WAGO 221 Lever nuts - geni.us/wKcBNC Knipex Hybrid Wire Strippers - geni.us/uVWn Locknut Wrench (3 Sizes) - geni.us/Wzm2Wtr Metal Box Used - geni.us/UUEBe GFCI Cover Plate - geni.us/sc1GXu Duplex Cover Plate - geni.us/AiS9x4t THHN (12 gauge Assorted Colors) - geni.us/l5kXo DISCLAIMER: This video is for entertainment purposes only. Also, this video and description contain affiliate links, which means that if you click on one of the product links, I’ll receive a small commission.
@bobsbarnworkshop Жыл бұрын
I was taught , back in the 70’s, to always use pan head screws when mounting boxes to avoid sharp edges on the heads of other types of screws that could cut the insulation. Also to ALWAYS add the green insulated ground wire, especially in damp areas, because the conduit connectors could loosen, rust or corrode and cause a high impedance ground system. Also if the box cover screws are loosened or removed, the ground is lost! Better safe than sorry! Don’t cut corners! I guess I had a good teacher!
@bobhall5893 Жыл бұрын
I agree w Bob, if that locking nut on the inside of the AC panel doesn't bite into the manufacture's finish on the panel, you would have a ground continuity issue. Green wire ground is best.
@glasslinger Жыл бұрын
Tbbbbbt! (fart noise)
@redjohnson4859 Жыл бұрын
I saw some ''pro'' work where the guy had 'grounded' the EMT by running a 10' length of bare ground wire a few feet into the conduit. Folded it over to increase the contact area. Did that at each end of a 60' run. Only reason it got noticed was that people were getting bit.
@pld8993 Жыл бұрын
There's no issue with properly installed EMT fittings and rust, corrosion, or just magically loosening. EMT is installed outdoors all the time so an indoor potentially damp area is of no concern. I learned to install EMT properly when I first started and to this day I don't run wire grounds unless there's a particular reason to do so. The NEC lists 14 types of grounding conductors; only 1 of the 14 is a wire type conductor.
@pld8993 Жыл бұрын
@@bobhall5893 That's why, on painted boxes and cabinets, the NEC requires that the paint be removed to expose bare metal. Takes a wire brush in a cordless drill about 10 seconds to get it done.
@kookiethebear Жыл бұрын
To be clear - While it is ideal to use individual conductors, it is NOT required by NEC. As long as there is enough room (per the NEC table) inside the conduit, you are allowed to use NM (sheathed) wire.
@MrOpinionCantSignIn11 ай бұрын
Admittedly I always believed it was not propper too but could not see changing back and fourth going to islands , so I ran oversized conduits and finally just looked it up , then asked an inspector if I missed something and they were just letting it slide ... nope, perfectly legal
@thesmallterror11 ай бұрын
The problem is the NEC table examines conductors by their diameter and the NM cable has to be treated as one giant conductor, because it is explicitly said as such in NFPA 70 Chapter 9, Paragraph #9, which reads: "A multi-conductor cable, optical fiber cable, or flexible cord of two or more conductors shall be treated as a single conductor for calculating percentage conduit or tubing fill area. For cables that have elliptical cross sections, the cross-sectional area calculation shall be based on using the major diameter of the ellipse as a circle diameter." As NM is an elliptical cable it gets classified as if it were a massive circular conductor, which means NM-b cable needs an unusually massive conduit. After working through Chapter 9 Article 358, the conduit size for single 14/2 gauge NM cables with ground, each 9mm across, needs to be 3/4 inches. 12/3 cable (12.5mm across) needs 1 inch conduit. The same 15 amp / 14 gague circuit in THNN conductors would fit 7 times in a 1/2" conduit (7 hots, 7 neutrals, and using the tube as ground for all 7 circuits), and the same multi-wire branch 20 amp circuit would fit three times in a 1/2 conduit (6 hots, 3 neutrals, tube as ground) for a total of 6 20-amp 120 volt circuits. One of the other common issues with NM-B inside conduit is you may be using conduit because of a wet location. NM-B isn't allowed here at all, but THNN is. Finally, stripping the cables out of the NM-B jacket is a bad idea because only the jacket has the "NM-B type" listing and Underwriters Laboratory certification printed on it. The cables inside have no type listing; your inspector will consider this "non-listed cable" even if its comparable to THNN type cable. Do I care? No. Does your inspector? Probably.
@Satchmoeddie11 ай бұрын
@@MrOpinionCantSignIn You do where I live. It used to be okay to use the conduit as a path to back ground, but not any more. NM cable in conduit is also no longer allowed anymore. That can vary from jurisdiction to jurisdiction, but we can't do it anymore. We also cannot strip back MC and go from MC to EMT and run the wire in the MC in EMT. The MC manufacturers no longer stamp the wires inside the MC with the type & ratings so that makes it illegal now. The wires have to have the 600VW rating, the type of insulation, etc. marked every 2 feet, or you can't use it. Back in the 20th century the wires inside MC cable were all marked like 600WV spool wire. NAFTA screwed that all up.
@thesmallterror11 ай бұрын
@@richt5986 Completely wrong. The jacket on NM-B is not a raceway; NM-B is a multi-conductor cable. Entirely separate definition in code. Furthermore, you cannot strip the conductors out of NM-B. They are not labeled or required to be THHN or XHHW. This is an immediate inspection fail for using an unlisted cable.
@pld899311 ай бұрын
@@richt5986 You wrote three sentences, every one of them is incorrect.
@mattweeks2272 Жыл бұрын
Run the ground. You’re there already. If foregoing the ground wire, at the very least bond the receptacles to the 1900 boxes. The receptacles will be grounded once mounted, but bonding them to the box is a sure fire way to make sure the ground will never be a failure point. Just my 2 cents
@EverydayHomeRepairs Жыл бұрын
Thanks for the feedback.
@Sembazuru Жыл бұрын
I agree. I don't know NEC, but I used to plan wiring inside medical equipment and had to follow IEC-60601. One of the things that my engineers drilled into my head (so they didn't have to redo my ground path planning) was to never rely on a mechanical connection for grounding. Always intentionally supply a dedicated grounding path. OK... I expect that electrical standards for medical devices are a lot more stringent than housing codes. But for such a short and easy run, put in the dedicated grounding path just for good measure.
@pld899311 ай бұрын
@@Sembazuru EMT is a dedicated grounding path. Isn't a ground screw also a mechanical connection?
@Sembazuru11 ай бұрын
@@pld8993 If the only thing a ground screw is doing is connecting a ground, that isn't considered a mechanical connection for what I was talking about because the ground screw's function isn't to hold mechanical things together. Mechanical connections would be things like PCB mounting screws and standoffs, screws holding panels onto boxes, outlet mounting screws, conduit set screws, etc. Basically anything that is expected to hold things together under mechanical load and/or vibration. A wire not under tension isn't enough load to be considered a mechanical load. Even conduit that is supported on a wall to regulations will be seeing mechanical stresses at the connection to the electrical boxes as the conduit stretches and contracts due to changing temperatures.
@pld899311 ай бұрын
@@Sembazuru So changes in temperature or ambient vibration affect the conduit but not the ground screw connection within a box that's connected to that conduit? Assuming an equal amount of temperature change, copper and aluminum are subject to greater levels of expansion and contraction than steel. Using your own description of a mechanical connection, a ground screw absolutely falls into that category. FYI, electrical engineers aren't automatically electricians (though many believe that they are) and should not be trusted to know what they're talking about when it comes to the electrical trade unless they are ALSO electricians. Conduit systems, when installed properly, are more than sufficient as EGCs and while running a wire type EGC isn't wrong, it's usually unnecessarily redundant.
@csimet Жыл бұрын
Tip for tapcons... I always have a spool of bare galvanized wire handy (18-16GA). Just before you put the tapcon in, take a piece twice the depth of the hole plus an extra inch and double it over. Insert it into the hole leaving about 1/2" exposed and bend over the extra, then drive the tapcon in. It helps make it bite even better and especially in loose holes or brittle concrete. I would also always run the green ground wire for any circuit in conduit. You never know if the conduit/connections/screws become loose over time and cause bad bonding.
@EverydayHomeRepairs Жыл бұрын
The tip can be a lifesaver if your hole is a bit loose 💯 Thanks for the feedback!
@rupe53 Жыл бұрын
some guys save the ends snipped from zip-ties and use them in concrete holes for extra bite.
@SgtJoeSmith Жыл бұрын
@@EverydayHomeRepairsrun the green and use isolated ground spec grade 20 amp outlets
@wallacegrommet9343 Жыл бұрын
That works so well! Costs almost nothing and holds tightly.
@ckm-mkc Жыл бұрын
@@karlwithak. Yup, tapcons have never worked for me. Pretty much anything else holds better, esp. if there is any kind of movement - like a plug - I'd never use them for that.
@christraudt6730 Жыл бұрын
if a raceway is over 18” it requires a means of support. i.e. a strap or that conduit hanger you mentioned. over 18 inches, and you need to strap every 10 feet and within 3 feet of each termination.
@christiansantos8904 Жыл бұрын
Intervals not to exceed 10 feet according to 2023 N.E.C 358.30. Cmon baby boy
@christraudt6730 Жыл бұрын
@@christiansantos8904 did the nix the within 3 feet of a termination in 2023? if not, you just didn’t read my whole comment lmfao
@stillthakoolest Жыл бұрын
The EMT needs to be secured within 3 feet of a box. The 18" nipple rule for strapping was removed years ago. Technically any length of conduit needs a strap.
@BackyardMaine Жыл бұрын
EMT shall be securely fastened in place at intervals not to exceed 3 m (10 ft). In addition, each EMT run between termination points shall be securely fastened within 900 mm (3 ft) of each outlet box, junction box, device box, cabinet, conduit body, or other tubing termination.
@rupe53 Жыл бұрын
@@BackyardMaine basically, with only a 6 ft run there's no additional support needed between boxes.
@46bovine Жыл бұрын
Electricians I worked with always ran the green (ground) lead. Yes, your ground can be through the emt but it can be interrupted by some schmuck. Having the ground lead is a safety device.
@majortom222410 ай бұрын
Agree cheap insurance that there will always be an uninterrupted ground to the panel.
@Frontslider10 ай бұрын
Grounding by EMT is not allowed.
@johnspathonis107810 ай бұрын
Another reason to run a dedicated earth is the the EMT could suffer from corrosion many years into the future causing a bad earth.
@Frontslider10 ай бұрын
The code requires a ground wire. Conduit grounding is no longer allowed.@@johnspathonis1078
@RadioRich10010 ай бұрын
The guy that made the video is the schmuck.
@The_DuMont_Network Жыл бұрын
For the small incremental cost and time, I always run a separate ground wire. Never had an issue, and the local inspector agrees with me.
@MrOpinionCantSignIn11 ай бұрын
Actually, it has been required per NEC for over 30 years , ever since an inspectir got zapped due to a sepperated conduit
@whiggins10111 ай бұрын
@@MrOpinionCantSignIn That is NOT true. EMT (electrical metallic tubing used here) and other metallic conduits are acceptable for grounding according to the National Electrical Code.
@pld899311 ай бұрын
@@MrOpinionCantSignIn Not true. Conduit EGC is legal.
@jaymes752111 ай бұрын
@@whiggins101 Yup. A ground is ground. I have been splicing high voltage PILC cable for 40 years, the lead sheave acts as ground, with an occasional twisted #10 wire going to the ground tree in the manhole.
@choimdachoim9491 Жыл бұрын
I can't count the number of emt screws I've tightened on old houses over the years. I always run a separate ground. It's quick, easy, cheap and is an unbroken-by-loose-screws piece of protection. I see by reading comments, that I'm in good company on this subject. Another point I'm curious about is the ring on your left hand: if it is metallic, you're taking a risk. I learned the hard way connecting 4/0 cable to bus-bars in an 800 amp DC can...my arm was straightened so hard I was knocked away from the can.
@stevenhinch18711 ай бұрын
It looks like a silicone ring on his finger, alot of public safety personnel use those inplace of their metal wedding band.
@richt598611 ай бұрын
It's not cheap anymore
@choimdachoim94919 ай бұрын
@@richt5986 My wife says it's cheaper than a funeral.
@richt59869 ай бұрын
@@choimdachoim9491 definitely
@ersalbaydar9 ай бұрын
All metal surfaces must be grounded with grounded wire can handle the short circuit current. Do not trust the conduit , it can brake or louse connection can put lives to the danger. Run the grounding wire .
@bradkrahenbil922011 ай бұрын
Thanks for the video - Journeyperson Electrician and a few comments: 1) Conduit should have offsets at the boxes so it is against the wall, and be strapped (fastened) per code. 2) A ground wire from the box to the receptacles is code here, but I would suggest it is best practice even it it is not where one is located. Certainly there is no harm having a ground wire in the conduit as well, although not required per the codes I am aware of.
@marshal1x10 ай бұрын
conduit does not need offsets per code as long as the pipe hanger aka Minis. as well call them are used to support the pipe. i would run a ground vice using the box and emt as a ground. it is required where i am located.
@KjKase10 ай бұрын
@@marshal1x Not required, but looks better and more professional.
@Mike_H769 ай бұрын
Non electrician and thought the same regarding a ground wire, since I'd trust a "protected" wire over the conduit on a painted panel (granted, it's probably "ok" mechanically). I feel that extra grounding is safer than trusting the conduit connections alone. It also seems that Romex IS allowed from a "master electricians" video I just watched, in this instance.
@dmiguy58979 ай бұрын
What about minis? Specifically designed to be away from the wall
@LoudByNature029 ай бұрын
All u haters Always dielectric grease on connections 😐
@bossmonkie11 ай бұрын
The reason a grounding pigtail is needed is so that if the device is removed from contact with the metal box, it will still be bonded. With the raised covers it is possible to remove the cover with the devices leaving both the metal cover and the devices unbonded.
@pld899311 ай бұрын
Sort of. If the receps were riveted to the cover, no grounding pigtail necessary. The way he did it, pigtail required.
@Sparkeycarp11 ай бұрын
@@pld8993 Never seen one riveted. At the very least he should have bonded to the box even if he is using the conduit as a ground.
@pld899311 ай бұрын
@@Sparkeycarp Doesn't have to be rivets, that's one example, but it has to be something permanent that is not removable. Pigtails are certainly easier. I've never riveted one either but I did a job long ago that spec'd permanent fasteners on cover mounted devices. I don't remember exactly what we used but they were some type of irreversible screws.
@kingdommanlegacyministries776911 ай бұрын
True
@jaremaw2368Ай бұрын
_"The reason a grounding pigtail is needed is so that if the device is removed from contact with the metal box, it will still be bonded...."_ The same applies to the neutral.
@MajGenAtlas Жыл бұрын
Always pull a ground Don't drill into mortar for anything Use a hacksaw, plumber's pipe cutters run the possibility of decreasing interior diameter, which is a code violation Supports are needed within 3ft of the box Don't feed wire toward the panel Bend boxsets and use one hole straps instead of using Mae Wests
@EverydayHomeRepairs Жыл бұрын
Thanks for the feedback.
@greggpurviance7252 Жыл бұрын
Using one hole straps against block basement walls increases the chance of dampness against the emt, no matter the outside barrier. Yes, never use plumbers pipe cutter on emt
@dave7038 Жыл бұрын
Why do you feed wire away from the panel?
@greggpurviance7252 Жыл бұрын
@@dave7038 don't want to poke wire into hot breaker, on the other hand pushing wire FROM a hot panel with your hand next to hot breaker is probably just as bad
@TheKingOfInappropriateComments Жыл бұрын
I cringed when I saw that! @@greggpurviance7252
@larrychristian7239 Жыл бұрын
Scott, once more. At the 4:45second mark you show a minerallac. These ARE required by the National Electrical Code (NEC) within 3' feet of every box. This means you are short three of them. One needs to be used between the service and the first box, and two more between the second two boxes. If you had just used a 5 foot piece of pipe for your second pipe you could have gotten by with just one in the center. Evan jsu cutting your pipe one inch short of 6 feet would have allowed you to use one minie (as we call them).
@icevariable9600 Жыл бұрын
I never thought of using minies to strap the EMT down. Gotta say, it's rather ingenious, as you avoid putting in a box offset. I'll have to remember that. I don't understand why he showed the minnies, but didn't use them. So odd.
@pld8993 Жыл бұрын
Because the first section is not more than 3', no strap required there. The second section is 6' so one strap dead center covers it. Only 1 strap/mini needed to make the conduit code compliant.
@icevariable9600 Жыл бұрын
@@karlwithak. Funny sarcasm.
@pld8993 Жыл бұрын
@@karlwithak. Yeah, what you described is exactly how someone who has no idea what they're doing would do it. Would the circuit work when you plug something in? Sure, just as running a single black wire and a single white wire and no ground wire and leaving them dangling along the floor would work. Just because it works that doesn't mean it's done correctly or safely.
@icevariable9600 Жыл бұрын
@@karlwithak. No idea what you’re talking about. But again, that was some funny shit you posted on how a DIY fool fixes wiring issues. LOL! 😂
@stillthakoolest Жыл бұрын
Electrician here. While you said it was just best practice, there is nothing against code running NM cable in conduit like in your thumbnail. You do have to follow cable fill requirements in Chapter 9, however. The problem most people make is stripping the jacket off and just using the wires inside. Unlike MC or spooled wire, the conductors inside NM cable are not labled with their insulation class or any other required information, and not permitted to be run in conduit without the jacket. You used solid wire, so I hope you didnt strip the romex and use it for this reason. While it is true EMT is a permitted EGC in 250.122, you are relying on the set screws and locknuts being tight for that grounding and bonding purpose. They can loosen over time, so its not a bad idea to pull a wire type EGC. Also, code has NO prohibition for using a bare grounding conductor for this installation.
@alryky30 Жыл бұрын
Totally agree. Best practice is to run grounding if you can. Trusting "BONDED" grounding is a dice roll at best as stated. Equipotential for all of your circuits is key, heaven forbid a child or anyone else plug something in on a loose "BONDED" box and then when finished noticed this and used their one hand to support the box and the other to remove the plug. The possibility of a fault that "EXPOSES" itself could be very dangerous.
@frankesposito1399 Жыл бұрын
Does the conduit need to be metal or can you use the plastic conduit for a basement run like this?
@stillthakoolest Жыл бұрын
@@frankesposito1399 pvc sch 40 or 80 would also be acceptable
@nickpckles8902 Жыл бұрын
No conduit support straps or mini’s. When you see “bonded grounding” fail you will always pull a ground after! And why strip nm when you can pull thhn. Teach the real way to do things.
@stillthakoolest Жыл бұрын
@@nickpckles8902 you cant strip the NM, thats my point. I agree, pull THHN. I was simply stating it is code compliant to use NM in conduit.
@mjg263 Жыл бұрын
I haven’t seen or installed a conduit run to a panel without a separate ground wire since the late 1970’s, thought they settled that a long time ago. If the conduit rusts out or becomes disconnected from the conduit connectors along the run you would lose the ground entirely (and trust me, it happens more often than one might think).
@greggpurviance7252 Жыл бұрын
I have never seen emt rust out inside a building. Seen it maybe twice & both were installed so the emt was touching the earth
@quademasters249 Жыл бұрын
It made me uncomfortable too. I'd rather spend the extra on a real ground wire.
@mjg263 Жыл бұрын
@@greggpurviance7252 wish I could attach photos to the comments here, I’d show you all of the emt that’s rotted out in my basement right now. When I installed it 27 years ago I kicked offsets on all the boxes and strapped it to the cinderblock walls with emt straps. Now all these years later it’s rusted through on all the drops and most of the laterals because the basement walls tend to be a bit damp. Eventually I’ll change it all out to pvc but for now it’s ok because it has a separate ground conductor and gfci protected devices. I also see plenty of conduit hanging loose with the connector sleeves disconnected at work when other shops need to move it out of the way to do plumbing / woodwork / masonry repair. They don’t think twice about sliding conduit apart and leaving it that way which is another reason why I would never run conduit without a ground wire, you never know what kind of idiot is going to mess with it after you’re done.
@greggpurviance7252 Жыл бұрын
@@quademasters249 the emt is a real ground
@RJ-ej1nr Жыл бұрын
I deal with large ~50 year old buildings that used conduit as EGC and it’s a total pain. It fails enough that I’ll never call it reliable. With long runs buried in building walls, it’s not practical to fix, it’s do a new run instead.
@arthouston7361 Жыл бұрын
There are many people who don’t know how to properly use a wire nut, and for them, the Wago is a good choice to help make an acceptable installation. Most modern THHN wire has multiple designations, including for wet and damp environments. It’s easier for the wire manufacturer to produce one wire listed for all applications, than to make separate wires as they used to years ago. It is important to remember that the use of a raceway listed for a wet and damp environment does not create a dry environment inside the raceway. In a wet and damp environment, all components must be appropriately listed for that environment.
@elektrikman883411 ай бұрын
the wage will fail in time the weren't not so much especially when you twist the wires together
@paulgrieger818211 ай бұрын
I do not trust, and would not use a WAGO. In order to make good connections, twist the wires together with you lineman's pliers, clip off the excess, and install the PROPER wire nut. WAGO might work for your Lionel train set, but I would not trust then with line voltage.
@marchurnik10 ай бұрын
@karlwithak That will work inside under dry condition . But as electrician you will lost your insurance and as a homeowner possible too. You can do also old edison style: line up a bunch of nails and wrap 2 blank cables around.
@paul56832 ай бұрын
An electrician buddy of mine suggested that after the new circuits are all working the way you want, he suggested taking the wire nut off of the pig tail and then put some solder into the pig tail and replace wire nut. The pig tail will never come apart. I don't like those wago things either, tried them and had a bunch of loose connections.
@ralphdoid Жыл бұрын
Correct me if I'm wrong. I believe a grounding conductor that makes a bond to each metal box needs to be present to satisfy code in this particular arrangement. The set screw on the conduit connectors may loosen or go missing which results in poor continuity as an EGC over time. But of course, this is permissible by code. However, I believe having the conduit and boxes as an EGC is not enough. There needs to be bonding jumpers from those types of box cover plates to the inside of the 4x4 boxes. NEC 250.148 Continuity of Equipment Grounding Conductors and Attachment in Boxes. If circuit conductors are spliced within a box or terminated on equipment within or supported by a box, all wire-type equipment grounding conductor(s) associated with any of those circuit conductors shall be connected within the box or to the box in accordance with 250.8 and 250.148(A) through (D) (C) Metal Boxes. A connection used for no other purpose shall be made between the metal box and the equipment grounding conductor(s) in accordance with 250.8 NEC 250.8 Connection of Grounding and Bonding Equipment. (A)Permitted Methods. Equipment grounding conductors, grounding electrode conductors, and bonding jumpers shall be connected by one or more of the following means: (1)Listed pressure connectors (2)Terminal bars (3)Pressure connectors listed as grounding and bonding equipment (4)Exothermic welding process (5)Machine screw-type fasteners that engage not less than two threads or are secured with a nut (6)Thread-forming machine screws that engage not less than two threads in the enclosure (7)Connections that are part of a listed assembly (8)Other listed means (B)Methods Not Permitted. Connection devices or fittings that depend solely on solder shall not be used.
@EverydayHomeRepairs Жыл бұрын
The screw or locknut loosening over time could happen but I don't think that potential failure would make the grounding through conduit against code. Easy enough to run another ground wire for triple protection. Currently this circuit is protected by the conduit providing equipment ground and also the GFCI protection starting at the first outlet. Thanks for the feedback.
@TwilightxKnight13 Жыл бұрын
@@EverydayHomeRepairs as with anything, check with your jurisdiction. Just because the Code allows for something does not mean your local inspector will allow it. If we use EMT in our area, we must run a grounding conductor and it must be bonded to the junction box and the device.
@EverydayHomeRepairs Жыл бұрын
@@TwilightxKnight13 Agreed, best to ring the inspector to avoid any rework. Thanks for the feedback.
@edmessina8392 Жыл бұрын
@@EverydayHomeRepairs metallic boxes require bonding. I do not think there are any exceptions. You can purchase a bag or box of pre-loaded pigtails specifically for this purpose.
@KevinCoop1 Жыл бұрын
@@edmessina8392. If EMT is the grounding system to metal boxes, and the device (receptacle) has an approved grounding clip on one of the attachment points, then the pigtail is not required from the receptacle to the back of the box. If the receptacle does not have the required clip, then the pigtail would have to be installed from receptacle to the box.
@GFlCh11 ай бұрын
I'm glad you used your outlet tester. Now run the test again after removing the cover screws. Spend the $little and add the green insulated ground wire.
@TangoIndiaMikeJuliet10 ай бұрын
Exactly what I thought. With the cover removed the receptacles and anything plugged into them are no longer grounded.
@vicalvaran37966 ай бұрын
12 AWG THHN is between $0.22 - $0.60 per foot at the time I'm replying. Price is so insignificant I'm honestly surprised he didn't pull one.
@briankolley3550 Жыл бұрын
When it comes to bonding and equipment grounding conductors (egc's), the system should be designed such that a single point of failure does not degrade the integrity of the system. In order to ensure this, it must be understood that bonding and egc's are two different things. Bonding is intended to tie all metal surfaces together to guarantee that they are all at the same electrical potential in order to prevent a potential difference between adjacent metal surfaces that can cause a shock or an electrocution should someone inadvertently complete circuit between them. The egc is intended to provide a dedicated conductor to carry electrical fault current back to the source to complete the circuit and instantly trip the overcurrent protection to de-energize the circuit in order to reduce the risk of fire and electrocution. Tying the bonding system to the egc, ensures that an electrical fault on the bonding system will trip the overcurrent protection and de-energize the circuit. Relying on the bonding system to act as the egc significantly increases the risk that a high resistance connection will develop over time either through corrosion issues, loosening of bonding screws, or other potential ways that the bonding can degrade or fail. Having a dedicated egc ensures that the fault current path is not reliant on the state of repair of the bonding system. It further ensures that each metal box and fixture are independently bonded to each other at the main panel through their respective egc's. Even if the emt bonding screws come loose or individual bonding connections become compromised, each box and fixture will still remain bonded to all the other boxes and fixtures through their respective egc's. In addition, in the case of emt, even if one end has its bonding compromised, the other end can maintain the bond and keep the conduit at the same potential. Such a design ensures system reliability in the presence of a single point of failure. Of course, you can have bonding failures at both ends of the emt, but, that would be 2 points of failure, and attempting to design a system that remains reliable in the presence of any 2 points of failure is nearly impossible, and even if possible is so expensive that it becomes unaffordable. Also, in order for the emt whose bonding is compromised at both ends to become energized, the wires within would need to be compromised, which may happen if a wire was skinned during the pull, or during subsequent maintenance or repair activities, but that would be a 3rd point of failure. In the case of your installation, a single point of failure compromises the system to save the cost of a bit of wire. It's a very bad design.
@EverydayHomeRepairs Жыл бұрын
Thanks for the feedback Brian. I agree adding a ground wire would be a better design.
@donl1410 Жыл бұрын
But not required @@EverydayHomeRepairs
@briankolley3550 Жыл бұрын
@@donl1410 Whether or not it's required depends on the electrical inspector. The code is not the final authority, the authority having jurisdiction (AHJ) is the final authority. Since the electrical inspector is the AHJ, they are free to reject the code provision in this circumstance and require a dedicated egc. There is little you would be able to do about it since the inspector wouldn't be requiring you to violate the code or do something that reduces the reliability or drastically increases the cost of the installation. You could argue with the inspector and cite the code and maybe they would change their mind and accept it, but I doubt it. Of course, you might get an inspector who's OK with it, but why take the risk over $2 worth of wire and a few minutes of install time? While theoretically you can appeal a rejection, any such appeal will almost certainly be rejected since the cost is negligible and it improves the safety reliability of the system.
@donl1410 Жыл бұрын
The AHJ is not necessarily the inspector, but the rule making body that interprets the code for the area, and has written documented code amendments. If the area, city, county, or state has amended the NEC, to state, in this case an EGC shall be installed in all raceways, then I agree with it. The electrical inspector can not, or should not be able to make up his own rules to the way he or she thinks it should be done. I have questioned inspectors on different points over the years , when I new the answer, and have generally been able to resolve the issue in the field, At one point I did take an issue to the head building official and the problem was satisfactorily resolved in his office without further necessary action. There are some primitive rejoins that do not require any licensing where the inspector does his own interpretation, I agree, Problems usually arise when nebulous articles of the NEC come forth. In which case, I contact the the AHJ official to get their interpretation, so we all can be on the same page, before proceeding. What probably would have made both your 'narrative' and the one I'm writing unnecessary, would have been to have me written, "But not necessary by the NEC".@@briankolley3550
@briankolley3550 Жыл бұрын
@@donl1410 I wouldn't agree that the inspector requiring an egc would be making up the rules, I would interpret it as the inspector having concerns about the likelihood of the bonding being maintained over time and wanting the higher standard to be met. In this particular case, if the inspector required an egc to be run, I seriously doubt you would even appeal it given that it would cost you way more in time to appeal than it would to just install it and be done with it. However, if the situation were such that utlizing the provision results in a large cost savings on a much larger project, then appealing the decision may be the better way to go. Also, I agree that having a conversation with the inspector can be beneficial in most cases provided that you are knowlegeable about the code and have high quality workmanship. However, if the inspector knows that the homeowner is doing the work they are going to come to the site prepared for a disagreement and such a conversation may not go well. I've had inspectors express great relief that the work was done so well and that they had geared themselves up for an argument. An inspector in that state of mind dealing with a non-expert homeowner may not be the best combination. That being said, high quality workmanship goes a long way with inspectors. As far as us writing these long narratives, I think it's useful to have these conversations because people who don't understand why things are in the code have a chance to learn a little bit.
@Brodmann312 Жыл бұрын
Genuinely, big thanks to the electricians commenting. I've got a list of stuff to check in my basement now.
@tservo1000 Жыл бұрын
You still need a ground wire going to the breaker box as you are relying on a current path running thru the conduit to the ground connection in the breaker box. The problem is the painted surface where your conduit enters the breaker box it may be good now, but if it rusts and corrodes. Are you sure its a good connection? Just run the ground wire from boxes into the breaker panel to be safe.
@pld8993 Жыл бұрын
No ground wire needed if using metal conduit EGC.
@js4187 Жыл бұрын
Agree 100% . Youre relying on too many conduit connections staying tight to get a good ground . It takes maybe 36 seconds more to ground the metal box .
@hankkline7300 Жыл бұрын
I believe where he ran the conduit into the panel box was concentric k.o.s Not allowed for grounding purposes. No straps, I would have stripped about 3/4" of insulation off the wire and wrapped it around the device screw and continued on to the next devise screw then continued down to the next receptacle and done the same thing. I may be wrong, but I believe the codes now require every junction box to be grounded by wire. also I do not know an inspector who would approve using a pipe cutter on EMT.
@pld8993 Жыл бұрын
@@hankkline7300 Concentric knockouts are allowed for grounding, except for service equipment. Junction boxes with EMT grounding system are not required to have a wire-type ground.
@rhaegoti Жыл бұрын
According to NEC 358.30(A) "EMT shall be securely fastened in place at intervals not to exceed 3 m (10 ft). In addition, each EMT run between termination points shall be securely fastened within 900 mm (3 ft) of each outlet box, junction box, device box, cabinet, conduit body, or other tubing termination." Your video showed that you had the EMT straps, you should install these before walking away from your project. You are correct about the grounding: according to NEC 358.60 "EMT shall be permitted as an equipment grounding conductor." But, again, your video showed that you had the grounding pigtails. Using the pigtails and an actual equipment grounding conductor from the outlets to the panel would cost a couple of dollars and a couple of minutes. It would also add protection, and help "future proof" an installation (NEC generally becomes MORE restrictive over the years, not LESS).
@EverydayHomeRepairs Жыл бұрын
Yeah, should have added the 2 hangers between the boxes. Thanks for the feedback!
@mxslick50 Жыл бұрын
@@EverydayHomeRepairs And the pigtails between the devices and the box. A loose plate = loose grounding to the devices.
@brynnrogers5081 Жыл бұрын
I just ran some 1/2" an d 3/4" emt, and I've found that the connectors to the main panel don't make a real good connection because of the paint on the box. Seems like the better the paint, the worse your connection. GFCI popped on the first test. I dremeled down to bare metal for the connector ring, or ran a ground wire to the first box to make connections. Now I am getting a bunch of people including electrictains saying best practice might be to still run a ground wire - most commercial jobs require it, they tell me.
@pld899311 ай бұрын
The NEC requires that the paint be removed at the fitting connection when using it a grounding path, unless the fitting is designed to bite through the paint. Also, the lack of ground will not trip a GFCI, you must have a different issue. Most commercial jobs do not require a wire type ground.
@racenuke Жыл бұрын
NM cable is not illegal inside EMT, it is simply not necessary. NEC 334.10 shows “uses permitted.” NEC 334.12 shows “uses not permitted.” No mention of NM cable inside EMT. It’s acceptable. But it’s not a good idea because it takes up a lot of room inside a raceway you may want to add more circuits to later.
@rogerk1710 Жыл бұрын
Does the extra sheathing with NM cable use more than the allowable capacity of 1/2” EMT? 40% capacity? Just asking
@racenuke Жыл бұрын
@@rogerk1710 chapter 9 table 1 shows that using one Cable, you can fill it to 53% capacity. The same table has 10 notes below it. Note 9 says cables that are elliptical in shape (NM) the cross sectional area shall be calculated based on the major diameter of the ellipse. So, you need to physically measure the size and type of nm cable and find the cross sectional area. Ch 9 table 4 shows that 1/2” EMt with 1 cable (53%) can be filled up to .161inch^2
@donl1410 Жыл бұрын
Very debatable. 344.22, and 358.22 clearly state that "cables shall be installed where such use IS PERMITTED by the respective cable articles. Nowhere in Article 334.10 does it say NM can be installed within these raceways. If you look at Article 336.10 for Type TC, # 2 allows TC in raceways. Other cable systems are indeed allowed. NM and UF are two that are not.
@rogerk1710 Жыл бұрын
@@racenuke Still not a good idea or needed right? I find it easier to just buy wires as needed for the amps. Thanks for the info
@racenuke Жыл бұрын
@@rogerk1710 oh I would 100% buy THHN wire spools and use what I need and save the rest for a future project. NM cable in a conduit is cheesy.
@faradaysage1522 күн бұрын
Your safety glasses are on top of your head in the entire video. You're just like the people I work with.
@EverydayHomeRepairs22 күн бұрын
Isn't that how you wear them 🤷♂️
@erikmoseid10 ай бұрын
I always run 2 hots, adding a red. That way I can have each outlet on a separate circuit (it also allows me to easily change to 220v if needed. And, I always add a green (as noted below), and add screws to support the conduit (as also noted below). And, although it is a pain, I bend the conduit so it does lay flat against the wall (which is also mentioned by others, below).
@chrisharper2658 Жыл бұрын
I would not rely in the conduit set screws for adequate grounding since over time they will likely oxidize. Also, why didn't you do the bends to get the conduit to lay flat against the wall and use the "C" type wall fasteners?. I thought it was okay to run only one piece of Romex inside a conduit but no more due to possible heat build up.
@aurvaroy6670 Жыл бұрын
Well it's obviously easier to install a straight piece of conduit than to bend it several times. Also, no extra tools required. When it comes to NM cable, yes in some instances, depending on the jurisdiction of course, it is permissible to run a short section of NM inside a conduit to protect it from physical damage. But NM shouldn't be fully enclosed by a conduit.
@jaycahow4667 Жыл бұрын
I just buy the angled conduit box adapters with set screws as they bring the conduit right up against the wall.
@chrisharper2658 Жыл бұрын
@@jaycahow4667I've used a couple of the 1/2" offsets but remember them as being a little expensive. Do they have them for the 3/4" conduit?
@herrtomas6729 Жыл бұрын
In UK we thread each conduit end, so its ground is definitely solid
@chrisharper2658 Жыл бұрын
@@herrtomas6729 We use the thick-wall (threaded) for outdoors but this is the thin wall with indoor fittings that use a single set screw. No need to be cheap, just include the ground wire.
@marshallpendleton139910 ай бұрын
I'm not an electrician, but have done electrical training and code IS to ground all metal electrical boxes.
@dieselsoggydog62999 ай бұрын
only if using eccentrics on the box.
@KevinCoop17 ай бұрын
EMT is a NEC approved means of grounding.
@jay930828 күн бұрын
@@KevinCoop1 EMT is an approved equipment ground per article 250.118(4)
@KevinCoop128 күн бұрын
@@jay9308 ???
@ArcadiyIvanov Жыл бұрын
You never drill holes in the mortar of the masonry wall. You always mount into the block.
@ChuckD59 Жыл бұрын
And that was the only question I had about this otherwise excellent (and for me, timely) presentation. (And I won a bunch of blue ribbons for demonstrating at the county fair as a kid in 4-H. So if that doesn't make me an expert...) : )
@alaincote6684 Жыл бұрын
🤣🤣🤣🤣🤣🤣🤣🤣😂😂😂😂😂 4H memories... I got beat by a gurl at the milking competition @@ChuckD59
@kylekelley213 Жыл бұрын
😂
@CliffsideStables Жыл бұрын
@@ChuckD59BUT did you stay in a Holiday Inn Express? 😜😎😇 Tim in northern TN
@ChuckD59 Жыл бұрын
@@CliffsideStables Nope, lived nearby. But did better than the kids who slept in the stables with their animals.
@philmann3476 Жыл бұрын
So nice to see conduit being used. As an old timer who grew up in Chicago, the sight of Romex being run through holes in studs and into plastic boxes has always left me a bit jarred. Intellectually I know it is permitted in most places, safe, up to code, etc., but still, it just looks wrong -- sort of like knob and tube wiring or something. While I never did this professionally, one of life's joys was bending a semi-complicated conduit run and having it drop into place just so. For the pros this is likely old hat, but for an amateur it can bring great happiness and satisfaction for a while.
@harpsealSF11 ай бұрын
Yeah, that 60+ years of romex really has gone badly. 🙄🤦🏻♂🤷🏻♂
@paul56832 ай бұрын
After I had an electrician rewire the second story of my old house. Replaced one circuit that ran everything on the second floor, Replaced with five circuits ,two 20 Amp circuits and three 15 Amp circuits. I would have needed a 2 inch conduit for all the wires in the first half of the new circuits.
@Patrick_Gray5 ай бұрын
I was a Master Electrician and would like to comment: (1.) We always ran an insulated ground wire with the other wires. The Code may not make you but it is standard practice. (2.) We always used a box off set and one hole clamps on the EMT. Where the conduit was located where no one could rub against it we may use hangers like you showed. (3.) The wire would need to be labeled for the use.
@RJ-ej1nr Жыл бұрын
On cutting conduit, if you are going to use a plumbers pipe cutter, use a reamer like a Klein 85191 to ensure that you have expanded the inside of the pipe to required dimension. The pipe cutter squeezes reduces the inner diameter and can catch wire. You did ream, but that does not confirm it's enough. For your install here, it's not going to matter, but for ones with some conduit bends, it can nick/strip wires. Preferred for cutting is a bandsaw (fast and square) or in a pinch a recip saw, but understand those not being standard DIY arsenal.
@TheOldManAndTheSaw Жыл бұрын
This method of cutting conduit is DEFINITELY done by a DIY person. A pro would never do that.
@markkempton4579 Жыл бұрын
I learned something new for sure. I would have expected the pro to use the pipe cutter as it seems more efficient, quieter and neater. Thanks for the tip on the reamer. I've seen them but did not know the benefits.
@TheOldManAndTheSaw Жыл бұрын
A sharp hacksaw is much faster than a pipe cutter with a minimum amount of reaming required.
@markkempton4579 Жыл бұрын
@@TheOldManAndTheSaw I'm obviously not very efficient with a saw then. LOL
@RJ-ej1nr Жыл бұрын
@@TheOldManAndTheSaw Good point. I forgot hacksaws existed in this context. Too spoiled by being used to having power options around.
@busyguy7479 Жыл бұрын
I agree pulling the ground wire into the boxes is better because the bonding through the conduit could be compromised .
@ethanbrush493210 ай бұрын
O interesting. Please explain how a wire EGC magically can't be compromised
@Phillyhillbilly11 ай бұрын
Good critiques and cautionary comments. I always use electrical tape to cover all exposed receptacle connection screws. My first boss was too cheap to buy tape, so I always had my own. Ground wire, tape and sleep easy...
@markelliott791711 ай бұрын
Tape not necessary. It will leave a messy residue on the receptacle. It will make it more difficult to work with in the future.
@c50ge10 ай бұрын
What you did works well, another option is to run conduit vertically then run your 12/2 w ground up the wall then it is acceptable to run the sheathed above the flooring joists and to your breaker panel. This will leave the wall space unobstructed.
@bradleybuyer554120 сағат бұрын
Note how he spins the pipe cutter around the correct way folks. Great video! Got a project just like this in my basement.
@windward281811 ай бұрын
If this is a damp location you should pull THWN/THHN stranded wire in the conduit. Beyond this you have several options as to the installation that fall under workmanship and technically would not be a code violation depending on the state you live in of course and how the local codes are worded and who is doing the inspection. I would recommend the following: 1) Make the branch circuit 20Amp you are literally at the main breaker box there is no reason to run a 15Amp 120VAC branch circuit. Better yet for a square D breaker panel you can use a tandem 20Amp breaker, string two 20Amp branch circuits and alternate in each quad box, one GFCI #1, and the other GFCI #2 in the same box, then alternate the same in the next box. 2) Use THWN/THHN 12AWG stranded wire (will work for damp basement locations). For one circuit use Black, White, Green (don't rely on the conduit for ground fault protection or GFCI leakage detect always run a ground wire even if you run rigid conduit). For two branch circuits you could use Black (line), White, Green, Red (Line), Yellow (or White marked), Green with Yellow stripe (or Green Marked). You would be pulling 6 wires which would not violate the conduit fill or box fill. Stranded wire is much easier to use in creating a longer pigtail while folding into the box. It is always better to have a slightly longer pigtail for repair or future work. Use a dedicated box stranded 12AWG wire ground screw with captive spade lug to ground each receptacle to the box and the circuit ground. In the video you have the proper boxes in that they have the bulged ground connection for use against a flat masonry brick wall. 3) For 4 total duplex receptacles, use four GFCIs, I dislike ganging GFCIs because if you trip a GFCI you will lose all of the receptacles. 4) Use the industrial version of the GFCIs (local code may require tamper proof version). The quality is much higher, and the wire connection screws are larger and more robust. They also have versions that are prewired using stranded wire or solid wire but are not always in stock. 5) For stranded 12 AWG Wire I use ferrules at the breakers. I like the square style crimp it fits nicely under the breaker screw clamp and keeps its shape. Don't forget to torque the breaker screws to specification, for Square D it is listed on the breaker body. 6) I like using crimped captive spade terminals to the receptacle screws, if the receptacle will not accept spade terminals I use ferrules, but here I like a hex crimp style. To daisy chain you can use twin wire ferrules two wires into one ferrule. You could also use butt splices (some are even step up and step down to allow two wires in one side of the crimp) with high temp heat shrink. To pass inspection it is good to have branded terminals and ferrules used with the branded or approved crimping tools. For example you would use Weidmuller ferrules with Weidmuller ferrule crimpers. When you use a spade lug under a screw head, like you would see if you build industrial control panels, you have a flat connection under a flat screw head, and once this is torque properly (screw is stretched) it will not come loose. I don't like putting a solid round wire around a screw if I can help it, and I certainly don't like to put a stranded wire around a receptacle screw and I never use the back stab easy insertion connections. 7) Use offsets where so the conduit is flush with the wall. Always support conduit with at least one wall strap even if the boxes are close together. With EMT you can bend your own offsets, or you can also buy premade EMT offsets. Bending EMT is not all that difficult it just takes a little practice. If the premade offset is too large for the junction box chosen you can use the two 3/4 inch knockouts that are across from each other on the box so the conduit entry is angled up and exit angled down which look fine. 8) I never use WAGO splices on receptacle branch circuits, I only use them with ceiling lighting circuits. 9) When modifying the GFCIs to fit in the metal face plate use a vice to hold your work you will have to take the ears off and cut off the threaded mount. 10) Use an automatic wire stripper to strip the THWN/THHN. Proper automatic strippers will not nick the strands. 11) Also test new Receptacles and GFCI Receptacles after installation with a dedicated branch circuit tester like the IDEAL 61-164 SureTest Circuit Analyzer (it will fully test GFCIs for current trip and trip time). As you can see the "workmanship" approach depends on who is doing the wiring and who the client is. My approach, as described above, and the approach in the video have nothing in common other than they both should pass inspection. The only real thing that I would do the same as in the video is have the branch circuit conduit come straight out from the side of the breaker box. This way the conduit run will not block any additional runs that need to go parallel.
@Danielthornton61 Жыл бұрын
*NEC (National Electric Code) mandates you to ground wire each switch and electrical receptacle box to EACH receptacle ground screw in those boxes, so that it's protected if the faceplate/ receptacle is off the box and the circuit is live, in order to trip the breaker instead of going through the person and not tripping the breaker. Just picture that live before you pushed the plate forward to screw the plate down...there is no ground protection, they have those codes for a reason.*
@donl1410 Жыл бұрын
State the code article to support your view, please
@RJ-ej1nr Жыл бұрын
NEC 250.118(A) .. equipment grounding conductor ... shall be one ... of the following ... (4) EMT. Please detail with code reference why you believe that does not apply.
@TomCee53 Жыл бұрын
@@RJ-ej1nrhe’s saying that the EMT provides ground to the box, but if the plate is loose, the receptacle would no longer be grounded. I know that nobody ever uses receptacles with cover plates missing or unmounted, but it’s the safest way. I also believe that receptacles are not considered grounded unless they have a listed brass contact between the frame and the box the screws are no longer sufficient. Again, check with your inspector. Local rules override code.
@urieaaron Жыл бұрын
I believe you are correct. The metal box and the conduit is the ground but the receptacles do have to have a ground wire to bond them to the box for the reasons you have stated. I can be wrong though, I have been retired for a long time and may have a faulty memory.
@RJ-ej1nr Жыл бұрын
@@TomCee53 He says "NEC mandates" and that's what I was responding to. I cited NEC code which allowed something other than what he said was wrote as mandated. Discussions on what could be problematic or a good idea or not are reasonable ones to have, but that's not what I was getting into with my response.
@4speed3pedals Жыл бұрын
I do not like to drill into mortar for Tapcon screws. The mortar pulls out easily, especially if aged.
@EverydayHomeRepairs Жыл бұрын
I am with you but this type of brick/block easily blows out so it is actually worse.
@wernerviehhauser94 Жыл бұрын
Use Fischer rawlplugs.... you know, the right tool for this job exists since over 50 years. Please learn to use it...
@theDgrader Жыл бұрын
yes, better to use proper fixings and stay away from the mortar and edges of brick to secure, you also need saddles on the conduit. If you follow this guy in the EU and do it without a qualification in electrical installation then you will Not be insured...
@glasslinger Жыл бұрын
@@theDgrader That is the MAIN consideration in the installation! It's not about safety or durability over time. It is ENTIRELY what the inspector writes on his report! If the insurance agent refuses to insure you can be in deep shit!
@mrcryptozoic817 Жыл бұрын
@@EverydayHomeRepairs I agree with that 100%. It's easy to crack that block; it's too rigid and brittle.
@scottcarr326411 ай бұрын
Here in Australia, PVC conduit and Boxes are used to do Household Electrical and Green/yellow Earth wires are used to every Power receptacle, we also use European Wiring code, Brown for Positive and Blue for Neutral. All our Household power is 240 volts most 10 Amp and possibly a 15 Amp outlet, (which have a larger Earth pin) anything larger than 15 Amp is Hard Wired.
@joetorres341211 ай бұрын
This is a clean installation. There is nothing wrong with this installation. No separate EGC is needed as the conduit is a compliant use as an EGC. With this installation all that is needed is to remove the insulating washers from the receptacles for metal-to-metal contact that extends all the way to the panel. He is also using THHN 12awg which is also compliant. EMT can be used underground and within concrete. It's perfectly fine for this damp location installation. If anything there should be a conduit support at the center of the 6 foot length per 358.30. This is an excellent how-to video despite the hypothetical what-if's mentioned.
@pld899311 ай бұрын
Yes, there is something wrong. In addition to the 6' run needing support, receps are grounded incorrectly. Need a grounding pigtail from box to receps, or receps must be riveted (or some other permanent means of attachment) to the cover.
@joetorres341211 ай бұрын
@@pld8993 If it was a plastic cover i could see the need for the pigtail, but it is metal and receptacles are secured to the face plate with locknuts and the plate is fastened with screws. The mechanical ground is sufficient.
@pld899310 ай бұрын
@@joetorres3412 Electrically it works, but it's a violation, 250.146(A)
@MegaMcwizard10 ай бұрын
@@pld8993 I'm learning here so would like your feedback. the two conditions 250.146(A)(1) and 250.146(A)(2) appear to BOTH be met since the author states that the device screws have ridges on the underside of the head which I am interpreting as complying with "screw or nut locking means".
@pld899310 ай бұрын
@@MegaMcwizard Ridges under the screw head or nut is not a locking means because it doesn't lock the screw. Irreversible screws, rivets, screws with a locking nut, or the addition of lock washers to what he has would be required.
@stevekovacs4093 Жыл бұрын
What happened to the conduit offsets?
@pld899311 ай бұрын
Not necessary. He should have added a mini to the center of the 6' length that way he did it, or he could have used box offsets to get it tight to the wall and used a 1-hole strap. Either way is fine.
@artyaffe6439 Жыл бұрын
I was under the impression that three feet of the floor in front of the panel had to be kept clear; in fact, an inspector chastised me for having a lightweight folding chair open in front of the panel (but allowed me to remove it before he began his inspection). If that's NEC, the battery box you have in this video is in the way, and should be moved.
@markkempton4579 Жыл бұрын
that's a portable box. I assume he put it there for the video.
@chriscordray8572 Жыл бұрын
You are correct. Nothing can't be overhead ( say a water line) or 3 feet in front of any electrical panel.
@tomasdvorak7307 Жыл бұрын
I'm not an electrician but intuitively it occurred to me that the battery placement is less than ideal. It has a non-zero probability of self combustion and who'd want to trip the main breaker two feet above a battery in thermal runaway mode?
@larrychristian7239 Жыл бұрын
Scott, your panel should have mounted your garage service on thin strips of wood so there is an air gap behind it so that moisture from the all will not compromise the integrity of the panel. The usual way is to mount a couple strips of wood and then mount a piece of plywood to them thus giving you a solid foundation to mount your panel.
@donl1410 Жыл бұрын
The enclosure has ¼ inch standoff features stamped at the mounting holes to account for this, by code.
@pld8993 Жыл бұрын
Not necessary in above-ground garage.
@ckm-mkc Жыл бұрын
@@donl1410 Still would be much better for it to be mounted on a plywood backing.
@coreyfranco7060 Жыл бұрын
@@ckm-mkcthats a waste of time
@greggpurviance725211 ай бұрын
@@ckm-mkc plywood is not that stable over time. Have come across several panels hanging on rotting plywood. Agree it is a waste of time & unnecessary
@hornetd7 ай бұрын
I'm a retired Journeyman electrician and I do have opinions on your Electrical Metallic Tubing installation and I think it falls somewhat short of NEC compliant. The NEC requires that EMT be supported within 3 feet of each box and every 10 feet of continuous run. Since the length of the longer piece is 6 feet that would require one of those Mineralac conduit clips at exactly 3 feet as the minimum required support. There would also need to be a support in the 3 foot run because every length must be supported independently of the boxes. There are exceptions but none of them apply to that installation. I will not harp on my particular beliefs on grounding for raceway installation because the US National Electric Code (NEC) doesn't have a requirement for a particular conductor type for Grounding in them. [Raceway is a term encompassing any enclosure for wire and cable that provides physical protection and, in many metallic raceway installations, the low impedance ground fault current path that is required by the NEC.] Since the code requires that a raceway system be complete prior to the installation of conductors I can test the raceway assembly for its impedance back to the service equipment's Main Bonding Jumper before the first conductor is installed. That is good practice anyway because an electrically discontinuous portion of a raceway run can act as a high impedance choke against the flow of fault current in a wire EGC and thus hold the amount of fault current below the trip level of the Over Current Protective Device. [In residences that will nearly always be in the form of a fuse or circuit breaker.] Keep in mind that although an Equipment Grounding Conductor (EGC) does not count as a current carrying conductor for ampacity calculations it does count toward conduit fill. So, depending on the details of the installation, using a metal raceway as the EGC may save going up a raceway size thus raises the cost of the whole installation. The more conduit you are installing the more that effects the cost. My position then is that there is no ONE correct answer for whether an wire EGC should be installed with the other wire conductors in a raceway system. It should be done were experienced judgement suggests its use. But were it is clearly unnecessary I would sometimes do without it to hold the customers final cost as low as is practical. I've come to prefer running EMT, in unfinished areas, vertically rather than horizontally because it deters the occupants from using the EMT as a support for other things such as coiled hose and cords. There are changeover fittings that are listed for 2 NM cables that allow me to run the NM cable through bored holes in the floor joists above and removed from most causes of physical damage. One piece of EMT running down to the surface wall box then brings NM cables from each direction down to the box. The cable must be sized as a single conductor calculated as a round conductor for its cross sectional area based on its widest dimension. The conduit size is then selected from the % of the conduit that may be filled by 2 conductors. 2 conductors is the least percentage of fill. Alternatively the NM can enter a surface box near or on the joists and be spliced to individual conductors which take the circuit down to each lower box. That is more splicing but it may save 2 nominal sizes of EMT. The larger EMT with the only one box at user height saves splicing work and reduces the number of points of connection failure. All of these are choices. There is seldom only one way that an installation can be done. Tom Horne
@pld89937 ай бұрын
Anything less than 3' does not need additional support independent of the boxes.
@hornetd2 ай бұрын
@@pld8993 What he said in the video is 3 feet. That means it gets a strap.
@pld89932 ай бұрын
@@hornetd There is no rule that says every conduit run must be supported independently of the boxes. Up to and including 3', no strap needed because each box/fitting provides support within 3' of the other box. Additional support needed for anything longer than 3'.
@SiteReader9 ай бұрын
When your not using a dedicated ground wire, it seems to me the ground connection becomes dependent only upon those two screws holding in the face plate. In a damp environment, such as a basement, those could corrode or rust over time, interrupting the ground connection to the breaker box and ultimately to the ground rod in the soil. Those screws could also work loose, interrupting or at least weakening the path to ground. The extra work of adding a single green wire seems well worth it to me. I'm a science educator, not an electrician. But what do you think?
@pld89939 ай бұрын
Why would fitting screws magically come loose or corrode but a ground screw is immune to those same issues? Nonsensical, conduit grounding path is solid and as long as it's installed properly will last for decades. EMT is installed outdoors every day so in a basement, even if there's dampness present, it's a non-issue.
@SiteReader9 ай бұрын
@@pld8993 You've got a point there, but with both a ground wire and conduit, you've got a backup in case one or the other fails. For the minimal extra cost of a ground wire, it seems a no-brainer to me.
@pld89939 ай бұрын
@@SiteReader True, in this case the cost and labor to add a ground wire is miniscule, but I've done projects where adding ground wires would add many thousands of dollars to the project, sometimes requiring larger conduits to accommodate the ground also.
@SiteReader9 ай бұрын
@@pld8993Ahh, I see. Well, as I said, I'm not an electrician but a science writer and teacher. If I were doing this in my house, I'd certainly add a ground wire. . . Come to think of it, I did a small installation in the garage of my old house where I ran conduits to two boxes on one wall to power an overhead light, my saw, and other plug in tools. I used 12 ga. Romex (which I think I recently read isn't the right thing to run inside steel conduit). I was planning to switch out the breaker to a 20A one, but I wasn't sure how and never got around to it.
@pld89939 ай бұрын
@@SiteReader There's nothing wrong with running romex in conduit and it's sometimes required. Two of the biggest myths in the trade are a) romex is not allowed in conduit and b) everything must have a wire type ground. Both false.
@paulainc10 ай бұрын
I might have missed it with 1500 comments. But he is running 12/2 wire with a 20A breaker. Using a 15A GFI. I would think you would need a 20A GFI too. The 15A outlets I understand, which would be code since there are a few outlets. But 20A ones would be better!
@Ron_P6 ай бұрын
You can use #12 wire with a 20a breaker and 15a receptacles. Code says must use more than one receptacle so a single duplex would be sufficient. It's just about the only thing he did correctly in this video.
@davevandervelde47995 ай бұрын
I am a master electrician in Canada and we are not permitted to install 15 amp rated devices on a 20 amp breaker, no matter if the wire size is #12 . That was one of many mistakes I saw in this video. Why is a diy teaching electrical? Most people think it looks ok.
@seephor Жыл бұрын
Don't quote me but I believe EMT doesn't pass as a ground even though it's attached to the panel here in California. I believe the reason is that the conduit connections can come lose and some weather resistant connectors/couplers have plastic mating surfaces which breaks the bonding.
@EverydayHomeRepairs Жыл бұрын
I would agree that a local inspector, jurisdiction, or state could require a dedicated ground back to panel. Probably worth a call to see how the inspector is going to interpret code.
@pld899310 ай бұрын
CA electrical code allows EMT as a grounding path. The raintight fittings have a plastic washer internally, but in no way do they disrupt the metal to metal contact between the conduit and the fitting. EMT fittings don't just magically come loose any more than ground screws magically come loose.
@MrKen59 Жыл бұрын
I believe you need to secure conduit within 3 feet of a box. Thought 3/4”was overkill, but certainly sexy and helpful if you are running some 10 awg down the line for a future dryer outlet. NM is not Illegal in EMT, and my preference is to run a green wire as it’s not that far and it’s an extra safety margin IMO. I love metal BTW as it looks awesome. Nice presentation.
@realtyrocks1969 Жыл бұрын
That's correct. And every 10 feet for straight runs. If the box is 3 feet or less to the breaker it doesn't need to be supported as it's supported on the end but should still maintain that every 10 feet standard. I believe the one in this video was a run of 3 to the box and another 6 feet to the next box though so it's fine just screwing. Securing wouldn't hurt though if you wanted to put one up on each section to be safe.
@blueplasma5589 Жыл бұрын
BTW braided twisted wire, bye the way?
@jeffriley-lq5np Жыл бұрын
it nay be sleeved but since this is a complete conduit system no. the device looses ground if removed . stay in your lane kid you have no business teaching anybody wireing
@realtyrocks1969 Жыл бұрын
@@jeffriley-lq5np cool story bro. NAY hu?
@realtyrocks1969 Жыл бұрын
@@blueplasma5589 it's just by the way. Bye means the opposite of hello. And it's not braided twisted wire. It's THHN and THWN specifically. Braided twisted wire is not solid core wire. Use 12/3. Not that hard to figure out dickweed.
@jentronics375411 ай бұрын
If you do use a pipe cutter you can score the pipe by cutting a groove instead of cutting through the wall of the EMT. Then use a pipe bender on the groove and it will snap in two. If you did it right there will be no sharp edge inside the pipe. The sharp edge will be on the end of the pipe. Do note some electrical contractors probably be ready to fire an employee for using a plumbing pipe cutter. If cut all the way through, an unremoved sharp burr insde the pipe could "shave" the wire as it is pulled through the pipe. I know I would be nervous having an employee using a plumbing pipe cutter.
@TangoIndiaMikeJuliet10 ай бұрын
Most people I know use a hand-held band saw to cut conduit.
@pedroespinal6871 Жыл бұрын
Once you dismount the GFCI from the metal box....it is no longer grounded. I recall that in another one of your videos you used a wire to ground the GFCI to the metal box to ensure protection from hazards in the event of servicing the GFCI or testing the circuit lines when servicing. The GFCI protection performance is assured when it is grounded and being serviced.
@EverydayHomeRepairs Жыл бұрын
Actually the GFCI will work independent of a ground. There could be no ground and the circuit would still have GFCI protection when a difference between the hot and neutral is detected.
@KarlUppianoKarlU Жыл бұрын
I would run a ground wire, even though the conduit and metal boxes ought to work. If the conduit screws loosen, the conduit could become intermittent. A ground wire inside would ensure that the boxes are still grounded even if the conduit becomes loose. Then I would also tie the ground wire to the green screw on each outlet.
@pld899311 ай бұрын
Fittings screws will not magically loosen. If that was true, why would it apply to conduit fittings but not to a ground screw?
@AF-O6 Жыл бұрын
Even though your way is 100% fine, it simply makes me feel better to run a ground conductor in a raceway, and have a ground connected at each outlet. That way, if for whatever reason the plates aren’t touching the box, the circuit is still grounded.
@robm3063 Жыл бұрын
I piped EMT in homes for over 20 years here in Chicagoland west suburbs (IBEW 701) . EMT is what we do here that's code. Never pulled a ground once unless it was through a PVC underground slab pipe. Now some towns do make you put a ground from the box to the outlet mainly while using Garvin covers like this video.
@greggpurviance7252 Жыл бұрын
& insulated ground needed for isolated ground receptacles
@vwvan Жыл бұрын
Never drill into the mortar. Only into the main block itself. The screws will not stay tight in the Mortar.
@sigcrazy7 Жыл бұрын
I was thinking the exact same thing. I'd have bent an offset to get the knock-out off the mortar line so I would be drilling directly into the block.
@taxicamel Жыл бұрын
@@sigcrazy7 .....far easier to drill mounting holes in different, wider locations. .
@Sembazuru Жыл бұрын
@@sigcrazy7There were plenty of knockouts in that box, he could have chosen the next one up or down to avoid drilling in the mortar. I was actually a little concerned about that red wire in the box that got closer to that unibit for my comfort. Probably didn't shave any insulation off of it, but as I said, it was a little close for my personal comfort.
@ericgautreaux175211 ай бұрын
In mortar,use lead anchors.
@ptg015 ай бұрын
Great explanation on why you are not installing a ground but seems so much simpler to just run a ground wire while you are at it.... Less probability of mistakes in the future...
@TexansForChrist8 ай бұрын
I've opened up boxes where I had correctly used Wagos with correctly stripped wires and found wires pulled out of the Wagos. When you fold and then jam your wires back into the box there will be pressures and stresses on the Wagos that will make you have nagging doubts. I don't make any money endorsing anything and the only thing that I have full trust in, as a DIYer, is a good twisted connection. That gives me the peace of mind I seek
@EverydayHomeRepairs8 ай бұрын
Thanks for the feedback 👍
@rickhawkins2186 ай бұрын
@@EverydayHomeRepairs I have used wire nuts and wegos and i would trust a wire nut a lot further than a wego.
@LordHog Жыл бұрын
I always wondered, with using the metal conduit as the ground isn’t there an hazard if current is flowing through the conduit, if something goes wrong, and a person touches the conduit? Also, why not use an AFCI outlet? I thought those were mandatory to use I today’s code?
@EverydayHomeRepairs Жыл бұрын
If a hot conductor was to short against the box that would provide a path back to ground and trip the breaker. Specifically in this instance since the circuit is GFCI protected the GFCI breaker would trip before the breaker as a small difference between the hot and neutral would be detected. If there was no GFCI, and no path back to the panel for ground, and the hot conductor shorted then the conduit could ground through you when you touched it.
@davidg428811 ай бұрын
That doesn't look like a living space that would require an AFCI. It does look like an unfinished area that would require a GFCI as he used.
@outlet6989 Жыл бұрын
Thanks to your video, I've ordered the Locknut Wrenches. I didn't know they existed. Did you say the cable sheathing should be removed if the installation location was considered a 'wet' location? How does one think an inside garage wall is a 'wet' location? When installing conduit, I always place a plastic cap on the ends to prevent the wires from being damaged. A Master electrician lives in the house behind mine. He helps and teaches me when I do electrical DIY projects. I asked him to watch this video. Later, he grinned and bent his head backward.
@knothead52 ай бұрын
To tighten the lock nut, put a screwdriver on the top tabs and tap with a hammer.
@davideyres955 Жыл бұрын
It would be interesting to see what the resistance of the conduit was at install and over time. I guess the GFI on the socket means this is less of a problem but in the uk the electrics rely on the fuse board / breaker panel to provide short circuit protection via mini circuit breakers and what we call RCB (RCBO or RCCD) so the resistance is critical for calculating trip time for the breakers.
@EverydayHomeRepairs Жыл бұрын
I will do that test today as a side project to test the resistance of the conduit along the length compared to a 12 gauge insulted ground wire.
@mxslick50 Жыл бұрын
The GFCI does not give a pass on grounding requirements or integrity, it is a device and as such can be easily damaged or fail, resulting in loss of GF protection. While Code allows conduit to be used as a grounding conductor, it is in the REAL WORLD a bad practice. Any damage to fittings can cause a high resistance or lost grounding path, which is dangerous. And candidly, with such a short run there is absolutely NO EXCUSE for not using a separate grounding conductor, NONE.
@ronlovell53749 ай бұрын
You should always run a separate ground conductor. Redundancy is key in case any conduit connections come loose or suffer corrosion. At the panel you should use a bonding nut on the first connector. The enamel on the equipment or slight variations in the size of the hole can compromise the strength of the ground connection. Also you should use nylon or pvc isulating bushings after the nuts on all the connectors to protect the wires insulation. And finally, code requires the conduit to be strapped within 3 ft of any box or encloser.
@pld89939 ай бұрын
Fittings do not magically loosen any more than ground screws magically loosen. Corrosion, except in the harshest of conditions, is rare. Redundancy is unnecessary on a properly installed conduit system.
@ronlovell53749 ай бұрын
@@pld8993 Yes, I somewhat agree with you, but as someone in the industry, and does a fair amount of commercial work, I don't think I've ever gone in any shop or warehouse that didn't have conduits hanging by the wires or off some random mangled J-boxes. Where there's people, machinery and equipment there's damage, which is great for me being in the maintenance/service business anyway.
@Johnlee051310 ай бұрын
FYI in Michigan-no problem running 14/2 Romex in EMT with ground in my unfinished basement against wall. Ran two circuits 9 boxes all city inspected and passed
@mabelisle Жыл бұрын
The thing I don't like is that the breaker panel is painted and your connector is creating an inconsistent grounding with the box depending on the hole size and if it is touching the metal properly. I'm no expert but I see that as a risk pretty substantial risk.
@aurvaroy6670 Жыл бұрын
Well the GFI tripped so what's your point lol?
@andydelle4509 Жыл бұрын
GFCI's don't need a ground to work. They sense an imbalance between the hot and neutral. If the imbalance exceeds 7-10ma, they trip as some of the supplied current is finding another return path, perhaps through you. That said I am not advocating not to use a ground wire and neither does the NEC except when replacing old two wire receptacles with a GFCI.
@mabelisle Жыл бұрын
For your argument to hold the GFCI would need to be before the conduit and not in it. Which means that the cables leading to the GFCI and the connection to it are not protected if the ground is not proper.
@andydelle4509 Жыл бұрын
@@mabelisle I'm not following you here? The feed wires to any receptacle mounted GFCI are not GFCI protected. But they are still protected by the panel breaker. GFCIs are only required for certain receptacles in certain areas. Hard wired appliances such as air conditioner condensers and pool pumps do not require a GFCI as the are properly grounded with a permanent ground wire. Again, the ground terminal on a GFCI has nothing to do with it's GFCI functionality.
@GigsTaggart Жыл бұрын
@@andydelle4509 I think they are saying that there's a real world risk. If the conduit ground is broken at the panel fitting, and the before-the-GFCI hot contacts the metal conduit, you have a hot chassis situation that will not trip the GFCI and could give you a bad shock. He should have just used a ground wire, I think the majority of people would have.
@netpasya Жыл бұрын
Great Video. Before we moved into our new house, I had an electrician buddy install outlets on (2) 20 amp circuits on all 4 walls. He installed 12 outlets--on 2 GFCI breakers. He put the conduits vertically. He did offset bends to put the conduits flush to the concrete walls. He did run romex inside the conduits, short distance up to the open ceiling. I was there with him, helping out as best I could. We were drinking beer. We had music playing. We talked about life, etc... I love the job we did till this day.
@EverydayHomeRepairs Жыл бұрын
Sounds like a pretty fun Saturday 🍻
@bobsbarnworkshop Жыл бұрын
I learned to bend offsets by eye early in my career, but when we were on bigger jobs we had an offset bender tool! Just stick the end of the emt in, push the lever down, BINGO!!! Offset!
@bobsbarnworkshop Жыл бұрын
We did a lot of EMT drops with romex inside as you described many times when I was an electrician in the 70’s. We put box connections on the open end as bushings. Usually at businesses with drop ceilings and block walls. So it was apparently an acceptable practice back then. I would have no reservations doing it now, at least for private use!”Ya done good”!
@psdaengr911 Жыл бұрын
@@bobsbarnworkshop It's still acceptable as the codes do not allow Romex within 8" of the floor. If this were a commercial, industrial or hospital site, an inspector might require a box with an insulated bushing above ceiling height, with romex splced there, but it would be rarer at a residential site.
@BatMan-co1gy Жыл бұрын
I'd go vertical also, just looks cleaner
@richardyates1033 Жыл бұрын
Your metal boxes should be mounted on a moisture barrier, i.e. piece of wood. This keeps the boxes from rusting from the moisture that comes through those cinder blocks. That wall shows signs of moisture penetration and efflorescence already. Additionally, although you may not technically have to run a grounding conductor through that conduit, it is a good practice to do so. Over time, the set screws in the connectors and conduit will loosen and/or corrode losing the bonding effect for the ground path. I believe that running Romex in conduit may cause a possible overheating situation due to the temperature rating of the Romex and it being enclosed in conduit.
@johnrocha5294 Жыл бұрын
@@karlwithak.my guy
@jonpatterson721111 ай бұрын
Actually Karl, the code is written by the assholes that manufacture electrical equipment. Find a copy of the NEC and look at chapter 9, "The code writers board". It'll make you sick.@@karlwithak.
@centurionhomeinspectionsin22538 ай бұрын
NM in conduit inside is absolutely fine and code compliant. Only in wet locations do you need to run individual THWN conductors
@keithharrington871511 ай бұрын
I am going to defend this gentleman. I like that he is encouraging people to think about electrical work and how much goes into it. Did he do it the way i would, maybe not. Did he violate code? That is a harder question because code can change from place to place. In this specific case, is the basement a dry location? is it damp? A dry basement means he could use nm cable inside the pipe. A damp location puts extra requirements on the receptacles he installed. This is all code book requirements, but what about ahj and there requirements? Good job sir, keep up the good works.
@karllaun2427 Жыл бұрын
The 20A outlets I find locally look different than the ones you installed (shape of the neutral). Do these vary by region?
@EverydayHomeRepairs Жыл бұрын
Nope, all 20 Amp outlets will have the horizontal slot you are referencing. As long as you have more than one outlet (even just a duplex outlet) on the 20 Amp circuit you can use 15 Amp.
@holysirsalad11 ай бұрын
No, those are NEMA 5-15R (15 amp receptacles) and they are not rated for 20A service. There's no protection device to prevent an overload of those receptacles in this circuit. I am not sure if this is code where this was filmed but it's not a great idea in general.
@louisogden8033 ай бұрын
As a retired professional electrician, I WOULD have mounted the conduit against the wall by bending an offset where the pipe leaves the panel and where they enter the 4" square boxes. I would also have used the third green wire (#12 THHN) to make a reliable ground.
@pld89933 ай бұрын
There's no need for box offsets in this installation, and the EMT is a reliable ground. Neither offsets or a wire EGC is wrong, just unnecessary.
@louisogden8033 ай бұрын
@@pld8993 I was simply stating how I would have accomplish this same task. Yes, the conduit makes a good ground unless a connector comes loose. Your work is neat and well done (up to code standards). No hard feelings. I did mostly commercial work and that was how I was trained back in the 70s when I was an apprentice. Thanks for your response.
@davidcook113020 күн бұрын
my thoughts exactly... where's the bends?
@louisogden80320 күн бұрын
@davidcook1130, thanks David. My main reason for doing this is to get rid of the hanger type strap which will be constantly snagging your clothing when walking by. With the offsets, a single-hole strap can be used with the pipe against the garage wall.
@briankowald6465 Жыл бұрын
I would have used a bender to put offsets in the conduit, or just bought the connectors that have the offset.
@davidcolantuoni916511 ай бұрын
Especially in a workshop. Were we are all guilty of using that nice screwdriver/ chisel storage space between the emt and wall !
@munsters29 ай бұрын
Aren't you required to have bushings on the connectors to protect the wires?
@pld89939 ай бұрын
Not if the conductors smaller than #4
@marquisdemoo179210 ай бұрын
Although it was a UK style 220V system, I did have an issue with some work benches in Hong Kong where the faceplate securing screws loosened and there was a non-existent ground return. As a minimum I would advise connecting the face plates to the conduit boxes with a short bootstrap earth lead and not relying on the faceplate screws. Actually, better still run a ground wire back to the distribution board and then you are covered for any loose or corroded joints in the future.
@dougdiplacido240611 ай бұрын
I never use the conduit and boxes as a ground. Loose connections can occur way to easily. Run the green ground wire always.
@racenuke Жыл бұрын
This install is not to national code standards. See: NEC 358.30(A) You need straps every ten feet and within 3 feet of every outlet box, device box, cabinet; conduit body, or other tubing termination.
@bb55555555 Жыл бұрын
Also to me that is the perfect application for MC cable. What is wrong with using MC cable? So much easier to work with and install.
@EverydayHomeRepairs Жыл бұрын
For installation like this I actually like the clean look of conduit. I know it takes a bit of getting used to but overall I like the finished product. Probably just me but overall I am not a fan of MC.
@TwilightxKnight13 Жыл бұрын
In most people's opinion MC looks like garbage in a visible application. No matter how well it is installed, it will droop. It is generally used for lighting whips and in wall cavity areas with limited access or that require more protection for the wiring than Romex provides.
@bb55555555 Жыл бұрын
@@TwilightxKnight13 of course it's going to droop. That's why you put in supports. I would argue it's still better looking and safer than bare romex in a garage, which is what my previous owner did.
@Zappy121010 ай бұрын
35 years experienced electrician here. Just a few things I'd like to address. First, it's just not a good idea to NOT run a ground wire in any metal conduit. Yes technically it is legal to use the metal conduit as a ground, but the conduit can easily be compromised. Loose locknut, corrosion etc will cause you to lose your only ground which makes it very unsafe. You are pulling wire anyways, just pull a ground too, it's just smart. Second, these spring/lever type wire connectors are just not safe. I was all in on them several years ago when they first popped up. Since then I have gone back on jobs for issues and it is almost ALWAYS these type of wire connectors that cause the problems. Under long term bigger loads they become weakened and brittle. I have seen them completely melted many, many times. Use a good wire nut and have piece of mind knowing as long as installed tightly with wires twisted together you will never have any issues from them. Wire nuts take just a few more seconds to install and IMHO is worth it when lives may be on the line.
@CybekCusal8 ай бұрын
35 years experience and you think painted metal provides a code approved ground?
@Zappy12108 ай бұрын
@@CybekCusal Don't recall saying that...
@CybekCusal8 ай бұрын
@@Zappy1210 you said it's legal what he did but it's not.
@Zappy12108 ай бұрын
@@CybekCusal According the NEC it is in fact legal to use metallic conduit as a ground source. I do not agree with that code at all, but it is technically legal.
@CybekCusal8 ай бұрын
@@Zappy1210 not if the metal knockout is painted.
@Rivenworld Жыл бұрын
Hi, I am in the UK so presume the 'code' may be different but I would have thought the extra layer of insulation on Romex would be a good thing but obviously I am wrong. What is the rationale behind this? Many thanks.
@67L-88 Жыл бұрын
I don't have an official answer but I was always told it was due to the wire temperature rating. Inside the conduit, the Romex does not get enough air around it for cooling?? Also, I think it was not rated for being in conduit?
@holysirsalad11 ай бұрын
Romex is permitted inside EMT in the United States. Conduit has a maximum fill ratio to deal with heat dissipation. It's metal so it does allow some heat out. I imagine rules are different for PVC. It's not a great idea though as Romex is pretty stiff and you can't rearrange the wires so easily, so it takes up a lot of space compared to stranded wire.
@danielstickney2400 Жыл бұрын
That step bit you used to enlarge the hole in the panel makes a much better pipe deburring tool than the thin, cheesy deburring blades on most pipe cutters. You don't need a drill, just turn it by hand.
@jfowler702910 Жыл бұрын
I believe that you still need the ground wire pigtail from the grounding terminal on the device to a ground bonding screw inside the box. Yes you can use the metal conduit and boxes as the grounding BUT as soon as you remove that outlet cover with the outlets from the box, the cover as well as the outlets are no longer grounded. A pigtail ground from the devices to the box needs to be in place for when the outlet cover is removed. This allows for troubleshooting on live electrical circuits where all safeguards (i.e. grounds) are still intact on all metal equipment.
@donl1410 Жыл бұрын
NEC does not require the ground pigtail, 250.146(A)
@jfowler702910 Жыл бұрын
@@donl1410 "I believe" was a bad choice of words. While the code allows it IMO it's only a matter of time before someone has a cover removed while testing/troubleshooting a live circuit and becomes the path from the energized ungrounded cover and devices to the grounded box. Once someone gets injured or dies they'll eliminate this code allowance.
@realtyrocks1969 Жыл бұрын
I always put some construction adhesive on the juction box behind it to the wall. Helps hold it a bit stronger and seals around the drill holes a bit better. The gauge of wire youre using is the same as the Romex. There is nothing wrong with using romex in conduit.
@donl1410 Жыл бұрын
Can you support, "There is nothing wrong with using romex in conduit." Code citation, please
@realtyrocks1969 Жыл бұрын
@@donl1410 absolutely. The NEC states you can't use Romex in damp or wet locations or in conduit ran under ground. That code is 334.12 (b)(4). There is nowhere in code that it can't be used in any conduit or in garages or other areas that are not underground or wet or damp locations. Romex is the same gauge wire as individual strands and is actually better protected than individual strands. Old times don't do it because it's cheaper than Romex, not because it's any safer or better. I challenge you to find code that says that you can't... Because it's not in there.
@realtyrocks1969 Жыл бұрын
Old timers*
@HypherNet Жыл бұрын
@@donl1410 This appears to be covered in Section 334 of the NEC. In short, I read it as saying that where an NM/Romex cable is exposed, it muse be protected from physical damage, and lists EMT among other things, as acceptable protection. The inspector in my jurisdiction told me, if I recall correctly when I asked, that a single NM cable in conduit is allowed, but not with anything else. Below are the code sections, titles, and a link if you're curious for the details. Disclaimer: I am not an electrician, just a hobbyist who likes understanding code. Everything I say might be totally wrong. Article 334 Nonmetallic-Sheathed Cable: Types NM and NMC 334.15 Exposed Work In exposed work, except as provided in 300.11(B), cable shall be installed as specified in 334.15(A) through (C). 334.15 (B) Protection From Physical Damage, states: Cable shall be protected from physical damage where necessary by rigid metal conduit, intermediate metal conduit, electrical metallic tubing, Schedule 80 PVC conduit, RTRC marked with the suffix -XW, or other approved means. Link here: up.codes/viewer/texas/nfpa-70-2023/chapter/3/wiring-methods-and-materials#334.15_(B)
@realtyrocks1969 Жыл бұрын
@@HypherNet In addition to the 334.12 I cited before where it states where Romex can be used these others further demonstrate nothing about not being used in conduit.In fact in a garage is an area where it could be exposed to physical damage, as states in your above codes, that REQUIRE Romex to be protected if used (conduit). So basically there is nowhere it states you can't use it conduit, and it states areas you can't use it (these areas include wet, damp or underground locations - doesn't apply here) and states that if you use it, it must be protected (ie inside conduit).
@MitrovichtheMagnificent3 ай бұрын
When using the box and conduit for ground, make sure the exposed work cover has crushed ears, if it doesn't you need a bonding jumper. I'm not sure how many newer ones come like that but many old ones are
@rickmorenojr8 ай бұрын
Romex can be installed in conduit so long as the conduit isn't going to be in wet locations (outside). A basement or garage is considered dry locations. Romex sheathing unfortunately takes up a majority of conduit fill preventing multiple Romex runs unless you size the conduit accordingly. Another reason to use THHN type separate conductors is that they are way easier to pull through conduit, Romex tends to bind up.
@mxslick50 Жыл бұрын
The GFCI does not give a pass on grounding requirements or integrity, it is a device and as such can be easily damaged or fail, resulting in loss of GF protection. While Code allows conduit to be used as a grounding conductor, it is in the REAL WORLD a bad practice. Any damage to fittings can cause a high resistance or lost grounding path, which is dangerous. And candidly, with such a short run there is absolutely NO EXCUSE for not using a separate grounding conductor, NONE.
@EverydayHomeRepairs Жыл бұрын
I agree, running a ground would be a better option and give a backup to avoid failure. Thanks for the feedback.
@hotflashfoto Жыл бұрын
I think that using the raceway is a lousy means of providing a ground. Anything that can possibly carry current should be a dedicated conductor. I mean, what does your family's safety mean to you? Is it worth the $1 or $2 you'll save if just one of them is ever injured? What happens when the faceplate is removed from the 4x4 box and power is energized? Yep, no ground. And no GFCI, either.
@EfficientRVer Жыл бұрын
You're right about no ground. You're wrong about no GFCI. While here, there is no ground available at the outlet (of a removed cover) for a GFCI tester to use to create a fault to ground (which will trip the GFCI) the GFCI will still trip if the current in the hot and neutral are not equal. For instance if some of the current returns via neutral and some returns through your body to a grounded water pipe you are touching. Basically, you confused whether a GFCI tester will trip the GFCI, with whether or not an actual ground fault at the actual outlet will trip the GFCI. They are not the same thing, specifically when the ground prong of the outlet the tester is plugged into, isn't grounded, so the tester fails to create a ground fault to test.
@hotflashfoto Жыл бұрын
Thank you for making that information more accurate for me. You're right, I was assuming that the ground path had to be complete for the GFCI to operate.@@EfficientRVer
@SteveM0732 Жыл бұрын
It doesn't sounds to me like best practice to not run a ground wire if you have to check with the AHJ to see if it is permitted.
@pld8993 Жыл бұрын
You don't have to check with the AHJ is you're following the NEC. There are 14 different types of grounding conductors allowed, and only 1 of them is a wire.
@electricboyo11 ай бұрын
Learned something new from reading the comments: Do not use plumber’s tubing cutter on EMT. Better to use hacksaw. Tubing cutters leave behind a sharp inside lip which is difficult to remove. Another thing I do is to screw a plastic bushing onto the threads of the EMT connector inside the J box. This provides really good protection against chafing the insulation on the wire.
@doug871811 ай бұрын
Several points: 1) Wire is cheap, compared to safety...always run a grounding (green or bare) wire through the conduit and to outlets/switches. Your metal ground through the boxes/conduit depends on tight screws, etc. Screws will work loose over time, which will destroy your grounding conductor system. This is dangerous situation that could occur and you'd never know it until disaster strikes. Having a separate grounding conductor provides redundancy. If someone later does work and fails to re-tighten screws, you won't be in trouble. 2) You stated this is a 20Amp circuit, and you correctly used 12 gauge wire, yet you used 15 Amp outlets. You no longer have a 20Amp circuit. 3) While you did say you turned off the power to your sub-panel, it's always a good practice to actually put a meter on it to ENSURE the power is off. Taking 30 seconds of extra effort provides extra safety. This rules out any hint of something not going as planned when turning a breaker off (if it happens to be the wrong breaker). 4) I think you'll find that unless you're in a wet environment, using NM type cable (Romex) is perfectly fine inside a conduit, provided you follow any derating required by code.
@larrychristian7239 Жыл бұрын
Scott, one more time. At the 10:00 minute mark when you talk grounds, you should be aware that anyone one who has gone to school for an electrical license will tell you that you do not need to run a ground all the way back to the panel. But you should install a pig tail to the ground screw on the box and pigtail a ground to each separate device. Especially the GFI as if your screws become loose for any reason holding the receptacles to the cover you then could have huge complications with grounding. That effectively ties the ground on the devices to the metal pipe.
@generessler6282 Жыл бұрын
Actually 'no Romex in conduit" seems to be a myth. NEC Article 334.15 on NM sheathed wire says "Cable shall be protected from physical damage where necessary by rigid metal conduit, intermediate metal conduit, electrical metallic tubing, Schedule 80 PVC conduit, RTRC marked with the suffix -XW, or other approved means." I'm not an electrician, but this seems pretty clear.
@jrock865 Жыл бұрын
you can do it but you have to go by conduit fill which makes running it in any conduit just ridiculous. Also you can only do it in dry areas.
@TwilightxKnight13 Жыл бұрын
@@jrock865 there is zero difference in conduit fill calculations if you run three #12 THHN vs 12-3 romex. Conduit fill is based on current carrying conductors, not the insulation. That being said, the installer is also responsible for ensuring that the wiring is not damaged when installed and pulling Romex through conduit is much harder than single wire, so the risk is there for problems. As such, you should avoid running Romex inside conduit.
@jrock865 Жыл бұрын
@@TwilightxKnight13 romex is a cable assembly you have to use the cross sectional area of the cable.
@KevinCoop1 Жыл бұрын
My first NEC when I was an electrical drafter, was 1981. Back then NM was not allowed except for up to 24” sections. Then it was allowed to protect cable in basements by using conduit down the walls if exposed and the 24” went away. Then they said that NM in conduit fill was not to exceed 53%. Now we are at what you said. It was intended that short pieces of conduit be installed down the walls. Now people are running it horizontal full length and nothing I can find specifically that states to not do it.
@jrock865 Жыл бұрын
@@TwilightxKnight13 actually there is a huge difference in running 3 #12 thhn and a 12-3 romex....the conduit will be bigger always when running nm-b in a conduit. NM-B is also sized as a single conductor meaning it can be 53 percent fill which lets face it would be ridiculous to pull romex's in conduit you'd be running 2 inch conduit all over the place in a dry location just not feasible. so can you run it in it yes in some instances that are dry locations unless it's UF but who in their right mind would run bigger pipe and struggle with romex pulls...
@adielawson6854 Жыл бұрын
I always use pvc Condit and wet location boxes for basements espically on block wall
@marcdich Жыл бұрын
Yeah, I don’t know so much about that. I agree with you on the mechanical ground but unless you’re basement is really sealed tightly I can see where you might have moisture issues later on, and that eventually is going to roll on that conduit and cause issues with your grounding, I would’ve ran a permanent ground wire as a secondary back up just to be safe
@pld899311 ай бұрын
Dampness or moisture are not going to affect the continuity of a properly installed metal raceway. EMT is installed outdoors every day so in a protected environment, even a potentially damp one, not an issue.
@haroldgreen14252 ай бұрын
A couple of suggestions here. First you need a pair of channel locks. I prefer 430's and they need to be uninsulated. That way you can ream the outside of the pipe with the jaws and ream the inside with the handles. Saves carrying extra tools. You can also tighten the connectors with those same channel locks. I would never use payne hangers on an exposed wall as they are a hang up issue from the ears stuck out. Learn to bend box offsets on that half inch emt. It's very easy to do. Then you can use one hole straps to support the pipe and nothing sticks out. Also you need a strap within eight inches of each box and if you're using a full joint of pipe you'll likely need a third strap in the middle for support. There's nothing wrong with the way you made up the dual outlets in the industrial covers but most of us find it easy to tie the two outlets together first and only have one set of wires to connect to the feed. In a damp location like a basement I'd also suggest you toss those wago's and learn to use a quality wirenut correctly. It will make a far better connection for long term use. And as others have told you you need a good ground wire running through the pipe even though you have a sound mechanical connection a continuous ground wire is better.
@pld89932 ай бұрын
EMT requires support within 3' of a box, not 18". Only damp basements are damp locations, which means visible moisture. Most basements are dry locations. EMT is fine as a ground and a wire type ground is not required, or better.
@haroldgreen14252 ай бұрын
@@pld8993 Thanks for the laugh. By the way I've seen inspectors grab a connector and twist it as hard as they could by hand. If it turned at all they failed the inspection.
@pld89932 ай бұрын
@@haroldgreen1425 Yeah, laugh. They should fail it. Hand tightened fittings is an improper installation and an NEC violation.
@tmiklos4 Жыл бұрын
I only ever use pigtails going from one outlet to the next. Wires in go to the first outlet pig tailed to the next. Then out to the next box. I learned back in the 1980s and have been doing electrical work for nearly 40 years. I now use waggo but i don't use them unless absolutely needed. I like my boxes to be clean. All of the pigtails make a crowded box. Also i onl yh use drawn boces. They work well in cinder block i have no issues what so ever with drawn boxes. . in 40 years i have only has a few items that i had to change for inspectors. And only one was an actual code issues, the others were preference items of inspectors not actually a code issue. ( Which were 100% BS). That is very annoying both with electrical and building ( structural ) inspections.
@EfficientRVer Жыл бұрын
He wasn't saying to not use a drawn box. He was saying to use a box with the 2 screws at the corners of the box, not the 4 screws where devices screw to regular boxes in the wall.
@TwilightxKnight13 Жыл бұрын
if you are suggesting to "daisy chain" your devices, that is no longer permitted (by Code). Just because something works and you have been doing it that way for years does not make it correct or "best practice."
@shidfard Жыл бұрын
@@TwilightxKnight13 You can daisy chain receptacles. You can't daisy chain them on a MWBC. Hit the code book a little harder.
@scotts4125 Жыл бұрын
I always used a hammer drill for Tapcons. I don't believe it's the impact driver that strips them. I am sure they were already stripped. I met a low voltage guy. I have met many in my life but this guy is the best at what he does that I have ever seen. His advice was to stop using a hammer drill and use a regular drill with a masonry bit. He said since he stopped using a hammer drill he rarely has them strip. He also uses a regular drill for larger holes in masonry so he doesn't get the exit hole blow outs. We are in Florida so it's mostly block with stucco over it. The exit holes can make huge blowouts. I stripped many Tapcon holes in my life. Since not using the hammer drill I haven't had even one strip. If they do strip adding a stripped wire in the hole usually works to grab the Tapcon.
@tonycoraccio3514 Жыл бұрын
Great tip ,thank you
@jamesa8851 Жыл бұрын
Tapcons are one of the most frustrating useless fasteners. Just get a pack of plastic anchors with matching screws. Change your life.
@scotts4125 Жыл бұрын
You aren’t wrong they are a PITA but I like them better than plastic anchors. If they don’t strip they are great. Try using them without the hammer drill major success rate increase.
@lawcohn281511 ай бұрын
Bent drill bit and going too fast is the problem. I use SDS rotary hammer all the time. No problems, trick is slow down and don't bend the bit. Your shoulder will hate using a regular drill if you do this alot
@donl1410 Жыл бұрын
Pretty good job. But you should have installed the Minerallac conduit hangers since you didn't bend box offsets or use offset box connectors for the EMT. The EMT must be supported.
@aurvaroy6670 Жыл бұрын
Isn't EMT already supported by the boxes and/or panel?
@KameraShy Жыл бұрын
@@aurvaroy6670Not enough. Code requires support.
@aurvaroy6670 Жыл бұрын
@@KameraShy Yes I know code requires it but do you know why it does? Cause I don't
@TwilightxKnight13 Жыл бұрын
@@aurvaroy6670 box connections are not considered supporting by the Code. You must physically support the conduit no further than three feet from any connection and every ten feet in a horizontal run.
@aurvaroy6670 Жыл бұрын
@@TwilightxKnight13 But why?
@dennisbrown496610 ай бұрын
hello and thank you for the excellent video.metal emt is a good conducter for as your ground but in all my years as working with electric i always recomend running a green line as a posative ground in emt from outlet to back to service panel only as an additional safety to avoid conduit run seperation.again thank you for the video. mr dennis brown
@jayztoob9 ай бұрын
Not required, but it's a good idea to use other than the center knockouts in the 1900 boxes. It'll give you more room for wiring, and might be necessary if you put a dimmer or a 50amp receptacle in one in the future. There's reasons apprentice electricians usually have to prove 10,000 hours working with licensed electricians plus 5 years of school before they can even apply to take the licensing exam. All the good comments pretty well point this out.
@SlackMaster Жыл бұрын
That panel is coming off the wall. Notice the gap at the top. Also, like others mentioned, don't fasten to the mortar. That's probably what happened to the panel as well.
@KameraShy Жыл бұрын
No offset bends at the boxes??? 😞
@Russianmafia10 Жыл бұрын
The supports he's using holds it farther from the wall anyway. For diy it's not really necessary anyway
@donl1410 Жыл бұрын
If he had used the Minies, that would have satisfied the lack of an offset. When that job is inspected, he'll be adding them to provide the necessary conduit support as well. Offset EMT connectors are also available.
@davewalker992611 ай бұрын
I think best practice would be to always use the insulated green ground wire so as not to depend on grounding continuity through metal conduit connections, which can become loose over time. Also, I would never use WAGO lever nuts, particularly on circuits where the loads might be heavy; not just my opinion - see plenty of comments on other KZbin pro channels about WAGO lever nuts.
@darryldodge838311 ай бұрын
Agree about Wago , they are junk. Ordered a bunch from Amazon and found they DO NOT stay closed ! Sent them all back rather Quickly for a refund. 3M Push -In connectors Very Good as a quick-wire alternative.
@brewer1321010 ай бұрын
Run the earth/ground wire...belts and suspenders. I've seen too many electrical boxes in environments like this (garage, etc.) where they're constantly knocked in to, and over time the conduit fittings become loose to the point where you can't rely on them as a ground path.