MIKE..u made a mistake, thats not NM (Romex), thats UF which is for outdoors
@MikeHoltNEC
@MikeHoltNEC 5 күн бұрын
After the video was posted, it was brought to my attention that the cable is actually UF which is listed to be suitable in a wet location [340.10(3)], so, this installation is correct.
@noahautumn7611
@noahautumn7611 3 күн бұрын
Sometimes it helps; by the way, nice tips
@benfowler2127
@benfowler2127 6 күн бұрын
Misspoke, it’s 110.12 and I don’t know that I’ve ever seen it enforced. How does an inspector tell someone their worked looks terrible, you need to redo it and make it look professional? 😂 I wish it was enforced.
@TheCreativeMind
@TheCreativeMind 6 күн бұрын
That looks like UF cable
@adfadgaqgv
@adfadgaqgv 6 күн бұрын
​@@champinsoccer9Actually it looks exactly like UF.
@champinsoccer9
@champinsoccer9 6 күн бұрын
@@adfadgaqgv ahh gotcha. Well the UF I'm used to isn't loose in the sheathing
@adfadgaqgv
@adfadgaqgv 6 күн бұрын
@@champinsoccer9 look at it again. You can see where the insulation was molded around the ground wire. It looks like it's only loose where it's stripped. I've noticed it all depends on how you strip it.
@MikeHoltNEC
@MikeHoltNEC 5 күн бұрын
After the video was posted, it was brought to my attention that the cable is actually UF which is listed to be suitable in a wet location [340.10(3)], so, this installation is correct.
@MikeHoltNEC
@MikeHoltNEC 5 күн бұрын
After the video was posted, it was brought to my attention that the cable is actually UF which is listed to be suitable in a wet location [340.10(3)], so, this installation is correct.
@8080tequila
@8080tequila 5 күн бұрын
Romex it's not allowed in a conduit because it's becoming Doble insolation and it's going to over heat the conductors
@MikeHoltNEC
@MikeHoltNEC 5 күн бұрын
FALSE. NM cable is permitted in a raceway, just not a raceway located outdoors on in a wet location.
@PJChavez89
@PJChavez89 4 күн бұрын
Didnt touch on the IPC taps at all. If you are on 2023 NEC, 230.46, taps must be listed to be used on the line side of the service. As far as I know those Ilsco IPC taps are not. Polaris pass through plugs are and the brand new NSI ones are though.
@MikeHoltNEC
@MikeHoltNEC 3 күн бұрын
Excellent somment, than you for helping me help others.
@PJChavez89
@PJChavez89 3 күн бұрын
@@MikeHoltNEC Thank you for all you do to help all of us! I think I've gotten to where I am at primarily due to knowledge from your books and videos!
@MikeHoltNEC
@MikeHoltNEC 2 күн бұрын
Thank you for allowing me to be part of your sucess story. God Bless, Mike
@bramcoteelectrical1088
@bramcoteelectrical1088 6 күн бұрын
We have same crap installs in uk Mike🇬🇧 😂 P.s watch your videos in uk 🇬🇧 👀 very good
@MikeHoltNEC
@MikeHoltNEC 5 күн бұрын
😎
@scorep0rroman10madden8
@scorep0rroman10madden8 2 күн бұрын
You gotta be one of those inspectors
@MikeHoltNEC
@MikeHoltNEC 2 күн бұрын
Yep, the one that knows the Code and ensures that installation is in accordance with the NEC.
@StevenOslund-v5w
@StevenOslund-v5w 6 күн бұрын
It's not 300.12 it's 110.12......
@MikeHoltNEC
@MikeHoltNEC 5 күн бұрын
Did I seay 300.12? Where?
@MikeHoltNEC
@MikeHoltNEC 5 күн бұрын
😙
@donwaltman4276
@donwaltman4276 6 күн бұрын
Is it against the code to have a bond bushing when it's not necessary?
@xCALIMADRIDISTAx
@xCALIMADRIDISTAx 6 күн бұрын
No you just have to make sure you use the bushing correctly Example i was called out by an inspector. I used a bond bushing because I needed a smooth edge coming in and I didnt use the bonding screw. The correction was to just bond your ground going through it
@MikeHoltNEC
@MikeHoltNEC 5 күн бұрын
Nope
@jamesbsa6450
@jamesbsa6450 5 күн бұрын
​@xCALIMADRIDISTAx isn't this an example of using the bond to ground going g through the unnecessary bond bushing? If not, how is this different.
@MikeHoltNEC
@MikeHoltNEC 5 күн бұрын
I don't understand.
@marks6385
@marks6385 5 күн бұрын
It’s more better!
@RCEmalee
@RCEmalee Күн бұрын
Are the connections tight that’s the real issue
@RobertCunningham-pf9tg
@RobertCunningham-pf9tg Күн бұрын
Lol Except for the fact that about 3 issues were not violations 🤷🏻‍♂️ AND, beauty is in the eye of the beholder 😉 lol You got ONE violation, the knockout. Com'on man, I been doing this since 1984. Do better and don't be one of THOSE guys.
@MrFiver1111
@MrFiver1111 3 күн бұрын
lol he even brought out the book to school the haters
@MikeHoltNEC
@MikeHoltNEC 2 күн бұрын
😉
@RobertCunningham-pf9tg
@RobertCunningham-pf9tg Күн бұрын
Lol Except for the fact that about 3 issues were not violations 🤷🏻‍♂️ AND, beauty is in the eye of the beholder 😉 lol You got ONE violation, the knockout. Com'on man, I been doing this since 1984. Do better and don't be one of THOSE guys.
@MikeHoltNEC
@MikeHoltNEC Күн бұрын
I'm a guy that is doing all I can to help the industry understand the NEC.
@chrisshuhart5940
@chrisshuhart5940 3 күн бұрын
It’s 110.12 not 310.12
@MikeHoltNEC
@MikeHoltNEC 3 күн бұрын
Yep, I misspoked.
@Brian216U
@Brian216U 23 сағат бұрын
Romex can’t be STRIPPED in pipe. You’re welcome
@MikeHoltNEC
@MikeHoltNEC Сағат бұрын
FALSE
@Brian216U
@Brian216U 26 минут бұрын
@ Ok retard
@nickduggan3084
@nickduggan3084 6 күн бұрын
Used to say "neat and workmanlike manner" until politics got involved in the 2023!
@scorep0rroman10madden8
@scorep0rroman10madden8 2 күн бұрын
I thought you don’t need a brushing for pvc
@MikeHoltNEC
@MikeHoltNEC 2 күн бұрын
Judgment call by AHJ, but I'm leaning that you do. See 352.46 and watch MikeHolt.com/AHJ
@richd.4073
@richd.4073 4 күн бұрын
That bonding bushing is a code violation? Isn't it over exceeding code?
@MikeHoltNEC
@MikeHoltNEC 3 күн бұрын
It's not required, but it's okay to exceed the NEC requirements.
@pico3tinez
@pico3tinez 6 күн бұрын
Uf uf uf
@MikeHoltNEC
@MikeHoltNEC 5 күн бұрын
After the video was posted, it was brought to my attention that the cable is actually UF which is listed to be suitable in a wet location [340.10(3)], so, this installation is correct.
@pico3tinez
@pico3tinez 5 күн бұрын
@ thank you sir. You are doing an amazing job
@MikeHoltNEC
@MikeHoltNEC 5 күн бұрын
🙂
@joeerskine3920
@joeerskine3920 6 күн бұрын
Big picture here. Too many rules. I bet this panel isn't in a nuclear facility. This installation will easily outlive you.
8 Wire Stripper Features Everyone Should Know
13:55
LRN2DIY
Рет қаралды 1,9 МЛН
бабл ти гель для душа // Eva mash
01:00
EVA mash
Рет қаралды 9 МЛН
这是自救的好办法 #路飞#海贼王
00:43
路飞与唐舞桐
Рет қаралды 136 МЛН
When Cucumbers Meet PVC Pipe The Results Are Wild! 🤭
00:44
Crafty Buddy
Рет қаралды 41 МЛН
Family Love #funny #sigma
00:16
CRAZY GREAPA
Рет қаралды 59 МЛН
I never understood why you can't go faster than light - until now!
16:40
FloatHeadPhysics
Рет қаралды 3,5 МЛН
Why Are Cooling Towers Shaped Like That?
19:48
Practical Engineering
Рет қаралды 2,8 МЛН
Inspecting an Electrical Panel
5:13
Inspector AJ
Рет қаралды 46 М.
Automatic Disconnection of Supply Explain - ADS
17:29
GSH Electrical
Рет қаралды 11 М.
Let's Be Real About Heat Pumps!
15:13
Electric Vehicle Man
Рет қаралды 53 М.
10 Mistakes EVERYONE Makes When Doing DIY Electrics!💥
11:56
Artisan Electrics
Рет қаралды 221 М.
Add Outlet To Unfinished Basement Or Garage
14:16
Everyday Home Repairs
Рет қаралды 1 МЛН
Testing Dangerous Electrical "Life Hacks" from 1911
23:19
Turnah81
Рет қаралды 126 М.
COMMUNISM vs CAPITALISM: Who Made Better Power Tools?
24:39
The Doubtful Technician
Рет қаралды 844 М.
бабл ти гель для душа // Eva mash
01:00
EVA mash
Рет қаралды 9 МЛН